DISTRIBUTION SYSTEM DESIGN SKETCH
SKETCH OF LINE SECTION, T-OFF TO COFFEE FACTORY
ROAD, DOVER DISTRICT, ST. MARY
PMR Switch N/0
Pole #-
…from Annotto Bay
310
1 X J/Switch (Isol. Switch)
EP 1 T 1PH
/WR 40-4
Broken/dislodged prim cond–String &
tension+ Veg Control & D/end Polymer to
be installed at end of line
Damaged/fallen pole–Pole to be
replaced + Tall Tree; Veg clearance
EP2 TDE 1PH
40-4
EP3 CV 1PH
35-6
Broken prim. Phase + neutral
Veg. Clearance in secondary;
encroaching but not touching
prim.
EP4 CV 1PH
35-6
Veg. Clearance req.;
secondary only
EP5 TA 1PH
35-6
EP6 TA 1PH
35-6
EP7 TA 1PH
35-6
EP10 CV 1PH
35-6
EP11 T 1PH
35-6
EP12 DE 1PH 404, End of Prim
1. Replace fallen pole at EP1
2. Carry out vegetation control activities
at EP3, EP5, EP9 and EP10
EP8 TA 1PH
35-6
Spot bushing –
Secondary line
(minor)
RECOMMENDATIONS
Found okay (minor
spot/under veg
EP9 CV 1PH
35-6
Veg. Clearance req.
very near Prim. Cond.
3. Restore supply to lateral