An autoCAD layout of a Fire Sprinkler System
SECTION BCQ102.
SEC. 903.1.2 OF NYC BUILDING CODE.
QUICK-RESPONSE OR RESIDENTIAL SPRINKLERS ALL SPRINKLERS IN A
3.
COMPARTMENTED SPACE SHALL BE CHANGED. SEC. 8.3.3.4 OF NFPA
APPROVED AUTOMATIC SPRINKLER SYSTEMS IN NEW BUILDINGS AND
WHEN EXISTING LIGHT HAZARD SYSTEMS ARE CONVERTED TO USE
STRUCTURES SHALL BE PROVIDED IN THE LOCATIONS DESCRIBED IN SEC.
13-2016.
903.2 OF NYC BUILDING CODE.
3.
4.
SHALL BE INSTALLED IN SPECIFIC LOCATIONS AS REQUIRED BY SEC. 8.3.2
AUTOMATIC SPRINKLER SYSTEMS SHALL BE DESIGNED AND
SPRINKLERS OF INTERMEDIATE AND HIGH TEMPERATURE RATINGS
3.
18" MINIMUM CLEARANCE TO BELOW SPRINKLER DEFLECTOR AS PER
SECTION 8.5.6 OF APPENDIX Q SECTION BCQ102.
4.
SPACING AND LOCATION OF SPRINKLERS SHALL COMPLY WITH CHAPTER 8
OF APPENDIX Q SECTION BCQ102.
5.
SPRINKLER SYSTEM COMPLIES WITH NFPA 13 2016 AS MODIFIED BY
APPENDIX Q SECTION BCQ102.
INSTALLED IN ACCORDANCE WITH SEC. 903.3.1. THROUGH 903.3.7 OF
OF NFPA 13-2016.
NYC BUILDING CODE.
4.
5.
ACCORDANCE WITH THE REQUIREMENTS OF SECTION 8.5.
7.
BUILDING OR PORTION THERE OF BE EQUIPPED THROUGHOUT WITH AN
5.
OF APPENDIX Q SECTION BCQ102.
AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SEC. 903.3.1.1,
SHALL COMPLY WITH TABLE 8.6.2.2.1 (11/16) (b) (c) (13/16) OF NFPA 13-2016.
SPRINKLERS SHALL BE INSTALLED THROUGHOUT IN ACCORDANCE WITH
6.
WHERE THE PROVISIONS OF NYC BUILDING CODE REQUIRE THAT A
SPRINKLERS SHALL BE LOCATED, SPACED AND POSITIONED IN
PROTECTION AREAS AND MAXIMUM SPACING FOR EACH HAZARD
REQUIREMENTS OF DWELLING UNITS PROTECTIONS SHALL COMPLY
6.
SOURCES OF WATER SUPPLY FOR SPRINKLER SYSTEMS AS PER CHAPTER
23 OF APPENDIX Q SECTION BCQ102.
PIPE SCHEDULE SYSTEMS SHALL BE IN ACCORDANCE WITH SECTION 22.5
8.
AUTOMATIC INTERLOCK CUTOFF SWITCH FOR VENTILATION WILL CONFORM
TO CHAPTER 6 OF THE MECHANICAL CODE (APPLICABLE ONLY IF THERE IS AN AIR
NFPA 13 MODIFIED IN APPENDIX Q EXCEPT AS PROVIDED IN SEC.
WITH SEC. 8.15.8 OF NFPA 13-2016.
SYSTEM UTILIZING RECIRCULATED AIR AND REQUIRING A THERMOSTATIC
- OF NYC BUILDING CODE.
7.
DEVICE).
6.
SEC. 8.15.16 OF NFPA 13-2016.
AUTOMATIC SPRINKLERS SHALL NOT BE REQUIRED IN THE ROOMS OR
REQUIREMENTS OF STAGES AREA PROTECTION SHALL COMPLY WITH
AS AN APPROVED AUTOMATIC FIRE DETECTION SYSTEM IN ACCORDANCE
BE SIZED AS SHOWN IN TABLE 8.16.2.4.2 OF APPENDIX Q-NYC BUILDING
WITH SECTIONS 903.3.1 THROUGH SECTION 904.
CODE.
7.
9.
SPRINKLERS SHALL NOT BE OMITTED FROM ANY ROOM MERELY
TYPES OF HANGERS SHALL BE IN ACCORDANCE WITH THE
UPON OR TO BE CONSIDERED AS EITHER BEING APPROVED OR IN ACCORDANCE
WITH APPLICABLE CODES.
12.
PIPE AND FITTINGS TO BE BLACK STEEL SCHED. 10 OR 40 AND TO COMPLY
WITH NFPA 13 6.3
13.
WATER FLOW ALARMS TO COMPLY WITH NFPA 13 6.9
INSTALLED THROUGHOUT IN ACCORDANCE WITH NFPA 13R AS MODIFIED IN
SHALL COMPLY WITH TABLE 11.2.3.1.2 OF NFPA 13-2016.
14.
ALL HANGERS SHALL COMPLY WITH NFPA 13 CHAPTER 9
APPENDIX Q 903.3.1.2 OF NYC BUILDING CODE.
12.
15.
PROVIDE SEISMIC BRACING WHERE REQUIRED I.A.W. NFPA 13 9.3.1.2
9.
DENSITY/AREA CURVE, FIGURE 11.2.3.1.1 OF NFPA 13-2016.
16.
PUMP ROOM SHALL COMPLY WITH NFPA-
THE WATER SUPPLY FOR SPRINKLERS SHALL BE DETERMINED BY
13.
HYDRAULIC DESIGN AREA REDUCTION FOR QUICK RESPONSE
SPRINKLERS SHALL BE INSTALLED IN THE AREAS LISTED SEC. 903.3.2 OF
SPRINKLERS SHALL COMPLY WITH FIGURE- OF NFPA 13-2016.
NYC BUILDING CODE.
14.
CALCULATIONS FOR DRY SYSTEM WATER DELIVERY SHALL BE BASED
17.
CONTRACTOR SHALL SITE VERIFY ALL DIMENSIONS AND JOB CONDITIONS
AND SHALL REPORT TO ENGINEER ANY DISCREPANCIES OR OMISSIONS THAT
WOULD INTERFERE WITH SATISFACTORY AND EFFICIENT COMPLETION OF THE
ON THE HAZARD SHOWN IN TABLE 7.2.3.6.1 OF NFPA 13-2016.
SPECIFIED WORK.
OBSTRUCTIONS THAT WILL DELAY ACTIVATION OR OBSTRUCT THE WATER
15.
18.
DISTRIBUTION PATTERN. AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN
OF NFPA 13-2016.
OR UNDER COVERED KIOSKS, DISPLAYS, BOOTHS, CONCESSION STANDS,
16.
OR EQUIPMENT THAT EXCEEDS 4 FEET IN WIDTH. NOT LESS THAN 3 FOOT
WITH SEC 12.6 OF NFPA 13-2016.
CLEARANCE SHALL BE MAINTAINED BETWEEN AUTOMATIC SPRINKLERS
17.
AND TOP OF PILES OF COMBUSTIBLE SEC.903.3.3 OF NYC BUILDING CODE.
SEC- OF NFPA 13-2016.
11.
18.
10.
AUTOMATIC SPRINKLERS SHALL BE INSTALLED WITH DUE REGARD TO
WATER SUPPLIES FOR AUTOMATIC SPRINKLER SYSTEM SHALL
DESIGN CRITERIA OF WATER CURTAIN SHALL COMPLY WITH SEC 11.3.3
TYPE OF SPRINKLER HEAD IN GENERAL STORAGE SHALL COMPLY
MINIMUM OPERATING PRESSURE OF ANY SPRINKLER SHALL BE 7 PSL.
NUMBER OF WATER SUPPLY FOR SPRINKLER SYSTEM SHALL COMPLY
COMPLY WITH SEC.903.3.5 OF NYC BUILDING CODE AND SEC. 903.3.1 THE
WITH SEC. 23.1.1 OF NFPA 13-2016 AND APPENDIX Q OF NYC BUILDING CODE.
POTABLE WATER SUPPLY SHALL BE PROTECTED AGAINST BACK FLOW IN
19.
ACCORDANCE WITH THE REQUIREMENTS OF SEC. 608.16.4 OF THE NYC
BE PROPERLY INSPECTED, TESTED, AND IN ACCORDANCE WITH NFPA 25
PLUMBING CODE, AND RULES OF THE NYC DEPARTMENT OF
AND NYC FIRE CODE.
ENVIRONMENTAL PROTECTION.
20.
12.
A SECONDARY ON-SITE WATER SUPPLY EQUAL TO THE
HYDRAULICALLY CALCULATED SPRINKLER DEMAND, INCLUDING THE HOSE
STREAM REQUIREMENT, SHALL BE PROVIDED FOR HIGH-RISE
BUILDINGS IN SEISMIC DESIGN CATEGORY "C" OR "D" AS DETERMINED BY
THIS CODE, AND IN ANY HIGH-RISE BUILDING GREATER THAN 300 FEET IN
HEIGHT. THE SECONDARY WATER SUPPLY SHALL HAVE A DURATION NOT
LESS THAN 30 MINUTES AS DETERMINED BY THE OCCUPANCY HAZARD
SECTION BC 903.
21.
APPENDIX Q SECTION BCQ102.
22.
SHALL CONFORM TO SECTION BCQ102.1 SEE 23.2.1 AND 23.1.1 (D).
23.
ALL VALVES CONTROLLING THE WATER SUPPLY FOR AUTOMATIC
APPENDIX Q BCQ102, SEC. 8.16.4 AND 6.2.8.
25.
THE OCCUPANCY OF THE AREAS TO BE SPRINKLERED IN ACCORDANCE
WITH SECTIONS 5.2 AND A.5.2 OF APPENDIX Q SECTION BCQ102.
26.
TEMPERATURES, CRITICAL AIR PRESSURES AND WATER-FLOW SWITCHES
27.
ON ALL SPRINKLER SYSTEMS SHALL BE ELECTRICALLY SUPERVISED BY THE
PROTECTION AGAINST CORROSION, DAMAGE, VALVES, HANGERS, SPRINKLER
ON EACH FLOOR IN HIGH-RISE BUILDINGS.
15.
THE DOCUMENTS OR PORTIONS THERE OF LISTED IN CHAPTER 2 OF
NFPA 13-2016 ARE REFERENCED WITHIN NFPA-13 AND SHALL BE
CONSIDERED PART OF THE REQUIREMENTS OF THIS DOCUMENT.
16.
OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 5 OF
NFPA-.
PROTECTION REQUIREMENTS FOR MIXED COMMODITIES SHALL BE IN
UNLESS SPECIFICALLY STATED OTHERWISE, CONTRACTOR SHALL FOLLOW
MANUFACTURERS DIRECTIONS, INSTRUCTIONS AND RECOMMENDATIONS
FOR ALL MATERIALS AND PROCESSES USED IN THIS CONTRACT.
SPRINKLER & STANDPIPE PIPE PAINTING NOTES
SPRINKLER AND STANDPIPE SYSTEMS SHALL BE PAINTED
PURSUANT TO NYC BUILDING CODE SECTION 903.6.1,
903.6.1, 903.6.2, 903.6.3, 903.6.4, 903.6.5 AS FOLLOWS:
-
COMBINATION SPRINKLER AND STANDPIPE VALVE
HANDLES SHALL BE PAINTED YELLOW
-
SPRINKLER CONTROL VALVE HANDLES SHALL BE
PAINTED GREEN
-
SPRINKLER AND STANDPIPE RISERS SHALL BE
PAINTED RED
-
SPRINKLER AND STANDPIPE CROSS CONNECTIONS
SHALL BE PAINTED RED
-
STANDPIPE FEED MAINS SHALL BE PAINTED RED
-
STANDPIPE CONTROL VALVE HANDLES SHALL BE
PAINTED RED
WATER SUPPLY TEST PIPES AND GAUGES SHALL BE PROVIDED AS PER
SECTION 8.17.1 OF APPENDIX Q SECTION BCQ102.
VALVES SHALL BE PROVIDED AT THE POINT OF CONNECTION TO THE RISER
20.
INSPECTIONS AND TESTS OF SPRINKLERS SHALL BE CONDUCTED AS PER
SPRINKLER SYSTEMS, PUMPS, TANKS, WATER LEVELS AND
FIRE ALARM SYSTEM. APPROVED SUPERVISED INDICATING CONTROL
HYDROSTATIC TEST SHALL CONFORM WITH NFPA-
SPRINKLER SHALL BE PROTECTED AGAINST FREEZING AND INJURY AS PER
SEC. 901.5 AND APPENDIX Q, SEC. BCQ102, CH. 24.
14.
19.
DIRECT CONNECTION OF SPRINKLERS TO THE PUBLIC WATER SYSTEM
24.
DEPARTMENT HOSE THREADS.
APPROVALS
ONLY APPROVED MATERIALS SHALL BE USED AS PER CHAPTER 6 OF
13.
SPRINKLER SYSTEMS SHALL BE APPROVED AND COMPATIBLE WITH FIRE
SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS AND
AND TYPE OF SYSTEMS SHALL CONFORM TO APPENDIX Q, SECTION BC Q102 AND
CLASSIFICATION IN ACCORDANCE WITH NFPA 13-2016.
FIRE HOSE THREADS USED IN CONNECTION WITH AUTOMATIC
DEPARTMENT AND REGULATORY AGENCIES AND CODE REQUIREMENTS, AND
A SPRINKLER SYSTEM IN ACCORDANCE WITH THIS STANDARD SHALL
THE INSTALLATION COMPONENT, SIZING, SPACING, CLEARANCES, POSITION
CONTRACTOR SHALL COMPLY WITH ALL NEW YORK CITY BUILDING
FIRE SPRINKLER SYMBOL ABBREVIATION
PIPING, FITTINGS, SPECIFICATIONS, PIPE SCHEDULES, SYSTEM TEST PIPES,
SYMBOL
DESCRIPTION
GUARDS AND SHIELDS SHALL BE AS PER APPENDIX Q SECTION BCQ102,
SPRINKLER ALARM WILL BE IN ACCORDANCE WITH SECTION 8.17.1 OF
APPENDIX Q SECTION BCQ102.
30.
EXISTING SPRINKLER PIPING TO REMAIN
FOR CONVENIENCE ONLY. NOT EVERY SYMBOL OR
SPRINKLER PIPING DOWN
ABBREVIATION IS NECESSARY USED.
SPRINKLER PIPING DOWN
SPACING, LOCATION AND POSITION OF SPRINKLER WILL BE AS PER SECTION
SPRINKLER PIPING UP
8 OF APPENDIX Q SECTION BCQ102.
31.
ALL BLIND SPACES EXCEEDING 6" IN WIDTH OR DEPTH WHICH CONTAIN
EXISTING HEAD
ALL PIPING PASSING THROUGH WALLS WILL COMPLY WITH SECTION BC712.
EXISTING HEAD
18.
33.
THERE IS NO HIGH PILED STORAGE AS DEFINED IN SECTION 3.9.1.13 OF
CONCEALED PENDENT
19.
THE K-FACTOR, RELATIVE DISCHARGE, AND MARKING IDENTIFICATION
APPENDIX Q SECTION BCQ102.
34.
RESIDENTIAL CONCEALED
DISTANCE OF SPRINKLERS FROM HEAT SOURCE SHALL BE AS PER TABLES
FOR SPRINKLERS HAVING DIFFERENT ORIFICE SIZES SHALL BE IN
8.3.2.5 (a) AND 8.3.2.5 (b).
ACCORDANCE WITH TABLE 6.2.3.1 OF NFPA 13-2016.
35.
20.
LETTER WITH FLOW TEST DATA IF THERE IS A DIRECT CONNECTION TO THE
FLOOR CONTROL VALVE ASSEMBLY
STREET WATER SUPPLY.
WATER FLOW SWITCH
LARGE DROP AND ESFR SPRINKLERS SHALL HAVE A MINIMUM
NOMINAL K-FACTOR OF 14.2.
21.
AUTOMATIC SPRINKLERS SHALL HAVE THEIR FRAME ARMS,
DEFLECTOR, COATING MATERIAL, OR LIQUID BULB COLORED IN
ACCORDANCE WITH REQUIREMENTS OF TABLE 6.2.5.1 OF NFPA-.
LISTED CORROSION RESISTANT SPRINKLERS SHALL BE INSTALLED IN
LOCATIONS WHERE CHEMICALS, MOISTURE, OR OTHER CORROSIVE
36.
CHECK VALVE
THIS APPLICATION IS NOT FILED AS A RESULT OF BY THE FIRE
HYDRAULIC REFERENCE POINT
ALL VALVES SHALL BE IDENTIFIED AS REQUIRED BY SECTION 6-7.4 OF
39.
DRAINAGE SHALL CONFORM TO SECTION 8.16.2 OF APPENDIX Q SECTION
REQUIRED SPECIAL INSPECTIONS
BCQ102. A ONE PIECE REDUCING FITTING OF GOOD DESIGN SHOULD BE USED
PLASTIC IDENTIFICATION SIGNS. SEC. 6.7.4.1 OF NFPA 13-2016.
WHEREVER A CHANGE IS MADE IN THE SIZE OF PIPE, AS PER SECTION 6.4.6 OF
SPRINKLER ARE REQUIRED TO BE INSPECTED IN
24.
APPENDIX Q SECTION BCQ102.
ACCORDANCE WITH 2022 NYC
PLUGS OR CAPS, PROPERLY SECURED AND ARRANGED FOR EASY
40.
ALL VALVES ON CONNECTIONS TO WATER SUPPLY TO SPRINKLER SHALL BE
REMOVAL BY THE FIRE DEPARTMENT SEC. 6.8.2 OF NFPA 13-2016.
APPROVED OS&Y OR APPROVED INDICATOR TYPE.
25.
41.
REQUIREMENTS OF DRY PIPE SYSTEM INSTALLATION SHALL COMPLY
WITH SEC 7.2 OF NFPA-.
REQUIREMENTS OF PREACTION & DELUGE SYSTEM INSTALLATION
SHALL COMPLY WITH SEC. 7.3. OF NFPA-.
OUTSIDE SPRINKLERS FOR PROTECTION AGAINST EXPOSURE FIRE
SHALL COMPLY WITH SEC. 7.8. OF NFPA-.
THE MAXIMUM FLOOR AREA OR ANY ONE FLOOR TO BE PROTECTED
BY A SINGLE RISER FROM A CONTROL VALVE AND ALARM DEVICE SHALL
COMPLY WITH SEC. 8.2.1 OF NFPA 13-2016.
DRAIN VALVES AND TEST VALVES SHALL BE APPROVED TYPE AS PER
SECTION 6.7.3 OF APPENDIX Q SECTION BCQ102.
42.
BUILDING CODE SECTION BC-1705 AS FOLLOWS:
-
SPRINKLER SYSTEM - BC - 1705.29
-
FIRE-RESISTANT, PENETRATION AND JOISTS
SYSTEM - BC - 1705.17
HANGERS SHOULD BE SUPPORTED BY WROUGHT IRON U TYPE OR
APPROVED ADJUSTABLE HANGERS. HANGERS SHALL BE OF THE TYPE APPROVED
RELIABLE RFC49
RA0616 RESIDENTIAL CONCEALED
43.
5.6
7.0 PSI
165°
4.9
7.0 PSI
UL FM
NYC MEA # 258-93-E
UL FM
16X16 (256SF)
NYC MEA # 258-93-E
15X15 (225SF)
BC 1613:
1" SEPARATION REQ. FOR EACH
50' OF BUILDING HEIGHT ON
EACH SIDE
PROPOSED HEIGHT = 54'-6":
PROPOSED SEPARATION = 1"
ADJACENT 2 STORY
& BASMENT
18'-0"
100'-0" LOT
29'-6"
12'-4"
5'-9"
15'-1" SETBACK
14'-11"
15'-1"
14'-7"
STAIR BULKHEAD
1ST
STORY
4 STORIES
OUTER
COURT:
200 SQ. FT.
PROPOSED 4 STORY CELLAR & MEZZANINE
RESIDENTIAL BUILDING
1ST
STORY
2" RPZA
5'-9"
56'-11"
37'-4" REAR YARD
62'-8" BUILDING
ADJACENT 3 STORY
& BASMENT
REV
DESCRIPTION
1
ISSUED FOR FILING
DATE
2/03/26
WHEN THE DOMESTIC WATER IS USED TO SUPPLY SPRINKLERS, ALL OF THE FOLLOWING CONDITIONS SHALL BE MET
1.
THE DOMESTIC WATER SUPPLY LINE FROM THE TANK OR STREET SUPPLY SHALL
6.
BE AT LEAST THE SIZE OF THE SPRINKLER LINE AND THE CAPACITY AVAILABLE
THE NUMBER OF HEADS IN EACH FIRE SECTION SHALL NOT EXCEED TWENTY,
EXCEPT THAT THE NUMBER OF HEADS IN EACH FIRE SECTION MAY EXCEED
SHALL BE AT LEAST EQUAL TO THE CAPACITY REQUIRED FOR THE SPRINKLERS.
TWENTY IN BUILDINGS CLASSIFIED IN OCCUPANCY GROUP R-2, OR R-3 NOT
2.
THE DOMESTIC WATER SUPPLY LINE FROM THE TANK OR STREET SHALL
EXCEEDING SIX STORIES OR 75 FEET (22 860 MM) IN HEIGHT AND IN SPACES
HAVE THE REQUIRED PRESSURE AS PROVIDED IN THIS REFERENCED
CLASSIFIED IN OCCUPANCY GROUP R-2, OR R-3 IN BUILDINGS NOT
STANDARD.
EXCEEDING SIX STORIES OR 75 FEET (22 860MM) IN HEIGHT, PROVIDED THAT NO
MORE THAN 10 HEADS ARE SUPPLIED FROM ANY ONE DOMESTIC WATER RISER.
3.
THE DOMESTIC WATER SUPPLY LINE SHALL BE OF NONFERROUS MATERIAL
EXCEPT WHEN THE DOMESTIC WATER SUPPLY IS FOUR INCHES (102 MM) OR MORE.
7.
THE CONNECTION SHALL BE MADE AT THE SUPPLY OR RISER SIDE OF ANY
DOMESTIC BRANCH CONTROL VALVES.
4.
AN O.S.&Y. VALVE OR OTHER LISTED VALVE HAVING VISUAL INDICATION, AND
SEALED OPEN, SHALL BE INSTALLED IN THE SPRINKLER SUPPLY BRANCH, OR
8.
IN CONNECTION WITH THE ABOVE CONDITIONS, THE NUMBER OF FIRE
SUCH OTHER VALVE ARRANGEMENT AS MAY BE PROVIDED IN THIS REFERENCED
SECTIONS HAVING 20 OR FEWER HEADS MAY BE UNLIMITED; AND THE
STANDARD AND IN REFERENCED STANDARDSNFPA-13R OR NFPA 13-D AS
INSTALLATION OF ALARMS IN BRANCHES SUPPLYING FIRE SECTIONS SHALL BE AT
MODIFIED FOR NEW YORK CITY, AS APPLICABLE.
THE OPTION OF THE OWNER, EXCEPT THAT SUCH ALARMS SHALL BE PROVIDED
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
ADDRESS:
WHERE REQUIRED BY REFERENCED STANDARDS NFPA-13R AND NFPA-13D AS
5.
THE PIPE CONNECTING THE DOMESTIC WATER SUPPLY AND THE SPRINKLER
MODIFIED FOR NEW YORK CITY.
CONTROL VALVE SHALL BE OF NONFERROUS MATERIAL AND NOT LESS THAN
TWELVE INCHES (305 MM) LONG.
9.
A CHECK VALVE SHALL BE INSTALLED ON THE SPRINKLER SUPPLY BRANCH.
114 ADELPHI ST.,
BROOKLYN, NY 10205
DRAWING TITLE:
BULKHEAD
EL (119.08')
2"
ROOF
EL (108.08')
2"
2"
PIPING SYSTEM IN ACCORDANCE WITH NFPA 13
-
POST INSTALLED ANCHORS - BC - 1705.37
DOB:
2"
TO 11 SPRINKLER HEADS
2"
3RD FLOOR
EL (75.08')
3" SINGLE INLET FIRE
DEPARTMENT CONNECTION 18"
MIN. TO 36" MAX. ABOVE GRADE
2"
TO 11 SPRINKLER HEADS
2"
2ND FLOOR
EL (66.08')
2"
NEW YORK CITY ENERGY CONSERVATION CODE.
TO 12 SPRINKLER HEADS
D.O.B. BSCAN:
TO 13 SPRINKLER HEADS
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
2"
1ST FLOOR
EL (53.58')
GRADE
CURB VALVE WITHIN
1'-6" OF CURB LINE
SPRINKLER SYSTEM DESIGN STANDARD:
3"
3"
2"
NYC BC-, NFPA 13R 2016 EDITION
3" CHECK VALVE
WITH AUTO
BALL DRIP MAIN DRAIN
FEMA NOTE:
THIS PROPERTY IS NOT WITHIN THE SPECIAL FLOOD HAZARD AREA (SFHA)
12 CLEARANCE
ON TOP OF BFP
HYDROSTATIC PRESSURE TESTING
SPRINKLER SYSTEMS IN BUILDINGS SHALL UNDERGO SUCCESSFUL
HYDROSTATIC PRESSURE TESTING BY A LICENSED MASTER PLUMBER
OR LICENSED FIRE SUPPRESSION PIPING CONTRACTOR IN
ACCORDANCE WITH THE REQUIREMENTS OF THIS CODE, INCLUDING
SECTION 901.5, NFPA 13 AND NEW YORK CITY LOCAL LAW 63/2009
SCOPE OF WORK
INSTALL WET SPRINKLER SYSTEM IN THE ENTIRE BUILDING AND IN ACCORDANCE WITH
ON END OF A CROSS MAIN AS PER SECTION 8.16.3 OF APPENDIX Q SECTION
NFPA 13R 2016 EDITION AS MODIFIED BY NYC BC 2022 APPENDIX Q AS PER PLAN IN CONJUNCTION
BCQ102.
WITH DOB JOB NUMBER B--I1
SPRINKLER
SYMBOLS, NOTES,
SCHEDULES AND
LEGENDS
TO 3 SPRINKLER HEADS
2"
4TH FLOOR
EL (84.08')
PRESSURE TEST PERFORMED FOR THE ABOVEGROUND
PROFESSIONAL JUDGEMENT, THESE PLANS AND
TO 8 SPRINKLER HEADS
2"
MEZZANINE
EL (96.08')
SPRINKLER SYSTEMS SHALL PASS A HYDROSTATIC
TO THE BEST OF MY KNOWLEDGE, BELIEF, AND
TO 2 SPRINKLER HEADS
INSPECTOR
TEST TEE
RELIED UPON, OR TO BE CONSIDERED AS BEING APPROVED OR IN
PROVISIONS SHOULD BE MADE TO FACILITATE FLUSHING SYSTEM PIPING BY
PROVIDING FLUSHING CONNECTION CONSISTING OF A CAPPED NIPPLE 4" LONG
165° / 212°
ROOFED
BALCONY
FOR USE WITH THE PIPE OR TUBE INVOLVED, AS PER CHAPTER 9 OF APPENDIX Q
SECTION BCQ102.
CONCEALED PENDENT
114 ADELPHI ST.,
BROOKLYN, NY 11205
BLOCK: 2044
LOT: 71
ZONE: R6-B
OVERLAY: NONE
COMMUNITY BOARD: 303
USE GROUP: II
OCCUPANCY GROUP: R-2
FIRE SPRINKLER RISER
PROVIDED WITH PERMANENTLY MARKED WEATHERPROOF METAL OR RIGID
FIRE DEPARTMENT CONNECTIONS SHALL BE EQUIPPED WITH LISTED
RA3415
SPECIFICATIONS ARE IN COMPLIANCE WITH THE
NEW CONNECTION TO EXISTING
OCCUPANCY NOR IS SUCH ACTION PENDING.
23.
RELIABLE G5-56
K FACTOR REQUIRED PSI COVERAGE LISTINGS
PROPERTY INFO:
ALL PIPES PASSING THROUGH FOUNDATION WALLS SHALL BE PROTECTED
APPENDIX Q SECTION BCQ102.
TEMPERATURE
TYPE OF HEAD
AS PER NFPA 13R 6.4.2.1
COMMISSIONER AS AUTHORIZED BY BS&A TO MODIFY THE CERTIFICATE OF
38.
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
THE APPLICATION SHEET. ALL OTHER MATTERS SHOWN ARE NOT TO BE
AS PER SECTION BC903.1.2 PROVIDE DEPARTMENT OF WATER SUPPLY
VAPORS SUFFICIENT TO CAUSE CORROSION OF SUCH DEVICES EXIST.
ALL CONTROL, DRAIN, AND TEST CONNECTION VALVES SHALL BE
OS&Y VALVE WITH TAMPER SWITCH
AS PROVIDED BY SECTION 305.5 OF THE PLUMBING CODE.
37.
SIN #
ACCORDANCE WITH APPLICABLE CODES.
32.
COMPONENTS SHALL COMPLY WITH CHAPTER 6 OF NFPA 13-2016.
MFR & MODEL
THESE PLANS ARE APPROVED ONLY FOR THE WORK INDICATED ON
COMBUSTIBLE MATERIAL WILL BE SPRINKLERED.
ACCORDANCE WITH SEC 5.6.1.2 OF NFPA 13-2016.
REQUIREMENTS FOR CORRECT USE OF SPRINKLER SYSTEM
SYMBOL
ENGINEER'S SEAL AND SIGNATURE:
SCHEDULE OF SPRINKLERS
ORIFICE TYPES, UNLESS NOTED OTHERWISE
NOTE : SYMBOL LIST AND ABBREVIATIONS PROVIDED
STOCK EXTRA SPRINKLERS SHALL BE FURNISHED AS PER SECTION 6.2.9
APPENDIX Q SECTION BCQ102 (REQUIRED FOR EACH TEMPERATURE RATING)
29.
SPRINKLER - PIPE SCHEDULES AND DETAILS
NEW SPRINKLER PIPING
CHAPTERS 6 AND 9.
28.
SP-006.00
NEW 2" COMBINED WATER
SERVICE
BUILDING CODE, QUICK-RESPONSE OR RESIDENTIAL AUTOMATIC
SPRINKLER - ROOF AND BULKHEAD FLOOR PLAN
X EL. 53.66
SIX STORIES IN HEIGHT, AUTOMATIC SPRINKLER SYSTEM SHALL BE
11.
WHERE AUTOMATIC SPRINKLER SYSTEM ARE REQUIRED BY NYC
HOSE STREAM DEMAND AND WATER SUPPLY DURATION EQUIREMENT
SPECIFICATION SHEET. ALL OTHER MATTERS SHOWN ARE NOT TO BE RELIED
SP-005.00
X TC. 53.41
8.
TABLES 9.2.2.1 OF NFPA 13-2016.
WHERE ALLOWED IN BUILDING OF GROUP R, UP TO AND INCLUDING
MAXIMUM DISTANCE BETWEEN HANGERS SHALL COMPLY WITH
THIS APPLICATION IS MADE ONLY FOR WORK INDICATED ON THE
SPRINKLER - 4TH AND MEZZAINE FLOOR PLAN
EXISTING TREE X BC. 53.17
10.
11.
SP-004.00
X BC. 53.58
CONTAINS ELECTRICAL EQUIPMENT.
MINIMUM BRANCH PIPE SIZE TO BE ONE INCH (1").
SPRINKLER - 2ND AND 3RD FLOOR PLAN
X TC. 53.76
REQUIREMENT OF SEC. 9.1. OF NFPA 13-2016.
ACCORDANCE WITH CHAPTER 22 OF APPENDIX Q SECTION BCQ102.
10.
SP-003.00
X EL. 53.74
BECAUSE IT IS DAMP, OR FIRE-RESISTANCE-RATED CONSTRUCTION OR
DRAIN CONNECTIONS FOR SYSTEM SUPPLY RISERS AND MAINS SHALL
SPRINKLER - CELLAR AND 1ST FLOOR PLAN
EXISTING WATER MAIN
8.
HYDRAULICALLY DESIGNED SPRINKLER SYSTEMS SHALL BE IN
CLG
CO
CFP
CONC
CONN
CV
°C
DIA
DIAG
DISCH
DN
DWG
ELEV
EQ
EQUIP
EQUIV
EX
EXT
°F
FAI
FD
FH
FHC
FHR
FKC
FL
FLEX
FLR
FP
FPM
FSP
FT
GA
GALV
GC
GPD
GPH
GPM
GV
HC
HD
HR
HTR
ID
INCL
JP
LHSC
MAX
MFR
MIN
MISC
MTD
(N)
N.A.S.
NC
NIC
No
NO
NPW
NOM
NTS
OPG
OS&Y
PEX
PIV
PO
POS
PRESS
PS
PSI
PSIG
PSIA
PV
PVC
QTY
RCV
REQ
RM
RPZ
SCH
SCV
SPEC
STD
SYS
TDH
TEMP
TS
TYP
V
VO
W
WF
WM
SP-002.00
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-
NEW 2" CURB VALVE WITHIN
1'-6" OF CURB LINE
AREAS WHICH ARE LISTED IN- OF NYC BUILDING CODE AS LONG
9.
℄
SPRINKLER - SYMBOLS, NOTES, SCHEDULE, LEGEND
(70' WIDE)
2.
CONSTRUCTION DOCUMENTS FOR STANDPIPE SYSTEMS SHALL
SP-001.00
ADELPHI STREET
CONTAIN PLANS THAT INCLUDE THE INFORMATION AND DATA LISTED IN
2.
TEMPERATURE RATING SHALL COMPLY WITH SECTION 8.3 OF APPENDIX Q
DRAWING INDEX TITLE
1"
SPRINKLERS SHALL BE PERMITTED TO BE USED SEC.8.3.3. OF NFPA 13-2016.
DWG NO.
25'-0" LOT
APPENDIX Q SECTION BCQ102.
2.
ABOVE
AUTOMATIC BALL DRIP
ACCESS DOOR
ABOVE FINISHED FLOOR
BACK FLOW PREVENTER
BUILDING
BELOW
CELLAR
CAST IRON
CENTER LINE
CEILING
CLEAN OUT
COMBINED SPRINKLER
CONCRETE
CONNECTION
CHECK VALVE
DEGREES CENTIGRADE
DIAMETER
DIAGRAM
DISCHARGE
DOWN
DRAWING
ELEVATION
EQUAL
EQUIPMENT
EQUIVALENT
EXISTING
EXTERNAL
DEGREES FAHRENHEIT
FRESH AIR INLET
FLOOR DRAIN
FIRE HYDRANT
FIRE HOSE CABINET
FIRE HOSE RACK
FIRE KEY CABINET
FLANGE
FLEXIBLE
FLOOR
FIRE PROTECTION
FEET PER MINUTE
FIRE STANDPIPE
FEET
GAUGE
GALVANIZED
GENERAL CONTRACTOR
GALLONS PER DAY
GALLONS PER HOUR
GALLONS PER MINUTE
GATE VALVE
HUNG CEILING
HEAD
HOUR
HEATER
INTERNAL DIAMETER
INCLUDING
JOCKEY PUMP
LOBBY HOSE STORAGE CABINET
MAXIMUM
MANUFACTURER
MINIMUM
MISCELLANEOUS
MOUNTED
NEW
NO AUTOMATIC SPRINKLERS
NORMALLY CLOSED
NOT IN CONTRACT
NUMBER
NORMALLY OPEN
NON-POTABLE WATER
NOMINAL
NOT TO SCALE
OPENING
OUTSIDE SCREW & YOKE
CROSS LINKED POLYETHYLENE TUBING
POST INDICATOR VALVE
PLUGGED OUTLET
POSITIVE
PRESSURE
PRESSURE SWITCH
POUNDS PER SQUARE INCH
POUNDS PER SQUARE INCH GAUGE
POUNDS PER SQUARE INCH ABSOLUTE
PLUG VALVE
POLYVINYL CHLORIDE
QUANTITY
RISER CONTROL VALVE
REQUIRED
ROOM
REDUCED PRESSURE ZONE BACKFLOW PREVENTER
SCHEDULE
SPRINKLER CONTROL VALVE
SPECIFICATION
STANDARD
SYSTEM
TOTAL DYNAMIC HEAD
TEMPERATURE
TAMPER SWITCH
TYPICAL
VENT
VALVED OUTLET
WASTE
WATER FLOW SWITCH
WATER METER
24'-10" BUILDING
ORDINARY TEMPERATURE-RATED SPRINKLERS, STANDARD RESPONSE
APPENDIX Q OF NYC BUILDING CODE & NFPA 13R-2016.
ABV
ABD
AD
AFF
BFP
BLDG
BLW
BSMT
CI
1"
SPRINKLER SHALL BE AN APPROVED TYPE AS PER SECTION 8.3 OF
545.04' TO CORNER
1.
13'-3"
WHERE CIRCUMSTANCES REQUIRE THE USE OF OTHER THAN
11'-8" DORMER
1.
FIRE SPRINKLER DRAWING INDEX
ABBREVIATIONS
14'-0"
AUTOMATIC SPRINKLER SYSTEM SHALL COMPLY WITH SEC. 903 &
NEW YORK CITY SPRINKLER NOTES 3 OF 3
10'-10"
1.
NEW YORK CITY SPRINKLER NOTES 2 OF 3
25'-0" LOT
NEW YORK CITY SPRINKLER NOTES 1 OF 3
LETTER OF NOTIFICATION
CURB
VALVE
OWNER SHALL NOTIFY FDNY OF SPRINKLER SYSTEM
SUBMITTING A LETTER OF NOTIFICATION
DOMESTIC SHUT-OFF VALVE
2" TO DOMESTIC
MICV
30" MIN. FROM FLOOR
DISCONNECTIONS OR REMOVAL FROM SERVICE OF
EXISTING SPRINKLER SYSTEMS BY
CHECK VALVE
MOCV
TEST "T"
CELLAR
EL (42.58')
2"RPZA
RELATED JOB NUMBERS
ALTERATION CO.
B--I1
PRESSURE GUAGE
WATER FLOW SWITCH
(COORDINATE ELECTRICAL
CONTRACTOR)
SERVICE
CONTROL VALVE
CITY MAIN SOURCE
NEW 2" COMBINED
WATER SERVICE
2"
1
SP
TYCO RSV-2 TO PREVENT FLOW
ON THE DOMESTIC WATER
SYSTEM UPON OPERATION OF
SPRINKLERS. BC Q104 6.5.3
DOB JOB NO:
SPILL OVER TO NEAREST
FLOOR DRAIN
DRAWING NO:
NEW 4" F.D. TO HOUSE
SEWER BY GRAVITY
WITHIN 5' OF RPZA
FOR SPRINKLER ONLY
SCOPE OF WORK DOES NOT AFFECT THE ENERGY USE OF THIS BUILDING
SPRINKLER PROPOSED RISER DIAGRAM
NOT TO SCALE
2/4/2026
AS NOTED
SP-001.00
PAGE 1 OF 6
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-" RISER UP/DN
ENGINEER'S SEAL AND SIGNATURE:
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
3" FDC RISER UP
3" SINGLE INLET FIRE
DEPARTMENT CONNECTION
18" MIN. TO 36" MAX.
ABOVE GRADE
REV
DESCRIPTION
1
ISSUED FOR FILING
DATE
2/03/26
APT
APT
1A
1B
1ST FLOOR - FIRE SPRINKLER PLAN
SPRINKLER TOTAL HEAD COUNT PER FLOOR
12 SPRINKLER HEADS
SCALE: 1/4"=1'-0"
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
ADDRESS:
114 ADELPHI ST.,
BROOKLYN, NY 10205
2" RISER UP
DRAWING TITLE:
3" FDC RISER UP
SPRINKLER
CELLAR AND 1ST FLOOR
PLAN
DOB:
3" CHECK VALVE WITH
AUTO BALL DRIP
D.O.B. BSCAN:
NEW 2" COMBINED
WATER SERVICE TO
CITY MAIN
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
CITY MAIN SOURCE
CELLAR FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
SPRINKLER TOTAL HEAD COUNT PER FLOOR
13 SPRINKLER HEADS
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
AS NOTED
2/4/2026
DOB JOB NO:
DRAWING NO:
SP-002.00
PAGE 2 OF 6
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-" RISER
ENGINEER'S SEAL AND SIGNATURE:
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
REV
DESCRIPTION
1
ISSUED FOR FILING
DATE
2/03/26
APT
3A
APT
3B
3RD FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
SPRINKLER TOTAL HEAD COUNT PER FLOOR
11 SPRINKLER HEADS
2" RISER UP
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
ADDRESS:
114 ADELPHI ST.,
BROOKLYN, NY 10205
2" RISER UP/DN
DRAWING TITLE:
SPRINKLER
2ND AND 3RD FLOOR
PLAN
DOB:
APT
APT
2A
D.O.B. BSCAN:
2B
2ND FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
SPRINKLER TOTAL HEAD COUNT PER FLOOR
11 SPRINKLER HEADS
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
2/4/2026
AS NOTED
DOB JOB NO:
DRAWING NO:
SP-003.00
PAGE 3 OF 6
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-" RISER UP
ENGINEER'S SEAL AND SIGNATURE:
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
REV
DESCRIPTION
1
ISSUED FOR FILING
MEZZANINE FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
SPRINKLER TOTAL HEAD COUNT PER FLOOR
8 SPRINKLER HEADS
2" RISER
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
DATE
2/03/26
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
ADDRESS:
114 ADELPHI ST.,
BROOKLYN, NY 10205
DRAWING TITLE:
SPRINKLER
4TH AND MEZZANINE
FLOOR PLAN
DOB:
APT
D.O.B. BSCAN:
4A
4TH FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
2" RISER UP/DN
SPRINKLER TOTAL HEAD COUNT PER FLOOR
3 SPRINKLER HEADS
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
2/4/2026
AS NOTED
DOB JOB NO:
DRAWING NO:
SP-004.00
PAGE 4 OF 6
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-
ENGINEER'S SEAL AND SIGNATURE:
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
REV
DESCRIPTION
1
ISSUED FOR FILING
BULKHEAD FLOOR - FIRE SPRINKLER PLAN
DATE
2/03/26
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
SCALE: 1/4"=1'-0"
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
ADDRESS:
114 ADELPHI ST.,
BROOKLYN, NY 10205
2" RISER W/
INSPECTION TEST TEE
DRAWING TITLE:
SPRINKLER
ROOF AND BULKHEAD
FLOOR PLAN
DOB:
D.O.B. BSCAN:
ROOF FLOOR - FIRE SPRINKLER PLAN
SCALE: 1/4"=1'-0"
SPRINKLER TOTAL HEAD COUNT PER FLOOR
2 SPRINKLER HEADS
PIPE SIZE TO BE MINIMUM 1" UNLESS OTHERWISE NOTED
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
2/4/2026
AS NOTED
DOB JOB NO:
DRAWING NO:
SP-005.00
PAGE 5 OF 6
PRECISION ENGINEERING GROUP DPC
130 LEE AVENUE #101
BROOKLYN, NY 11211
P:-
HYDRANT FLOW TEST REPORT LETTER
ENGINEER'S SEAL AND SIGNATURE:
1 1/2"x2" REDUCING TEE OR
ELBOW
WALL CONSTRUCTION VARIES
NOT VALID FOR CONSTRUCTION WITHOUT AN ENGINEER SEAL
FINISHED WALL SURFACE
TERMINATE SLEEVE FLUSH
WITH FINISHED WALL SURFACE
2 5/8" DIA.
CEILING HOLE
SPRINKLER
CUP
ASSEMBLY
1" BRANCH LINE
SEAL & CAULK SLEEVES THRU
FIRE WALLS IN A SMOKE TIGHT
MANNER. REFER TO SPECIFICATIONS
FOR RATED CAULK TYPE.
PIPE
2 5/8" FACE OF FITTING
TO CEILING DIMENSION
MAX.
CASTING
1/2" CLEARANCE MAXIMUM
STANDARD WEIGHT STEEL PIPE
SLEEVE TO PASS PIPE
SPRINKLER BRANCH
CONCEALED TYPE
SPRINKLER HEAD
FINISHED ESCUTCHEON PLATE
FLUSH AGAINST WALL AND OF SIZE
TO COMPLETELY COVER OPENING
(TYP. FOR EACH SIDE)
COVER PLATE
ASSEMBLY
1/2" COVER
MAX. ADJUSTMENT
REV
DESCRIPTION
1
ISSUED FOR FILING
DATE
2/03/26
HUNG CEILING
3 5/16" DIA.
CL
1
3/16"
CONCEALED PIPING
TYPICAL SPRINKLER ARM OVER DETAIL
2
NOT TO SCALE
TYPICAL CONCEALED SPRINKLER HEAD DETAIL
NOT TO SCALE
3
PIPING EXPOSED TO VIEW
TYPICAL DETAIL OF PIPE INSTALLATION THROUGH RATED WALL
NOT TO SCALE
THE ENGINEER SHALL NOT HAVE CONTROL OR CHARGE OF
AND SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION
MEANS, METHODS, DEVIATIONS, TECHNIQUES, SEQUENCES,
OR PROCEDURES, OR FOR SAFETY PRECAUTIONS AND
PROGRAMS IN CONNECTION WITH THE WORK, FOR THE
ACTS OR OMISSIONS OF THE CONTRACTOR,
SUBCONTRACTORS OR ANY OTHER PERSONS PERFORMING
ANY OF THE WORK, OR FOR THE FAILURE OF ANY OF THEM
TO CARRY OUT THE WORK IN ACCORDANCE WITH THE
CONTRACT DOCUMENTS. ALWAYS USE DIMENSIONS AS
SHOWN. DRAWINGS ARE NOT TO BE SCALED.
EXISTING WF STEEL MEMBER OR
SUPPLEMENTAL STEEL AS REQUIRED
BY PROJECT CONDITIONS
THE GENERAL CONTRACTOR SHALL VERIFY ALL
DIMENSIONS AND REPORT ALL ERRORS AND OMISSIONS TO
THE ENGINEER. DO NOT SCALE THE DRAWING. THIS
DRAWING SHALL NOT BE USED FOR CONSTRUCTION
PURPOSES UNTIL SIGNED AND SEALED BY THE ENGINEER.
"C" CLAMP
CONCRETE ANCHOR HILTI-KWICK BOLT
SERIES HDL, OR APPROVED EQUAL.
INSTALLATION SHALL BE IN ACCORDANCE
WITH THE MANUFACTURER'S
RECOMMENDATION AND APPROVAL OF
STRUCTURAL ENGINEER.
ALL WORK IS TO BE DONE IN ACCORDANCE WITH NYC DOB
REQUIREMENTS & INSTALLATION SHALL BE PERFORMED
BY A NFPA ACCREDITED CONTRACTOR.
METAL DECK OR CONCRETE SLAB
ADDRESS:
STEEL RETAINING STRAP
COUPLER
ROD (SIZE AS REQUIRED)
NOT PERMITTED WHERE SPECIFICALLY
ADDRESSED IN THEIR DOCUMENTS
114 ADELPHI ST.,
BROOKLYN, NY 10205
COUPLER
*CLEVIS HANGER
DRAWING TITLE:
NOTES:
1. CLEVIS HANGERS REQUIRED ON PIPING LARGER THAN 1"
2. GENERAL PURPOSE HANGERS MAY BE USED ON 1" SPRINKLER
PIPING ONLY.
4
TYPICAL HANGER DETAIL
5
NOT TO SCALE
TYPICAL WOOD HANGER DETAIL
NOT TO SCALE
6
FIRE DEPARTMENT CONNECTION DETAIL
PIPE SCHEDULES AND
DETAILS
NOT TO SCALE
DOB:
ORDINARY TEMPERATURE-RATED SPRINKLERS (135° F TO 170° F)
SHALL BE INSTALLED MAXIMUM AMBIENT CEILING
TEMPERATURES DO NOT EXCEED 100° F.
HANGER ROD SPACING AND SIZE SCHEDULE
RESIDENTIAL SPRINKLERS (Table 8.3.2.5(c) NFPA 13)
SIDE OF OPEN OR RECESSED FIREPLACE
36 in
FRONT OF RECESSED FIREPLACE
60 in
COAL- OR WOOD-BURNING STOVE
42 in
KITCHEN RANGE
18 in
WALL OVEN
18 in
HOT AIR FLUES
18 in
UNINSULATED HEAT DUCTS
18 in
UNINSULATED HOT WATER PIPES
12 in
SIDE OF CEILING- OR WALL-MOUNTED HOT AIR DIFFUSERS
24 in
FRONT OF WALL-MOUNTED HOT AIR DIFFUSERS
36 in
HOT WATER HEATER OR FURNACE
6 in
LIGHT FIXTURE:
0 WATTS – 250 WATTS
6 in
250 WATTS - 499 WATTS
12 in
INTERMEDIATE TEMPERATURE SPRINKLERS TO BE INSTALLED IN
CONDITIONS WHERE SPRINKLERS CANNOT BE INSTALLED IN
ACCORDANCE WITH ABOVE TABLE.
1.
NOM. PIPE
STEEL PIPE
MINIMUM ROD
SIZE (INCHES)
MAX. SPAN (FEET)
DIAMETER (INCHES)
UP TO 4"
12'-0
3/8
D.O.B. BSCAN:
SPRINKLER HEADS SHALL BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS.
DRAWN BY:
DESIGN BY:
SCALE:
DATE:
2. PROVIDE METAL WIRE GUARDS WHERE SPRINKLERS ARE SUBJECT TO DAMAGE AND SPRINKLER HEADS LOCATED UNDER HVAC DUCTS IN MECHANICAL EQUIPMENT ROOMS WHEN LOCATED LOWER THAN 7'-O" A.F.F. ETC.
a.
ALL SPRINKLER HEADS THROUGHOUT THE FACILITY SHALL BE OF THE TEMPERATURE RATING AS REQUIRED BY NFPA 13
b.
SPRINKLER HEADS LOCATED CLOSE TO HEATERS, STEAM PIPING OR LOW-PRESSURE BLOW-OFF VALVE SHALL BE OF THE TEMPERATURE RATING AS REQUIRED BY NFPA 13.
c.
SPRINKLER HEADS LOCATED CLOSE TO HEATERS, STEAM PIPING OR LOW-PRESSURE BLOW-OFF VALVE SHALL BE OF THE TEMPERATURE RATING AS REQUIRED BY NFPA 13.
d.
ALL HEAT GENERATING EQUIPMENT WHICH CAN AFFECT THE TEMPERATURE RATING OF THE SPRINKLER HEADS SHALL BE CLEARLY IDENTIFIED ON THE SHOP DRAWINGS PRIOR TO SUBMISSION FOR APPROVAL.
3. SPRINKLER HEADS MINIMUM FLOW & MINIMUM PRESSURE REQUIREMENTS TO BE BASED ON HYDRAULIC CALCULATION DESIGN DENSITIES.
2/4/2026
AS NOTED
4. ALL SPRINKLER HEAD FINISHES TO BE APPROVED BY ARCHITECT.
5. PROVIDE INTERMEDIATE TEMPERATURE RATED SPRINKLER HEADS IN MECHANICAL ROOM.
DOB JOB NO:
DRAWING NO:
SP-006.00
FOR SPRINKLER ONLY
SCOPE OF WORK DOES NOT AFFECT THE ENERGY USE OF THIS BUILDING
PAGE 6 OF 6