Continues on B102
Existing Wall
and external
Structure above to S.E
specification.
30min fire resistance
to be installed to
structural steelwork
Minimum
30 minutes
fire rating
internal
and
external
700
103mm Facing brick to match existing - get brick matched by supplier
125mm cavity with 75mm Celotex CG 5000 - 0.2 W/m²k
100mm Supabloc 4 inner leaf
Wet Plaster internal finish.
Paint to client spec.
Wall ties to BS 1243 at 450 c/c vertical 750 c/c horizontal,
Type 2 tie incorporating a double drip type
SS starter profiles
if brickwork cannot
be toothed in
Provide
Extract to
Kitchen
60 or 30L
/ sec
Internal Wall Type A - with acoustic insulation - IWT A
Paint to client selection on plaster skim coat on 12.5mm Tile Backer Board
where Tiling is required and aquapanel in place of plaster board on 75 mm
timber studs at 400mm c /c
100mm Celotex between studs to provide thermal and acoustic insulation.
Internal Wall Type "B" - IWT B
Paint to client selection on plaster skim coat on 12.5mm Tile Backer Board
where Tiling is required and aquapanel in place of plaster board on 100 mm
timber studs at 400mm c /c
635
2600
Important Note
ID
01
IWT-A
2055
735
H:1090
C: 900
WC
686
H: 990
C: 880
Kitchen
2915
CBD
EWT-A
5215
Cut vertical DPC
into existing wall
HD
H:1400
C: 1275
External Wall Type 'A' - EWT A
IWT-B
Wall Removed
External doors to have a
U-Value of 1.1 W/m2k.
5450
ED
02
Ensure that new
cavities are
continuous with
existing
Removed Walls
Utility
B
Read Structural Information from Strucural Engineers notes.
If you do not have a copy and need one please ask.
H:1990
C: 840
Services Note
Lighting
A minimum of 75% of all new light fittings are to be energy efficient in
accordance with Approved Document L
Heating
Where required newly installed radiators to be installed with TRV's and all
pipework to be insulated in accordance with Approved Document L
New internal doors
Doors to match existing with architrave surround to match existing
Provide
Extract to
Utility 30
or 15L /
sec
Fire Detectors and Alarms
Mains interlinked smoke detection will be installed to all floor levels.
Proposed system shall be Grade D Category LD3 Standard in accordance
with BS 5839-6:2013
Entrance Hall
2900
Services
All notifiable electrical works will be completed and notified by a person
registered on a Part P competent persons scheme
Dining Room
2900
Extract Ventilation
Provide Extract to WC 15 L / sec
Provide Extract to Kitchen 60L / sec or 30L / sec
Lounge
2900
SD
Smoke Detector
HD
Heat Detector
Note:
All existing fire doors retained
Public Sewers
The public sewer being accurately located by the applicant on site prior to
commencement of foundation excavations in order that the effect of the
proposed works can be determined.
Where the public sewer is to be built over, the condition of the public sewer
being camera surveyed or fully exposed and determined as satisfactory.
Failing this the affected length of pipework being replaced with new.
All foundations (footings, walls etc.) running parallel to the line of the public
sewer being located within 500mm (minimum distance) of the public sewer.
Crossings being adequately supported using pre-cast or appropriately
designed in-situ, concrete lintels or beams.
A
A 15.10.18 First Issue
Rev
Date
Description
VB
JM
By
PM
500
DRAWING TITLE
7 Cousins Grove, Southsea,
PO4 9RP, Hampshire
Proposed 1 of 2
Ground Floor Plan
CLIENT
Ian and Julie Andrew
REVISIONS
0
PROJECT
1000
1500
2000
2500mm
Design Team Studios LLP
Copyright Reserved
Check Dimensions on Site
© Crown copyright and database rights [2018]
Ordnance Survey-
© Local Government Information House Limited copyright and database rights [2018]-
DRAWING STATUS:
Building Control
REVISION:
A
1:50
Drawn by :
VB
DRAWING NUMBER:
Oct 2018
Checked by :
JM
326.B101_A