TECHNICAL SPECIFICATION
PART:A 33/11KV 2X15MVA, 33/ 11 KV, Substation Equipment's
1. 33KV Outdoor Air Break Switch (ABS)
Sl.
No.
Description
Unit
Technical Specification
Wenzhou/Xinku Power,
China
1
Manufacturer's Name & country
2
Manufacturer's Model No.
N/A
3
Manufacturer's Model No.
Single Break
4
Frequency
Hz
50
5
System nominal voltage
kV
33
6
System maximum voltage
kV
36
7
Basic Insulation level
kV
170
8
Rated Normal Current
A
1250
9
Rated Short Item Withstand Current (for 3 sec.)
KA
25
10
Installation
Outdoor
11
Type
12
Construction
Open
13
Operation
Gang
14
Operating mechanism
15
Mounting position
16
Number of Pole
Nos.
3 (Three)
17
No. of break per pole
Nos.
Single
18
Contract resistance (µΩ) & contract area (mm2)
19
Materials of contact service
20
Air gap between pole of phase
mm
900 Approx.
21
Total weight of unit
Kg
300 (Approx.)
22
Line charging current breaking capacity
A
2.5
23
Magnetizing current breaking capacity
A
3
24
Creepage distance of Insulator
mm
25 mm/kV
25
No. of Aux. Contracts (NO/NC)
4 NO-4 NC
26
Standard
IEC - 60129
Air
Manual
Vertical/Horizontal
20 µΩ & (mm2)
Nickel Plated Copper
2. 33 KV, 800A ACR (AUTO CIRCUIT RECLOSER)
Description
SL
Specification
Noja Power-Australia/EntecKoreaEquivalent
1
Manufacturer's Name & country of origin
2
3
Manufacturer's Model No.
Max Voltage
4
Max. Current
800A
5
Continues Current is
630A
6
Short Circuit Current rating (1 sec.)
20KA
7
BIL
8
Ground earth Clarence (minimum)
9
Ground earth creempase distance
N/A
38.5 KV
170 KV
394/676mm
1763/1250 min
10
Rated minimum phase tripping current
100-630amp
11
Rated minimum ground tripping current
10-630 Amp
12
Number of First Curve
13
Current transformer ratio is
14
Other Component:
a
6x integral cable terminations
b
6x 1284mm creepage silicon rubber bushing boots
c
2x inbuild current transformers
d
6x Inbuild voltage sensors
e
1xRC10 Stainless steel Control & Communication Cubicle with IEC60870 &
DNP3 Communication Protocol, English software & provision for 110V-230V
AC Auxiliary Supply. Suitable for Temperature range from - 40Deg C to
+55Deg C.
f
1x7m Control Cable
g
1x Pole mounted Bracket
h
6x Surge Arrester Mounting Brackets integral
i
1x User Manual
j
1x33/.22KV, 100VA Auxiliary supply voltage transformer (VT)
-/5
5. 33KV Outdoor Lightning Arrester
Equipment
Technical Description
Brand
Rated voltage (RMS): 30kV
Rated system voltage: 36 kV
Frequency: 50Hz
Minimum Spark over (RMS): 48 kV
33KV Lightning
Arrester
Maxmum Spark (Crest): 72 kV
Maximum Impulse Spark (crest) withstand voltage: 72 kV
Wet, 10Sec: 65 kV
Dry. 1 Min: 92 kV
Discharge 33kV (crest): 20KA
impulse Current with Stand: 75 KA
CGL-India
6 & 7 . 33KV Gang Operated Isolator 1250A Interlocked with Earth Switch & With Out Earth Switch
Sl.
No.
Description
Unit
Technical Specification
1
Manufacturer's Name & country
-
Manufacturer's Model No.
Manufacturer's Model No.
Frequency
System nominal voltage
System maximum voltage
Basic Insulation level
Rated Normal Current
Hz
kV
kV
kV
A
N/A
Single Break-
9
Rated Short Item Withstand Current (for 3 sec.)
KA
25
Nos.
Nos.
Outdoor
Air
Open
Gang
Manual
Vertical/Horizontal
3 (Three)
Single
-
Installation
Type
Construction
Operation
Operating mechanism
Mounting position
Number of Pole
No. of break per pole
18
Contract resistance (µΩ) & contract area (mm2)
-
Materials of contact service
Air gap between pole of phase
Total weight of unit
Line charging current breaking capacity
23
Magnetizing current breaking capacity
24
Creepage distance of Insulator
25
No. of Aux. Contracts (NO/NC)
26
Standard
S&S-India
20 µΩ & (mm2)
mm
Kg
A
Nickel Plated Copper
900 Approx.
300 (Approx.)
2.5
A
3
mm
25 mm/kV
4 NO-4 NC
IEC - 60129
10. 33 KV CURRENT TRANSFORMERS
Sl.
No.
Description
Unit
Technical Specification
1
Name of the manufacturer
Gemini-India
2
Manufacturer's Model No.
N/A
3
Standard
4
Nominal System Voltage
kV
33
5
Heights System Voltage
kV
36
6
Frequency
kV
50
7
Impulse withstand voltage
kV
170
8
Power frequency withstand voltage (1 min)
kV
70
9
CT Ratio
a) Incoming
IEC 60044
CT: 300- 5/5/5
10
Number of core
11
Rated output & accuracy
Incoming
a) core-1 (metering)
b) core-2 (metering)
b) core-3 (prot.)
12
Width
mm
350
13
Length
mm
600
14
Total creepage distance
mm
900
15
Short Circuit Current rating (3 sec.)
KA
25
16
Total weight of one single phase unit
Kg
90 Kg (Approx)
17
Period of time, equipment has been in service
Years
More than 15 years
18
Period of time, equipment has been under
manufacture
Years
More than 15 years
19
Burden / Class
a) Metering winding
b) Protection Winding
3
30VA, 0.5 FS≤5
300 5/5/5 , for metering & Protection.
1st Core: 30VA, Class 0.5 for metering
2nd Core: 30VA, Class 0.5 for metering
3rd Core: 30VA, Class 5P20 for protection
9. 33 KV POTENTIAL TRANSFORMERS
Sl.
No.
Description
Unit
Technical Specification
1
Name of the manufacturer
Gemini-India
2
Manufacturer's Model No.
N/A
3
Standard
4
Nominal System Voltage
kV
33
5
Heights System Voltage
kV
36
6
Rated Primary Voltage
kV
33/√3
7
Rated Secondary Voltage
V
110/√3
8
Impulse withstand voltage (1.2/50 micro sec.)
KV
170
9
Power frequency withstand voltage
KV
70
IEC 60044
10
Period of time, equipment has been in service
Years
More than 15 years
11
Period of time, equipment has been under
manufacture
Years
More than 15 years
VA
50 VA/Class 0.5
(Metering)
50 VA/Class 5P
(Protection)
12
Burden / Class
a) Metering winding
b) Protection Winding
8. 33 KV OUTDOOR VACUUM CIRCUIT BREAKER (VCB)
Sl.
No.
Description
Unit
Technical Specification
1
Manufacturer's Name & country
Siemens-India
2
Manufacturer's Model No.
3
Rated voltage
KV
36
4
Freqency
Hz
50
5
Rated Current
A
1250
6
Rated Power-Ferquency Withstand Voltage
KV
70
7
Rated lighting impulse Withstand Voltage (peak)
KV
170
8
Rated short- circuit breaking current
KA
25
9
Rated short- circuit making current (peak)
KA
66
10
Rated Short time Withstand Current (for 3 sec.)
KA
26.3
11
Rated operating sequence
12
Service conditions
13
Degree of protection
14
Approx.total weight
N/A
O-0.3 s-CO-15 s-CO
O-0.3s-CO-3 min-CO
⁰C
-25
55
IP55
Kg
635
11. 33 kV Transformer Control & Relay Panel
Sl.
No.
1
2
3
4
Description
Unit
Manufacturer’s Name & Country
Manufacturer’s Address
Panel Size
Sheet, Color
Technical Specification
Reverie
Bangladesh
2000 x 600 x 600
16 SWG, Siemens Gray
Lot
Transformer Feeder Protection IDMT Relay
5
Manufacture Name & Country of Relay
N/A
N/A
Siemens, India/Equivalent
6
Type of Relay
N/A
N/A
Numerical Programmable
7
Relay Protection
N/A
N/A
50/50N, 51/51N
6
Transformer Feeder Protection Differential Relay
6.1
Manufacture Name & Country of Relay
N/A
N/A
ABB
6.2
Type of Relay
N/A
N/A
Numerical Programmable
6.3
Relay Protection
N/A
N/A
87/87N, 67/67N
Set
1
3P,4W Digital, 0.2 class
Set
1
Multifunction Meter, 0.5
class
Lot
1
LED Type
Nos
Lot
1
1
Siemens, India/Equivalent
Phonix-Germany
Set
Lot
Lot
Lot
Set
Lot
Lot
Lot
Lot
Lot
Lot
Lot
Lot
Set
Lot
-
Secure Meter, India
Phoenix, USA
Phoenix, USA
ABB-Germany
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
As per Reverie Standard
7
Metering & Indication
7.1
Multifunction Meter:ABB
7.2
Indication Voltmeter
-
Lamp for ON,OFF, TCS Healthy, Spring Charge,
Trip
Others Relay
TCS Relay
Aux Relay
Others
Metering TTB
CT & PT Slide Link Connector
2.5 mm TB
MCB
Buzzer
DIN Channel
Grounding Bar
TCS Relay Ext. Resistor
Cable Channel/Duct
Control Cable
Lugs
Tie
Thermostat
Heater
Ferrules
12. 110V DC Battery Bank Ni-Cd Type Battery (1.2V, 92 Cell)
Sl.
No.
Description
1
BRAND & ORIGIN
2
Application
3
4
Installation
Type
Technical Specification
HBL/Equivalent
Supply for Remote control automatic indicating, protecting & regulating apparatus
emergency light & power.
Indoor
maintenance free battery
-
Operating Voltage
Continuous Loading
Instantaneous Loading
Battery Capacity
Type of container
No of cells
12
Construction
13
Design Life
110V DC
5 amp
30 ampere per 1 minute
100AH
Transparent SAN Container
1.2V, 92 Cell
All equipment and materials shall be designed, manufactured in accordance with the
latest conditions of applicable IEC Standard.
10 Years (minimum)
Technical Specification of Battery Charger
Sl.
No.
1
Description
Installation
Rectifier Type
SCHEME
Rating
Charging mode
BRAND & ORIGIN
General :
a. Cabinet
b. Temperature range of Operation
c. Relative Humidity
d. Cooling
Technical Specification
Indoor
Thyristor Controlled
Full wave half controlled bridge Rectifier
110VDC/40Amps.
Float & Boost
A Power Engineering
Free standing steel cabinet easy access for
Installation & Commissioning, cable entry at
bottom.
0 to 45 ⁰C
0% to 99% non-condensing.
Natural Air cooling
2
AC INPUT :
400 VAC ± 10%.
50 Hz ± 5%.
03(Three) Phase.
3
a. Voltage
b. Frequency
c. Phase
DC OUTPUT :
a. Nominal Voltage
110V ± 5%.
b. Float Voltage
122V ± 5%.
c. Boost Voltage
128V ± 5%.
d. Regulation
Better than 1% of set value.
e. Ripple
Less than 3% RMS.
4
f. Current
40 Amp.
g. Output Voltage
110 VDC
h. Efficiency
88%.
i. Insulation Break down Voltage
2 KV for 1 (one) minute.
j. Current Limitation
110%
METERS :
a. AC Input Volt Meter
(0-500 V)
b. Battery Volt Meter
(0-100V)
c. Battery Amps Meter
(0-100A)
d. Load Volt Meter
(0-100V)
e. Load Amps Meter
(0-100A)
f. Alarm Meter
5
PROTECTION :
a. Input MCCB: 01 No 63A TP MCCB
b. Output MCB: 02 Nos 40A DP MCB
c. Electronic Short Circuit Protection
d. Reverse Polarity Protection
6
ALARM INDICATION :
a. Mains Fail
b. Rectifier Fail
c. Under Volt
d. Over Volt
e. Earth Fault [+]
f. Earth Fault [-]
7
ALARM CONTACT :
a. Common Alarm Contact
b. NC/NO Contact
15.Guaranteed Technical Data Schedule
FOR 33/11 KV, 3-PHASE, 15 MVA TRANSFORMER
Sl.
No.
Description
Unit
Requirement
Brand & Orgin
Rating and Performance
1
Manufacturer’s name & country
To be mentioned
Reverie-Bangladesh
2
Manufacturer’s Model no.
To be mentioned
33/11-15 MVA X-REV
-/-
Outdoor
-/-
Outdoor
Oil immersed
Oil immersed
Nos.
HT-LT
2
Porcelain
HT-LT
2
Porcelain
A
400/5
400/5
A
900/5
900/5
ONAN
ONAN
Mineral Oil free
from PCB as per
IEC-60296
Mineral Oil free from PCB
as per IEC-60296
-
Continuous maximum rating(ONAN)
No. of phases
Rated frequency
Normal transformation ratio at No-load
Rated HT voltage(phase to phase)
Maximum HT voltage(phase to phase)
Rated LT voltage(phase to phase)
Maximum LT voltage(phase to phase)
Installation
12
Type of Transformer
13
14
15
Direction of the normal power flow
No of Windings
Bushing materials
MVA
Nos.
Hz
kV
Transformer Bushing CT
a) HT Bushing CT
b) LV Bushing CT
16
17
18
19
20
Type of cooling
Coolant
Type of earthing
Vector group
Neutral to be brought out:
a)HT
b)LT
Method of Connection
a)HT
b)LT
Effectively earth
Earthing at
11kV Neutral
Dyn11
Dyn11
Nill
Yes
Nill
Yes
Delta
Star
Delta
Star
21
22
Basic Insulation Level (BIL)
a) High voltage winding
b) Low voltage winding
23
Max. Temp Rise by the Transformer when run at Max. abmbient temp. of 40°C
°C
°C
65
60
65
60
24
a) of Winding by Thermometer
b) of Top Oil by Thermometer
Test Voltage :
Impulse front wave test voltage(1.2/50 micro sec.
wave shape)
kVp
kVp
170
75
170
75
kVrms
kVrms
%
70
28
To be mentioned
70
28
9.0
1
2
3
4
a) High voltage side
b) Low voltage side
Power Frequency withstand test voltage for
a) High voltage side
b) Low voltage side
Impedance voltage at 75°C and at normal ratio and
Voltage Control (OLTC) :
Type of Tap Changer control
OLTC & MDU manufacturer's name and country
Oil filled/ Vacuum type Tap changer.
Nos. of tapping
5
Tapping steps
6
7
8
Model
HV or LV winding
Power Frequency withstand test voltage between first
General :
1
Manufacturer's Name and Address
2
a)No load losses at rated voltage, ratio and
frequency. (Tolerance 10%)
25
25
3
4
kV
kV
170
75
170
75
On Load Tap Changer
(MR-Gemany)
Vacuum Type
17 Position
(+1.25x4 to -1.25x12)%
@ 1.25%
kV
75
VVS
HV
75
To be mentioned
Posco-Korea/
Baosteel-China
KW
To be mentioned
12
b)Load Load losses at rated voltage, normal ratio &
frequency at ONAN (Tolerance 10%)
kW
To be mentioned
96
c)Total Loss(a+b) (Tolerance 10%)
kW
To be mentioned
108
Approx.
31800
Transformer weight
kg
Buchholz Relay:Hitachi(ABB)-Turkey / Equivalent
5
Pressure Release valve (PRV): Viat-India/Precimeasure-India /Equivalent
6
Magnetic Oil Level Gauge (MOG): Viat-India/Precimeasure-India / Equivalent
7
Oil Filling Valve
8
Oil Filteration Valve
9
Oil Drain Valve
10
Transformer Oil: BDV>=50kV Savita-India/Apar-India
11
Oil Temperature Indicator. (OTI) : Precimeasure-India / Equivalent
12
Winding Temperature Indicator.(WTI): Precimeasure-India / Equivalent
13
Insulation Paper: Hitachi (ABB)-India
14
Cu Wire:RR-Bangladesh/Rational Engineers-India
16. Technical Specifications of RTCC Panel
SL
No.
1
Item Name
Manufacturer
Description
Reverie Power & Automation Engineering Ltd.
IEC-297-2
2
Standard Compliance
DIN41494, PART7
3
Panel Dimension
As Required
4
AVR Controller
PLC-Rockwell/PHONIX-Germany
a) Front door margin with crescent design, exterior door hinge with 180 degrees
b) Cable entrance from the bottom
c) Thickness:1.2MM for the body,2.0mm for the 19'' rails
5
Panel Specification
d) Black or Grey color
f) fixed feet
h) Earthing bolt
a) Full automatic and manual control
6
Cubicle Option
b) Alarm & Indications
7
Auxiliary Voltage
Requirement
220 V AC 6 A
17. Mesh Earthing For 33KV Substation
Equipment
Technical Description
Brand
Origin
Reverie
Bangladesh
Installation, testing & Commissioning of the earthing system with
which comply with DESCO, DPDC, PDB, REB, and ELB rules &
regulation.
Mesh Earthing
Cu wire: 12.5mm Dia
Boring Depth: 40FT
Mesh Conductor: As per Actual
18. Earthing For Equipments of 33kV 15MVA Substation
Equipment
Technical Description
Brand
Origin
Reverie
Bangladesh
Installation, testing & Commissioning of the earthing system with
which comply with DESCO, DPDC, PDB, REB, and ELB rules &
regulation.
Earthing
Cu wire: 12.5 mm Dia
GI pipe: 1.5 Inch Dia (20 FT Long)
Boring Depth: 100FT
13. AC/DC Distribution Board
Supply, installation, testing & commissioning of Standard AC & D.C distribution board as per the requirements of
proper operation and maintenance of Substation (Complete package)
AC PART:
INCOMING: 01 No 400A 36kA (MCCB) TP, Molded Case Circuit Breaker with magnetic & Standard trip unit
protection.
01 No -Digital Ammeter
01 No -Digital Voltmeter
03 Nos Indicating Lamps & 03 Nos-Control Fuse
OUTGOING:
02 No-100A, 25kA (MCCB) TP TP, Molded Case Circuit Breaker with magnetic & Standard trip unit protection.
10 Nos-10A,6kA,230V,DP MCB
DC PART:
INCOMING: 01 No-100A,6kA,230V,DP MCB
01 No -Digital Voltmeter
OUTGOING:
10 Nos-6A,6kA,230V,DP MCB
04 Nos-10A,6kA,230V,SP MCB
Others
As per Reverie Standard
21. 2x1250A, 11KV Main HT Switchgear Panel (VCB)
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
1 no 1250A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
ABB-India
Current
Transformer
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 800-400/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class5P20 for protection
3rd Core:15VA, Class5P20 for protection
Xinku PowerChina/Equivalent
Potential
Transformer
2 nos dry type cast rasin insulated Potential transformer for open
delta connection. Ratio:11000/110V, Burden: 30VA & Class: 0.5,
Burden: 30VA & Class: 10P10
Xinku PowerChina/Equivalent
IDMT Relay
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
Indication
Secondary
Metering
Others
01 no of 8 Window Annunciator
Siemens-India
Equivalent
ABB-India
Minilac-India
Mimic diagram & TNC Switch
03 nos of Digital Ammeter
ABB-India
1 no of Digital Voltmeter
As Per Reverie Standard
22. 5x630A, 11KV Outgoing HT Switchgear Panel (VCB)
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign, & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
1 no 630A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
ABB-India
Current
Transformer
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 250/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class 5P10 for protection
Xinku PowerChina/Equivalent
IDMT Relay
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
Siemens-India
Equivalent
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
Indication
Secondary
Metering
Bus Potential
Transformer
Others
ABB-India
01 no of 8 Window Annunciator
Minilac-India
Mimic diagram & TNC Switch
03 nos of Digital Ammeter
ABB-India
1 no of Digital Voltmeter
2 nos dry type cast rasin insulated Potential transformer for open
delta connection. Ratio:11000/110V, Burden: 30VA & Class: 0.5,
Burden: 30VA & Class: 10P10
Xinku PowerChina/Equivalent
As Per Reverie Standard
23. 1x1250A, 11KV Outgoing HT Switchgear Panel (VCB)
For Chaity Composite
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign, & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
Current
Transformer
IDMT Relay
1 no 1250A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 800-400/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class5P20 for protection
3rd Core:15VA, Class5P20 for protection
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
Indication
Secondary
Metering
Xinku PowerChina/Equivalent
Siemens-India
Equivalent
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
ABB-India
ABB-India
01 no of 8 Window Annunciator
Minilac-India
Mimic diagram & TNC Switch
03 nos of Digital Ammeter
ABB-India
1 no of Digital Voltmeter
Bus Potential
Transformer
Others
2 nos dry type cast rasin insulated Potential transformer for open
delta connection. Ratio:11000/110V, Burden: 30VA & Class: 0.5,
Burden: 30VA & Class: 10P10
Xinku PowerChina/Equivalent
As Per Reverie Standard
24. 1x1250A, 11KV Outgoing HT Switchgear Panel (VCB)
For Bus-Cupler
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign, & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
1 no 1250A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
ABB-India
Current
Transformer
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 800-400/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class5P20 for protection
3rd Core:15VA, Class5P20 for protection
Xinku PowerChina/Equivalent
IDMT Relay
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
01 no of 8 Window Annunciator
Indication
Mimic diagram & TNC Switch
Secondary
Metering
03 nos of Digital Ammeter
Others
Siemens-India
Equivalent
ABB-India
Minilac-India
ABB-India
1 no of Digital Voltmeter
As Per Reverie Standard
Equipment
Lightning Arrester
20. Lightening Arrester
Technical Description
Rated voltage (RMS): 9 kV
Rayed system voltage: 12 kV
Frequency: 50Hz
Minimum Spark over (RMS): 14 kV
Minimum Spark (Crest): 40 kV
Maximum Impulse Spark (crest) withstand voltage: 45 kV
Wet, 10Sec: 24 kV
Dry. 1 Min: 28 kV
Discharge 33kV (crest): 5KA
Impulse Current with Stand: 55 KA
Brand & Origin
CGL-India
PART:B Technical Transformer & LT Panel
4x4.5MVA 11/.415kV Electrical
Sub-station. 8X1.5MW+2X1MW Gas Generator.
2. Technical Specifications of 4X4.5 MVA, 11/0.415 kV Electrical Transformer
Equipment
4.5 MVA Oil Immersed
Transformer
Technical Description
Three phase transformer ground mounted, oil immersed, with standered
accessories, outdoor use, routine tests and first filling oil included.
Design manufacturing, routine tests, & tolerance according to IEC 60076
standard.
Standard Fittings:
2 Lifting lugs for active part
4 Lifting lugs for transformer
2 Earthing points.
Cooling type: ONAN
1 Rating plate
HV bushing: 3 porcelain bushing
LV bushing: 4 porcelain bushing
Rated power in kVA: 4.5 MVA
System voltage: 11 kV
Frequency: 50Hz
Primary voltage:11000 V
Secondary voltage:415V
HV impulse voltage peak in kV: 75kV
Power frequency kV rms: 28kV
Vector group: Dyn11
Max. ambient temp in deg. C:40
Altitude lower thank in meter:1000
Temp rise in winding/oil in deg.C:65/60
No load loss: 3800 watt [Tolerance ±10%]
Load loss: 52000 watt [Tolerance ±10%]
Impedence voltage: 7.5% [Tolerance ±10%]
HV copper conductor
LV copper conductor
Transformer oil
Buchholz Relay
Viat-India/PrecimeasureIndia or Equivalent
Pressure Release Valve
Other Insulated materials & fittings
Voltage Control (OLTC):
Type of tap changer control
2
OLTC & MDU manufacturer's name & country
3
4
Oil Type/ Vacuum type tap changer
Nos. of tapping
5
Tapping Steps
Others
Reverie-BD
Baosteel-China / PoscoKorea
RR-BD/ Equivalent
RR-BD/ Equivalent
Savita-India
Apar-India
Hitachi(ABB) or
Equivalent
Hi-B grade silicon steel sheet
1
Brand
ABB-India
On Load Changer
MR-Germany (Eco Tap
VPD)
Vacuum Type
9 possition
+ 3 x 2.5% , 0, -5 x
2.5%
As per Reverie Standard
3.4X LT Switchgear Panel For 4.5MVA
Equipment
Technical Description
Brand & Origin
Supply of 16/14 SWG M/S sheet still clad with powder coated Siemens gray/RAL7035 color, dust and vermin proof, floor
mounting,type completely factory assembled 415 V, 50Hz, LT Switchgear Panel having 6400A (TPN+50%E) hard drawn electrolytic
copper busbars placed on Abonide Fiber. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer and modern locks .
Full Dust & Vermin Proof Cable gland as per cable size, cable entry .Earthling Bus bar is provided inside the box and same as Phase &
Neutral bus bar in and all cases sufficient gap. The board is designed and constructed in accordance with BNBC-2014 & IEEE Electrical
wiring. Panel board is provided capacitive information level & All type of danger sign. Panel Board all doors is connected by ECC with
earthing bus bar. Other Incoming & Outgoing cable Color Code will be followed the distribution board by internal wiring.
Incoming Breaker From
Transformer
1 No. 6300A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt
Opening, Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable
& Magnetic standard protection trip unit.
Breaking Capacity: 100KA.
03 Nos. 6300/5A Current Transformer with suitable accuracy & Burden
Metering & Control Unit
Others
Indication Lamp (RYB)
On/Off Push Button Swtich
Control MCB
Multifunction Meter
Model: M1M
ABB- Italy
Risesun-Taiwan
ABB-India/Equivalent
ABB-India
As per Reverie Standard
Technical Specification
4,5,6,7
Equipment
Technical Description
Brand & Origin
Supply of 16 SWG sheet still clad with powder coated RAL 7035,color, dust and vermin proof, free standing, floor mounting type
completely factory assembled Synchronization Panel. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer with
sufficient space as per modern locks.Full Dust & Vermin Proof Cable gland as per cable size, cable entry . The board is designed and
constructed in accordance with BNBC-2014 & IEEE Electrical wiring. Panel board is provided capacitive information level & All type of
danger sign,& panel base plate.Other Incoming & Outgoing cable Color Code will followed the distribution board by internal wiring,
Hinge, Lock, Louver: imported.
4X4.5MVA Grid Synchronization Control System
Controller
Display
Control Unit
01 No. InteliMains NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
2X Bus Cupler Control Unit
Controller
Display
Control Unit
01 No. InteliMains NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
8X1.5MW Gas Generator Synchronization Control System
Controller
Display
AVR Control & Dongle
01 No.InteliSys NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 No. IG-NTC AVRi
ComAp,Cz- EU
01 No. Dongle LSM+PMS
ComAp,Cz- EU
01 No. IG-NTC AVRi Trans
ComAp,Cz- EU
Control Unit
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
2X1MW Gas Generator Synchronization Control System
Controller
Display
AVR Control & Dongle
01 No.InteliSys NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 No. IG-NTC AVRi
ComAp,Cz- EU
01 No. Dongle LSM+PMS
ComAp,Cz- EU
01 No. IG-NTC AVRi Trans
Others
Nos Indication lamps
Nos Buzzer
Nos Push Button
Nos Emergency Stop Push Button
Nos Selector Switch
Lot Control MCB for secondery protection
Lot 24VDC Relays
As per Reverie Standard
Equipment
8. Earthing For Equipments of 33kV 4.5MVA Substation
Technical Description
Control Unit
-
ComAp,Cz- EU
ABB-India/Equivalent
ABB-India/Equivalent
ABB-India/Equivalent
ABB-India/Equivalent
ABB-India/Equivalent
Siemens/ Schneider
Phoenix- Germany
Brand & Origin
Installation, testing & Commissioning of the earthing system with which comply
with DESCO, DPDC, PDB, REB, and ELB rules & regulation
Earthing
Cu wire: 12.5 mm Dia
GI pipe: 1.5 Inch Dia (20 FT Long)
Boring Depth: 100FT
Reverie-BD
PART:C Technical HT,Transformer & LT Panel
2x4MVA 11/.415kV Electrical
Sub-station. 3X2MVA Gas Generator.
2. 1x1250A, 11KV Main HT Switchgear Panel (VCB)
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
1 no 1250A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
ABB-India
Current
Transformer
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 800-400/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class5P20 for protection
3rd Core:15VA, Class5P20 for protection
Xinku PowerChina/Equivalent
Potential
Transformer
2 nos dry type cast rasin insulated Potential transformer for open
delta connection. Ratio:11000/110V, Burden: 30VA & Class: 0.5,
Burden: 30VA & Class: 10P10
Xinku PowerChina/Equivalent
IDMT Relay
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
Indication
Secondary
Metering
Others
01 no of 8 Window Annunciator
Siemens-India
Equivalent
ABB-India
Minilac-India
Mimic diagram & TNC Switch
03 nos of Digital Ammeter
ABB-India
1 no of Digital Voltmeter
As Per Reverie Standard
3. 2x630A, 11KV Outgoing HT Switchgear Panel (VCB)
Equipment
Technical Description
Brand
Supply of 16/14 SWG sheet still clad with powder coated RAL-7035/ gray color, dust and vermin proof, free
standing, floor mounting type completely factory assembled 11KV, 50Hz, HT Switchgear panel having 1250A hard
drawn electrolytic copper busbars (TP) placed on Abonite fiber. Including cable color coding, cable lugs, Cable gland,
nut, bolts and , modern locks. Full Dust & Vermin Proof Cable gland as per cable size, cable entry and Exit point
checked by leaser light & Earthling Bus bar is provided inside the box and same as Phase all cases sufficient gap. The
board is designed and constructed in accordance with BNBC-2006 & 2012 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign, & panel base plate. Panel Board all doors is connected
by ECC with earthing bus bar. Other Incoming & Outgoing cable Color Code will followed the distribution board by
internal wiring.
VCB
1 no 630A, 12KV, 25KA, rated triple pole 50Hz, Drawout
Type VCB
ABB-India
Current
Transformer
3 nos. 11 kV cast resin insulated Three core current transformer
(CT) having ratio 250/5/5/5A, for metering & Protection.
1st Core: 10VA, Class 0.5 for metering
2nd Core:15VA, Class 5P10 for protection
Xinku PowerChina/Equivalent
IDMT Relay
1 no Triple pole IDMT Induction type relay for over
current,earthfault and short circuit protection.
Model: 7SR10
Siemens-India
Equivalent
01 no of Digital Multifunction Meter
Energy Metering (Volt, Ampere, KW, KVAR, Power factor, Frequency)
Model:M1M
Annunciator
Indication
Secondary
Metering
Bus Potential
Transformer
Others
ABB-India
01 no of 8 Window Annunciator
Minilac-India
Mimic diagram & TNC Switch
03 nos of Digital Ammeter
ABB-India
1 no of Digital Voltmeter
2 nos dry type cast rasin insulated Potential transformer for open
delta connection. Ratio:11000/110V, Burden: 30VA & Class: 0.5,
Burden: 30VA & Class: 10P10
Xinku PowerChina/Equivalent
As Per Reverie Standard
4. Technical Specifications of 2X4 MVA, 11/0.415 kV Electrical Transformer
Equipment
4 MVA Oil Immersed
Transformer
Technical Description
Three phase transformer ground mounted, oil immersed, with standered
accessories, outdoor use, routine tests and first filling oil included.
Design manufacturing, routine tests, & tolerance according to IEC 60076
standard.
Standard Fittings:
2 Lifting lugs for active part
4 Lifting lugs for transformer
2 Earthing points.
Cooling type: ONAN
1 Rating plate
HV bushing: 3 porcelain bushing
LV bushing: 4 porcelain bushing
Rated power in kVA: 4 MVA
System voltage: 11 kV
Frequency: 50Hz
Primary voltage:11000 V
Secondary voltage:415V
HV impulse voltage peak in kV: 75kV
Power frequency kV rms: 28kV
Vector group: Dyn11
Max. ambient temp in deg. C:40
Altitude lower thank in meter:1000
Temp rise in winding/oil in deg.C:65/60
No load loss: 4603 watt [Tolerance ±10%]
Load loss: 41053 watt [Tolerance ±10%]
Impedence voltage: 6.41% [Tolerance ±10%]
Reverie-BD
Baosteel-China / PoscoKorea
RR-BD/ Equivalent
RR-BD/ Equivalent
Savita-India
Apar-India
Hi-B grade silicon steel sheet
HV copper conductor
LV copper conductor
Transformer oil
Buchholz Relay
Hitachi(ABB) or Equivalent
Viat-India/PrecimeasureIndia or Equivalent
Pressure Release Valve
1
Brand
Other Insulated materials & fittings
Voltage Control (OLTC):
Type of tap changer control
ABB-India
On Load Changer
2
OLTC & MDU manufacturer's name & country
MR-Germany (Eco Tap VPD)
3
4
Oil Type/ Vacuum type tap changer
Nos. of tapping
Vacuum Type
9 possition
5
Tapping Steps
+ 3 x 2.5% , 0, -5 x 2.5%
Others
As per Reverie Standard
5.1X LT-3 Switchgear Panel For 4MVA
Equipment
Technical Description
Brand & Origin
Supply of 16/14 SWG M/S sheet still clad with powder coated Siemens gray/RAL7035 color, dust and vermin proof, floor mounting,type
completely factory assembled 415 V, 50Hz, LT Switchgear Panel having 6400A (TPN+50%E) hard drawn electrolytic copper busbars placed
on Abonide Fiber. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer and modern locks . Full Dust & Vermin Proof
Cable gland as per cable size, cable entry .Earthling Bus bar is provided inside the box and same as Phase & Neutral bus bar in and all cases
sufficient gap. The board is designed and constructed in accordance with BNBC-2014 & IEEE Electrical wiring. Panel board is provided capacitive
information level & All type of danger sign. Panel Board all doors is connected by ECC with earthing bus bar. Other Incoming & Outgoing cable
Color Code will be followed the distribution board by internal wiring.
Incoming Breaker From
Transformer
1 No. 6300A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt
Opening, Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable &
Magnetic standard protection trip unit.
Breaking Capacity: 100KA.
03 Nos. 6300/5A Current Transformer with suitable accuracy & Burden
Metering & Control Unit
Breaker For PFI
Others
Indication Lamp (RYB)
On/Off Push Button Swtich
Control MCB
Multifunction Meter
Model: M1M
ABB- Italy
Risesun-Taiwan
ABB-India/Equivalent
ABB-India
1 No.4000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
As per Reverie Standard
ABB- Italy
6.1X LT Switchgear Panel For 4MVA
Equipment
Technical Description
Brand & Origin
Supply of 16/14 SWG M/S sheet still clad with powder coated Siemens gray/RAL7035 color, dust and vermin proof, floor mounting,type
completely factory assembled 415 V, 50Hz, LT Switchgear Panel having 6400A (TPN+50%E) hard drawn electrolytic copper busbars placed
on Abonide Fiber. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer and modern locks . Full Dust & Vermin Proof
Cable gland as per cable size, cable entry .Earthling Bus bar is provided inside the box and same as Phase & Neutral bus bar in and all cases
sufficient gap. The board is designed and constructed in accordance with BNBC-2014 & IEEE Electrical wiring. Panel board is provided capacitive
information level & All type of danger sign. Panel Board all doors is connected by ECC with earthing bus bar. Other Incoming & Outgoing cable
Color Code will be followed the distribution board by internal wiring.
Incoming Breaker From
Transformer
1 No. 6300A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt
Opening, Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable &
Magnetic standard protection trip unit.
Breaking Capacity: 100KA.
03 Nos. 6300/5A Current Transformer with suitable accuracy & Burden
Metering & Control Unit
Indication Lamp (RYB)
On/Off Push Button Swtich
Control MCB
Multifunction Meter
Model: M1M
ABB- Italy
Risesun-Taiwan
ABB-India/Equivalent
ABB-India
Breaker For PFI
1 No.4000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
Outgoing
1 No.3200A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
Outgoing
1 No.2000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
Outgoing
1 No.1600A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
Bus-cupler
1 No.4000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Others
As per Reverie Standard
7.1XGenerator Synchronization Power Panel
Equipment
Technical Description
Brand & Origin
Supply of 16/14 SWG M/S sheet still clad with powder coated Siemens gray/RAL7035 color, dust and vermin proof, floor mounting,type
completely factory assembled 415 V, 50Hz, Generator Synchronization Power Panel having 10000A (TPN+50%E) hard drawn electrolytic
copper busbars placed on Abonide Fiber. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer and modern locks . Full
Dust & Vermin Proof Cable gland as per cable size, cable entry .Earthling Bus bar is provided inside the box and same as Phase & Neutral bus bar
in and all cases sufficient gap. The board is designed and constructed in accordance with BNBC-2014 & IEEE Electrical wiring. Panel board is
provided capacitive information level & All type of danger sign. Panel Board all doors is connected by ECC with earthing bus bar. Other Incoming
& Outgoing cable Color Code will be followed the distribution board by internal wiring.
Incoming Breaker From
2.5MVA Generator
3 No.4000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
09 Nos. 4000/5A Current Transformer with suitable accuracy & Burden
Metering & Control Unit
Breaker For TPL-3
Substation
Ground Floor
Indication Lamp (RYB)
On/Off Push Button Swtich
Control MCB
ABB- Italy
Risesun-Taiwan
ABB-India/Equivalent
1 No.3200A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
Chest Printing &
LT-02 Dyeing Unit Ground
2 No.2000A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
Breaker For
LT-02
Dyeing Unit
Outgoing
1 No.1600A (ACB) TP (Fixed type) LI Air circuit Breaker with Shunt Opening,
Shunt Closing, Under Voltage Coil, Gear Motor, Thermal adjustable & Magnetic
standard protection trip unit.
Breaking Capacity: 66KA.
ABB- Italy
02 No. 1000A (MCCB) TP Molded Case circuit Breaker with Thermal
adjustable & Magnetic standard protection tripx unit.
Adjustable current setting range: -)A.
Breaking Capacity: 50KA.
ABB- Italy
MDB-09 Store Building
GF
01 No. 630A (MCCB) TP Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection tripx unit.
Adjustable current setting range: (250-630)A.
Breaking Capacity: 36KA.
ABB- Italy
MDB-09 Store Building
GF
01 No. 400A (MCCB) TP Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection tripx unit.
Adjustable current setting range: (160-400)A.
Breaking Capacity: 36KA.
ABB- Italy
MDB-10 Pump Room
GF
01 No. 250A (MCCB) TP Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection tripx unit.
Adjustable current setting range: (100-250)A.
Breaking Capacity: 36KA.
ABB- Italy
MDB-08, Utility Panel &
Spare
Generator Cooling
Fan CP-03 & CP-01
02 No. 160A (MCCB) TP Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection tripx unit.
Adjustable current setting range: (100-160)A.
Breaking Capacity: 25KA.
ABB- Italy
Generator Cooling
Fan CP-02
01 No. 100A (MCCB) TP Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection tripx unit.
Adjustable current setting range: (63-100)A.
Breaking Capacity: 25KA.
ABB- Italy
Fire Control Panel
1&2
02 10A DP MCB
Breaking Capacitiy:6kA
ABB- Italy
Others
As per Reverie Standard
Technical Specification
8,9,10
Equipment
Technical Description
Brand & Origin
Supply of 16 SWG sheet still clad with powder coated RAL 7035,color, dust and vermin proof, free standing, floor mounting type completely
factory assembled Synchronization Panel. Including cable color coding, cable lugs, Cable gland, nut, bolts and washer with sufficient space as per
modern locks.Full Dust & Vermin Proof Cable gland as per cable size, cable entry . The board is designed and constructed in accordance with
BNBC-2014 & IEEE Electrical wiring. Panel board is provided capacitive information level & All type of danger sign,& panel base plate.Other
Incoming & Outgoing cable Color Code will followed the distribution board by internal wiring, Hinge, Lock, Louver: imported.
2X4MVA Grid Synchronization Control System
Controller
Display
Control Unit
01 No. InteliMains NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
1X Bus Cupler Control Unit
Controller
Display
Control Unit
01 No. InteliMains NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
3X2.5MVA Gas Generator Synchronization Control System
Controller
Display
AVR Control & Dongle
01 No.InteliSys NTC BaseBox
ComAp,Cz- EU
01 No.InteliVision 5
ComAp,Cz- EU
01 No. IG-NTC AVRi
ComAp,Cz- EU
01 No. Dongle LSM+PMS
ComAp,Cz- EU
01 No. IG-NTC AVRi Trans
ComAp,Cz- EU
Control Unit
01 Nos Indication lamps
ABB-India/Equivalent
01 Nos Buzzer
ABB-India/Equivalent
01 Nos Push Button
ABB-India/Equivalent
01 Nos Emergency Stop Push Button
ABB-India/Equivalent
01 Nos Selector Switch
ABB-India/Equivalent
01 Lot Control MCB for secondery protection
Siemens/ Schneider
01 Lot 24VDC Relays
Phoenix- Germany
As per Reverie Standard
Others
Equipment
12. Earthing For Equipments of 33kV 4MVA Substation
Technical Description
Brand & Origin
Installation, testing & Commissioning of the earthing system with which comply
with DESCO, DPDC, PDB, REB, and ELB rules & regulation
Earthing
Cu wire: 12.5 mm Dia
GI pipe: 1.5 Inch Dia (20 FT Long)
Boring Depth: 100FT
Reverie-BD
11. 2400KVAR Automatic PFI Plant (2 Set)
Equipment
Technical Description
Brand & Origin
Supply of 16 SWG sheet steel clad with powder coated 'Siemens gray color/ RAL 7035 color, floor mounting type assembled completely
automatic PFI plant suitable for operation at 415 V, 50Hz. Having 4000A hard drawn electorlytic copper busbars placed on Abonide Fiber.
Including cable color coding, cable lugs, Cable gland, nut, bolts and washer and modern locks . Full Dust & Vermin Proof Cable gland as per
cable size, cable entry. The board is designed and constructed in accordance with BNBC-2014 & IEEE Electrical wiring. Panel board is provided
capacitive information level & All type of danger sign. Panel Board all doors is connected by ECC with earthing bus bar. Other Incoming &
Outgoing cable Color Code will be followed.
PFC Relay
1 no 12 stages automatic power factor correction relay with push button,
indication lamp.
Iskra- Slovenia/
Equivalent
1 no (50x6) 300KVAR, 415V, 50Hz,TP dry type power
capacitors with built in discharge resister. (Stage-12)
1 no (50x6) 300KVAR, 415V, 50Hz,TP dry type power
capacitors with built in discharge resister. (Stage-11)
1 no (50x6) 300KVAR, 415V, 50Hz,TP dry type power
capacitors with built in discharge resister. (Stage-10)
1 no (50x5) 250KVAR, 415V, 50Hz,TP dry type
power capacitors with built in discharge resister. (Stage-09)
1 no (50x5) 250KVAR, 415V, 50Hz,TP dry type
power capacitors with built in discharge resister. (Stage-08)
1 no (50x5) 250KVAR, 415V, 50Hz,TP dry type
power capacitors with built in discharge resister. (Stage-07)
Capacitor Bank
1 no (50x4) 200KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-06)
1 no (50x4) 200KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-05)
Iskra- Slovenia/
Equivalent
1 no (50X3) 150KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-04)
1 no (50X2) 100KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-03)
1 no 50KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-02)
1 no 25KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Stage-01)
1 nos 25KVAR, 415V, 50Hz, TP dry type
power capacitors with built in discharge resister. (Direct)
Magnetic Contact
47 nos Magnetic Contact (MC) for 50KVAR for Capacitor switching.
01 no Magnetic Contact (MC) for 25KVAR for Capacitor switching.
Control & Protection Unit
Others
47 Nos. 100A TP MCCB Molded Case circuit Breaker with Thermal adjustable
& Magnetic standard protection trip unit.
Adjustable Current Rating: (70-100)A
Breaking Capacity: 25KA.
01 Nos. 63A TP MCCB Molded Case circuit Breaker with Thermal adjustable &
Magnetic standard protection trip unit.
Adjustable Current Rating: (28-40)A
Breaking Capacity: 25KA.
Indication lamp
1 Set of control MCB
As per Reverie Standard
Iskra- Slovenia/
Equivalent
ABB-Italy
ABB-India/
Equivalent