TECHNICAL SPECIFICATION
1. SUBSTATION-01 UTILITY BUILDING
1.1. SUPPLY OF PCC-1 (UTILITY AREA)
Technical Description
Sl No.
1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
16
Nos
Assembled By:
Reverie-BD
-A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
Annunciator
3
3.01 24 Windows Annunciator
1
Nos
Minilac-India
3.02 25A, DP, MCB, 10KA
1
Nos
ABB-Germany
1
Nos
ABB-Italy
4.02 32A TP MPCB
1
Nos
ABB
4.03 Type-01 SPD
1
Nos
ABB/Phonix
4.04 6A TP MPCB
1
Nos
ABB
4.05 3 Phase Digital Voltmeter
1
Nos
Reshabh-India
4.06 Voltmeter Selector Switch
1
Nos
ABB
4.07 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL5P10, 15VA
4.08 Reverse Power Relay (32R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.09 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CLPS, 15VA
4.10 Rotor earth fault Relay (64R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.11 6A TP MPCB
1
Nos
ABB
4.12 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.13 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.14 Voltage Monitoring Relay
1
Nos
ABB
Incoming From Distribution Transformer-01 (3500KVA-A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
4.15 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
4.16 Multifunction Meter
Model Number: M4M 20
4.17 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
1
Nos
Reshabh-India
4.18 Ammeter Selector Switch
1
Nos
ABB
4.19 6A TP MPCB
1
Nos
ABB
4.20 Indication lamps: R,Y,B
3
Nos
ABB-India
4.21 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
Incoming From Solar Panel
5
7
Nos
ABB-India
-A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
5.02 32A TP MPCB
1
Nos
ABB-Italy
1
Nos
ABB
5.03 Type-01 SPD
1
Nos
ABB/Phonix
5.04 6A TP MPCB
1
Nos
ABB
5.05 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
5.06 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
5.07 Voltage Monitoring Relay
1
Nos
ABB
5.08 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
5.09 Multifunction Meter
Model Number: M4M 20
3
Nos
Risesun-Tiwan
1
Nos
ABB
5.10 3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.11 Ammeter Selector Switch
1
Nos
ABB
5.12 6A TP MPCB
1
Nos
ABB
5.13 Indication lamps: R,Y,B
3
Nos
ABB-India
5.14 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
Bus-Coupler [For interconnection with PCC-02 Panel]
6
7
Nos
ABB-India
-A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
6.02 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
Outgoing: MCC-03 for Chilled Water Pumps for process - 450 CMH
7
7
Nos
ABB-India
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
7.02 6A TP MPCB
1
Nos
ABB
7.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
7.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
7.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
1
Nos
ABB-Italy
8.02 6A TP MPCB
1
Nos
ABB
8.03 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
8.04 Multifunction Meter
Model Number:
3
Nos
Risesun-Tiwan
1
Nos
ABB
8.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
1
Nos
ABB-Italy
9.02 6A TP MPCB
1
Nos
ABB
9.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
9.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
9.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
Outgoing: MCC-04 for Cooling Water Pumps 1000 CMH-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 66KA.
Outgoing: MCC-05 for Cooling Water Pumps-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
10
Outgoing: MCC-06 for Cooling Water Pumps
ABB-Italy
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
10.02 6A TP MPCB
1
Nos
ABB
10.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
10.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
10.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
11.04 Multifunction Meter
Model Number: M1M 30
11.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
12 Outgoing: Main Lighting Panel
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
12.04 Multifunction Meter
Model Number: M1M 30
12.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
13 Outgoing: 120KVA UPS-02
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
11 Outgoing: Main Lighting Panel-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
ABB-Italy
13.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
13.04 Multifunction Meter
Model Number: M1M 30
13.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
14.04 3 Phase Digital Ammeter
1
Nos
Reshabh-India
14.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
15 Outgoing: Active Filter
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
15.04
Model Number: M1M 30
15.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
16 Outgoing: SPARE
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
16.04
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
14 Outgoing: APFCR Panel-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
16.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
17 Outgoing: SPARE
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
17.03 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
17.04
Model Number: M1M 30
17.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
18 Outgoing: SPARE
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
18.02 6A TP MPCB
1
Nos
ABB
18.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
18.04 Multifunction Meter
Model Number: M1M 30
18.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1.2. SUPPLY OF PCC-2 (UTILITY AREA)
Technical Description
Sl No.
1
Panel Description
QTY Unit
Brand-Origin
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
16
Nos
Assembled By:
Reverie-BD
-A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
Annunciator
3
3.01 24 Windows Annunciator
1
Nos
Minilac-India
3.02 25A, DP, MCB, 10KA
1
Nos
ABB-Germany
1
Nos
ABB-Italy
4.02 32A TP MPCB
1
Nos
ABB
4.03 Type-01 SPD
1
Nos
ABB/Phonix
4.04 6A TP MPCB
1
Nos
ABB
4.05 3 Phase Digital Voltmeter
1
Nos
Reshabh-India
4.06 Voltmeter Selector Switch
1
Nos
ABB
4.07 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL5P10, 15VA
4.08 Reverse Power Relay (32R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.09 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CLPS, 15VA
4.10 Rotor earth fault Relay (64R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.11 6A TP MPCB
1
Nos
ABB
4.12 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.13 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.14 Voltage Monitoring Relay
1
Nos
ABB
4.15 Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
4.16 Multifunction Meter
Model Number: M4M 20
4.17 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
1
Nos
Reshabh-India
4.18 Ammeter Selector Switch
1
Nos
ABB
4.19 6A TP MPCB
1
Nos
ABB
4.20 Indication lamps: R,Y,B
3
Nos
ABB-India
Incoming From Distribution Transformer-02 (3500KVA-A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
4.21 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
TIE Feeder for interconection with PCC-3 (Station transformer)
5
7
Nos
ABB-India
-A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
5.02 32A TP MPCB
1
Nos
ABB-Italy
1
Nos
ABB
5.03 Type-01 SPD
1
Nos
ABB/Phonix
5.04 6A TP MPCB
1
Nos
ABB
5.05 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
5.06 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
5.07 Voltage Monitoring Relay
1
Nos
ABB
5.08 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
5.09 Multifunction Meter
Model Number: M4M 20
3
Nos
Risesun-Tiwan
1
Nos
ABB
5.10 3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.11 Ammeter Selector Switch
1
Nos
ABB
5.12 6A TP MPCB
1
Nos
ABB
5.13 Indication lamps: R,Y,B
3
Nos
ABB-India
5.14 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
Outgoing: Introgen plant
6
7
Nos
ABB-India
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 66KA.
1
Nos
ABB-Italy
6.02 6A TP MPCB
1
Nos
ABB
6.03 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
6.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
6.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
1
Nos
ABB-Italy
Outgoing: PDB-09 for Pump Room-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
7.02 6A TP MPCB
1
Nos
ABB
7.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
7.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
7.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
Outgoing: PDB-10 for AIR DRYER, AIR Compressor room exhaust fan and boiler-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
1
Nos
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
ABB-Italy
8.02 6A TP MPCB
1
Nos
ABB
8.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
8.04 Multifunction Meter
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
8.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
Outgoing: PAPER TUBE, Carton Plant +2 Storied Canteen+ Worker training hall-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
1
Nos
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
ABB-Italy
9.02 6A TP MPCB
1
Nos
ABB
9.03 Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
9.04 Multifunction Meter
Model Number: M1M 30
9.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
10 Outgoing: EFFLUENT TREATMENT PLANT
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
10.03 Current Transformer (CT)
Ratio:800/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
10.04 Multifunction Meter
Model Number: M1M 30
10.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
11 Outgoing: WTP
1
Nos
ABB
7
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
11.04 Multifunction Meter
Model Number: M1M 30
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
11 Outgoing: OIL FREE SCREW TYPE COMPRESSOR-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
11.04 Multifunction Meter
Model Number: M1M 30
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
12 Outgoing: OIL FREE SCREW TYPE COMPRESSOR-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
12.04 Multifunction Meter
Model Number: M1M 30
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
13 Outgoing: OIL FREE SCREW TYPE COMPRESSOR-03 (STAND BY-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
13.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
13.04 Multifunction Meter
Model Number: M1M 30
13.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
14
Outgoing: APFCR Panel-1 (600KVAR)
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
14.04 3 Phase Digital Ammeter
1
Nos
Reshabh-India
14.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
15 Outgoing: APFCR Panel-2 (600KVAR)
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
15.04 3 Phase Digital Ammeter
1
Nos
Reshabh-India
15.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
15 Outgoing: Active Filter
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
15.04
Model Number: M1M 30
15.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
16 Outgoing: SPARE
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
16.04
Model Number: M1M 30
16.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
17 Outgoing: SPARE
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
17.03 Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
17.04
Model Number: M1M 30
17.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
18 Outgoing: SPARE
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
18.02 6A TP MPCB
1
Nos
ABB
18.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
18.04 Multifunction Meter
Model Number: M1M 30
18.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1.3. 500KVAR APFC Panel
Sl No.
1
Technical Description
Panel Description
QTY Unit
Brand-Origin
1.01 Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar-A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
5
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 Indication lamps: R,Y,B
3
Nos
ABB-India
3.06 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07 Ammeter Selector Switch
1
Nos
ABB
3.08 3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.09 Voltmeter Selector Switch
1
Nos
ABB
3.10 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL5P10, 15VA
3.11 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH
3
Nos
Risesun-Tiwan
5
Nos
ABB-India
1
No
Iskra-Slovenia
5.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
5.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
5.03 Indication lamp: ON
1
Nos
ABB
5.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
5.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
5.06 Ammeter Selector Switch
1
Nos
ABB
5.07 Auto Manual Switch
1
Nos
ABB
5.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
5.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
5.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
2
set
Iskra-Slovenia
Incoming Power Supply from PCC-01-F-A (ACB) TP, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F]
Breaking Capacity: 65KA.
PFC Relay
4
4.01 16 Stages Automatic Power factor correction relay with push button,
indication lamp.
5
Stage -1: F-1
5.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
6.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
6.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
6.03 Indication lamp: ON
1
Nos
ABB
6.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
6.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
6.06 Ammeter Selector Switch
1
Nos
ABB
6.07 Auto Manual Switch
1
Nos
ABB
6.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
6.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
6.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
6.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
7.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
7.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
7.03 Indication lamp: ON
1
Nos
ABB
7.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
7.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
7.06 Ammeter Selector Switch
1
Nos
ABB
7.07 Auto Manual Switch
1
Nos
ABB
7.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
7.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
7.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
8.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
8.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
8.03 Indication lamp: ON
1
Nos
ABB
8.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
8.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
6
7
8
Stage -02: F-2
Stage -03: F-3
Stage -04: F-4
8.06 Ammeter Selector Switch
1
Nos
ABB
8.07 Auto Manual Switch
1
Nos
ABB
8.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
8.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
8.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
8.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
9.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
9.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
9.03 Indication lamp: ON
1
Nos
ABB
9.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
9.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
9.06 Ammeter Selector Switch
1
Nos
ABB
9.07 Auto Manual Switch
1
Nos
ABB
9.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
9.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
9.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
9.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
10.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
10.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
10.03 Indication lamp: ON
1
Nos
ABB
10.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
10.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
10.06 Ammeter Selector Switch
1
Nos
ABB
10.07 Auto Manual Switch
1
Nos
ABB
10.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
10.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
10.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
10.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
9
10
11
Stage -05: F-5
Stage -06: F-6
Stage -07: F-7
11.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
11.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
11.03 Indication lamp: ON
1
Nos
ABB
11.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
11.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
11.06 Ammeter Selector Switch
1
Nos
ABB
11.07 Auto Manual Switch
1
Nos
ABB
11.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
11.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
11.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
11.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
12.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
12.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
12.03 Indication lamp: ON
1
Nos
ABB
12.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
12.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
12.06 Ammeter Selector Switch
1
Nos
ABB
12.07 Auto Manual Switch
1
Nos
ABB
12.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
12.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
12.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
12.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
13.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
13.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
13.03 Indication lamp: ON
1
Nos
ABB
13.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
13.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
13.06 Ammeter Selector Switch
1
Nos
ABB
13.07 Auto Manual Switch
1
Nos
ABB
12
13
Stage -08: F-8
Stage -09: F-9
13.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
13.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
13.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
13.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
14.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
14.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14.03 Indication lamp: ON
1
Nos
ABB
14.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
14.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
14.06 Ammeter Selector Switch
1
Nos
ABB
14.07 Auto Manual Switch
1
Nos
ABB
14.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
14.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
14.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
14.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
15.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
15.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15.03 Indication lamp: ON
1
Nos
ABB
15.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
15.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15.06 Ammeter Selector Switch
1
Nos
ABB
15.07 Auto Manual Switch
1
Nos
ABB
15.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
15.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
15.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
15.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
16.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
16.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14
15
16
Stage -10: F-10
Stage -11: F-11
Stage -12: F-12
16.03 Indication lamp: ON
1
Nos
ABB
16.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
16.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
16.06 Ammeter Selector Switch
1
Nos
ABB
16.07 Auto Manual Switch
1
Nos
ABB
16.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
16.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
16.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
16.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
17.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
17.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
17.03 Indication lamp: ON
1
Nos
ABB
17.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
17.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
17.06 Ammeter Selector Switch
1
Nos
ABB
17.07 Auto Manual Switch
1
Nos
ABB
17.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
17.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
17.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
18.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
18.03 Indication lamp: ON
1
Nos
ABB
18.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
18.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
18.06 Ammeter Selector Switch
1
Nos
ABB
18.07 Auto Manual Switch
1
Nos
ABB
18.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
18.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17
18
Stage -13: F-13
Stage -14: F-14
18.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
18.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
19.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
19.03 Indication lamp: ON
1
Nos
ABB
19.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
19.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
19.06 Ammeter Selector Switch
1
Nos
ABB
19.07 Auto Manual Switch
1
Nos
ABB
19.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
19.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
19.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
19.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
20.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
20.03 Indication lamp: ON
1
Nos
ABB
20.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
20.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
20.06 Ammeter Selector Switch
1
Nos
ABB
20.07 Auto Manual Switch
1
Nos
ABB
20.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
20.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
20.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
20.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19
20
Stage -15: F-15
Stage -16: F-16
1.4. 600KVAR APFC Panel
Sl No.
1
Technical Description
Panel Description
QTY Unit
Brand-Origin
1.1
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
Nos
Assembled By:
Reverie-BD
1250A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 Indication lamps: R,Y,B
3
Nos
ABB-India
3.06 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07 Ammeter Selector Switch
1
Nos
ABB
3.08 3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.09 Voltmeter Selector Switch
1
Nos
ABB
3.10 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL5P10, 15VA
3.11 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH
3
Nos
Risesun-Tiwan
5
Nos
ABB-India
1
No
Iskra-Slovenia
5.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
5.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
5.03 Indication lamp: ON
1
Nos
ABB
5.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
5.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
5.06 Ammeter Selector Switch
1
Nos
ABB
5.07 Auto Manual Switch
1
Nos
ABB
5.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
5.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
5.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
2
set
Iskra-Slovenia
2
2.1
Incoming Power Supply from PCC-01-F-A (ACB) TP, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F]
Breaking Capacity: 65KA.
PFC Relay
4
4.01 16 Stages Automatic Power factor correction relay with push button,
indication lamp.
5
Stage -1: F-1
5.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
6.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
6.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
6.03 Indication lamp: ON
1
Nos
ABB
6.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
6.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
6.06 Ammeter Selector Switch
1
Nos
ABB
6.07 Auto Manual Switch
1
Nos
ABB
6.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
6.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
6.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
6.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
7.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
7.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
7.03 Indication lamp: ON
1
Nos
ABB
7.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
7.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
7.06 Ammeter Selector Switch
1
Nos
ABB
7.07 Auto Manual Switch
1
Nos
ABB
7.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
7.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
7.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
8.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
8.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
8.03 Indication lamp: ON
1
Nos
ABB
8.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
8.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
6
7
8
Stage -02: F-2
Stage -03: F-3
Stage -04: F-4
8.06 Ammeter Selector Switch
1
Nos
ABB
8.07 Auto Manual Switch
1
Nos
ABB
8.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
8.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
8.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
8.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
9.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
9.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
9.03 Indication lamp: ON
1
Nos
ABB
9.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
9.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
9.06 Ammeter Selector Switch
1
Nos
ABB
9.07 Auto Manual Switch
1
Nos
ABB
9.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
9.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
9.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
9.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
-A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
10.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
10.03 Indication lamp: ON
1
Nos
ABB
10.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
10.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
10.06 Ammeter Selector Switch
1
Nos
ABB
10.07 Auto Manual Switch
1
Nos
ABB
10.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
10.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
10.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
10.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
9
10
11
Stage -05: F-5
Stage -06: F-6
Stage -07: F-7
11.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
11.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
11.03 Indication lamp: ON
1
Nos
ABB
11.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
11.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
11.06 Ammeter Selector Switch
1
Nos
ABB
11.07 Auto Manual Switch
1
Nos
ABB
11.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
11.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
11.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
11.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
12.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
12.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
12.03 Indication lamp: ON
1
Nos
ABB
12.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
12.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
12.06 Ammeter Selector Switch
1
Nos
ABB
12.07 Auto Manual Switch
1
Nos
ABB
12.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
12.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
12.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
12.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
13.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
13.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
13.03 Indication lamp: ON
1
Nos
ABB
13.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
13.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
13.06 Ammeter Selector Switch
1
Nos
ABB
13.07 Auto Manual Switch
1
Nos
ABB
12
13
Stage -08: F-8
Stage -09: F-9
13.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
13.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
13.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
13.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
14.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
14.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14.03 Indication lamp: ON
1
Nos
ABB
14.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
14.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
14.06 Ammeter Selector Switch
1
Nos
ABB
14.07 Auto Manual Switch
1
Nos
ABB
14.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
14.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
14.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
14.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
15.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
15.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15.03 Indication lamp: ON
1
Nos
ABB
15.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
15.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15.06 Ammeter Selector Switch
1
Nos
ABB
15.07 Auto Manual Switch
1
Nos
ABB
15.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
15.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
15.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
15.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
16.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
16.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14
15
16
Stage -10: F-10
Stage -11: F-11
Stage -12: F-12
16.03 Indication lamp: ON
1
Nos
ABB
16.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
16.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
16.06 Ammeter Selector Switch
1
Nos
ABB
16.07 Auto Manual Switch
1
Nos
ABB
16.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
16.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
16.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
16.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
17.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
17.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
17.03 Indication lamp: ON
1
Nos
ABB
17.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
17.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
17.06 Ammeter Selector Switch
1
Nos
ABB
17.07 Auto Manual Switch
1
Nos
ABB
17.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
17.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
17.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
18.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
18.03 Indication lamp: ON
1
Nos
ABB
18.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
18.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
18.06 Ammeter Selector Switch
1
Nos
ABB
18.07 Auto Manual Switch
1
Nos
ABB
18.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
18.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17
18
Stage -13: F-13
Stage -14: F-14
18.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
18.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
19.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
19.03 Indication lamp: ON
1
Nos
ABB
19.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
19.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
19.06 Ammeter Selector Switch
1
Nos
ABB
19.07 Auto Manual Switch
1
Nos
ABB
19.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
19.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
19.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
19.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
20.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
20.03 Indication lamp: ON
1
Nos
ABB
20.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
20.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
20.06 Ammeter Selector Switch
1
Nos
ABB
20.07 Auto Manual Switch
1
Nos
ABB
20.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
20.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
20.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
20.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19
20
Stage -15: F-15
Stage -16: F-16
1.5. MCC 03 For Chilled water pump for process 450 CMH
Technical Description
Sl No.
1
Panel Description
QTY Unit
Brand-Origin
1.1
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
2
2.1
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
1600A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PCC-01-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
4
10
1
Outgoing: CHILLED WATER PUMP(01,02,03,04,05,06,07,08) WORKING & (09)STANDBY
4.01 250A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
9
Nos
ABB-Italy
4.02 6A TP MPCB
9
Nos
ABB
4.03 90KW VFD, Variable Frequency Drive
9
Nos
ABB-Italy
4.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
27
Nos
Risesun-Tiwan
9
Nos
Reshabh-India
63
Nos
ABB-India
4.04 Digital Ammeter
4.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
1.6. MCC 04 For Cooling Water Pump
Technical Description
Sl No.
1
Panel Description
QTY Unit
Brand-Origin
1.1
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
2
2.1
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
9
1250A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Incoming From PCC-01-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
4
Outgoing: COOLING WATER PUMP(01,02) WORKING & (03)STANDBY
4.01 500A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
3
Nos
ABB-Italy
4.02 6A TP MPCB
3
Nos
ABB
4.03 160KW VFD, Variable Frequency Drive
3
Nos
ABB-Italy
4.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
9
Nos
Risesun-Tiwan
4.04 Digital Ammeter
3
Nos
Reshabh-India
21
Nos
ABB-India
3
Nos
ABB-Italy
5.02 6A TP MPCB
3
Nos
ABB
5.03 75KW VFD, Variable Frequency Drive
3
Nos
ABB-Italy
4.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
5
5.01
Outgoing: HOT WATER PUMP(01,02) WORKING & (03)STANDBY
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Current Transformer (CT)
5.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
9
Nos
Risesun-Tiwan
5.04 Digital Ammeter
3
Nos
Reshabh-India
21
Nos
ABB-India
2
Nos
ABB-Italy
6.02 6A TP MPCB
2
Nos
ABB
6.03 45KW VFD, Variable Frequency Drive
2
Nos
ABB-Italy
Current Transformer (CT)
6.03 Ratio: 100/5A
Accuracy and burden: CL:01, 15VA
6
Nos
Risesun-Tiwan
6.04 Digital Ammeter
2
Nos
Reshabh-India
14
Nos
ABB-India
5.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
6
6.01
Outgoing: CHILLED WATER PUMP(01) WORKING & (02)STANDBY
100A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
6.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
1.7. MCC 05 For Cooling Water Pump For VAM & Compressor
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
2
2.1
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
1600A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Incoming From PCC-01-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
4.01 500A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
4
Nos
ABB-Italy
4.02 6A TP MPCB
4
Nos
ABB
4.03 160KW VFD, Variable Frequency Drive
4
Nos
ABB-Italy
12
Nos
Risesun-Tiwan
4
Nos
Reshabh-India
28
Nos
ABB-India
4
Outgoing: COOLING WATER PUMP(01,02,03,04) WORKING
4.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
4.04 Digital Ammeter
4.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
1.8.
MCC 06 For Cooling Water Pump For VAM & Compressor
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
2
2.1
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
1600A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Incoming From PCC-01-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
4
Outgoing: COOLING WATER PUMP (05,06,07,08) WORKING & (09) STANDBY
4.01 500A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
5
Nos
ABB-Italy
4.02 6A TP MPCB
5
Nos
ABB
4.03 160KW VFD, Variable Frequency Drive
5
Nos
ABB-Italy
15
Nos
Risesun-Tiwan
5
Nos
Reshabh-India
35
Nos
ABB-India
4.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
4.04 Digital Ammeter
4.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
1.9.
Technical Description
Sl No.
1
1.1
PDB-09 for Pump Room
QTY Unit
Brand-Origin
Panel Description
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
2
2.1
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
6
1600A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Incoming From PCC-02-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
4
Outgoing: STP 75-KLD
4.01 160A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
5.01 250A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
5.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
6.01 400A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
6.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
7.01 63A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
3
Nos
ABB-Italy
7.02 6A TP MPCB
3
Nos
ABB
7.03 Magnetic Contactor for Star Delta
9
Nos
ABB-Bulgaria
7.04 Thermal Overload Relay
3
No.
ABB
7.05 Relay
3
No.
9
Nos
Risesun-Tiwan
3
Nos
Reshabh-India
15
Nos
ABB-India
4.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
4.04
Model Number: M1M 30
4.05 Indication lamps: ON, OFF, TRIP
5
Outgoing: EFFLUENT TREATMENT PLANT (450KLD)
5.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
5.04
Model Number: M1M 30
5.05 Indication lamps: ON, OFF, TRIP
6
Outgoing: MULTI EFFECT EVAPORATOR (FUTURE)
6.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
6.04
Model Number: M1M 30
6.05 Indication lamps: ON, OFF, TRIP
7
Outgoing: FILTER FEED PUMP(01,02)- WORKING & (03)-STANDBY
7.06 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL:01, 15VA
7.07 Digital Ammeter
7.08 Indication lamps: ON, OFF, TRIP, R, ES
8
Outgoing: FILTER WATER HPN CONTROL PANEL
8.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
9.01 125A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
9.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
10.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
10.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
12.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
12.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
13.01 16A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
14.01 16A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
14.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
9
Outgoing: PROCESS RO WATER HPN CONTROL PANEL
9.03 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
9.04
Model Number: M1M 30
9.05 Indication lamps: ON, OFF, TRIP
10
11
Outgoing: BOILER RO WATER HPN CONTROL PANEL
Outgoing: MAIN FIRE PUMP CONTROL PANEL
11.03 Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
11.04
Model Number: M1M 30
11.05 Indication lamps: ON, OFF, TRIP
12
13
14
15
Outgoing: JOCKEY PUMP CONTROL PANEL
Outgoing: CONTROL PANEL EFFLUENT PUMP 6 FOR BOILER AREA
Outgoing: CONTROL PANEL EFFLUENT PUMP 7 FOR BOILER AREA
Outgoing: CONTROL PANEL EFFLUENT PUMP 8 FOR WTP AREA
15.01 16A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
15.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
16.01 16A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
16.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
9
Nos
ABB-Germany
1
Nos
ABB-Germany
18.01 16A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
18.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
19.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
19.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
20.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
16
17
Outgoing: CONTROL PANEL EFFLUENT PUMP 9 FOR WTP AREA
Outgoing: FEEDER 16
17.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
17.04
Model Number: M1M 30
17.05 Indication lamps: ON, OFF, TRIP
17.06 Sub Outgoing:
17.06. 63A, FP, MCB-Miniature Circuit Breaker-A, DP, MCB-Miniature Circuit Breaker
02
18
19
20
Outgoing: Spare
Outgoing: Spare
Outgoing: Spare
20.03 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
20.04
Model Number: M1M 30
20.05 Indication lamps: ON, OFF, TRIP
21
Outgoing: Spare
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
21.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
22.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
21.03 Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
21.04
Model Number: M1M 30
21.05 Indication lamps: ON, OFF, TRIP
22
Outgoing: Spare
22.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
22.04
Model Number: M1M 30
22.05 Indication lamps: ON, OFF, TRIP
1.10. PDB-10 Panel- For Air Dryer & Air Compressor Room
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 1600/5A
Accuracy and burden: CL5P10, 15VA
3
Nos
Risesun-Tiwan
2
2.1
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
9
1600A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Incoming From PCC-02-F-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
4.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C & ELR)
Breaking Capacity: 50KA.
10
Nos
ABB-Italy
4.02 Indication lamps: ON, OFF, TRIP
30
Nos
ABB-India
5.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C & ELR)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
5.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
6.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C & ELR)
Breaking Capacity: 50KA.
2
Nos
ABB-Italy
6.02 Indication lamps: ON, OFF, TRIP
6
Nos
ABB-India
7.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C & ELR)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
7.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB-India
Outgoing: AIR COMPRESSOR ROOM EX FAN(1,2,3,4,5,6,7,8,9,-A, MPCB, Motor Protection Circuit Breker
10
No.
ABB-Italy
8.02 6A TP MPCB
10
Nos
ABB
30
Nos
10
Nos
10
Nos
ABB
60
Nos
ABB-India
9.01 250A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
3
Nos
ABB-Italy
9.02 6A TP MPCB
3
Nos
ABB
9
Nos
Risesun-Tiwan
3
Nos
ABB
4
5
6
7
Outgoing: AIR DRYER (8BAR)- 1,2,3,4,5,6,7,8,9,10 Working
Outgoing: AIR DRYER (8BAR)- 11 Standby
Outgoing: AIR DRYER (10BAR)- 1,2 Working
Outgoing: AIR DRYER (10BAR)- 3 Standby
8.03 Current Transformer (CT)
Ratio: 30/5A
Accuracy and burden: CL:01, 15VA
8.04
01 No. Digital Ammeter
8.05 5KW DOL Satrter
8.06
9
Indication lamps: ON, OFF, TRIP, R, ES, A/M
Risesun-Tiwan
Reshabh-India
Outgoing: BOILER (1,2) WORKING & (3) STANDBY
9.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
9.04
Model Number: M1M 30
9.05 Indication lamps: ON, OFF, TRIP
9
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
8
Nos
ABB-Germany
2
No.
ABB-Italy
2
Nos
10
Outgoing: AHU UTILITY SUBSTATION- 55000 CFM
10.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
10.04
Model Number: M1M 30
10.05 Indication lamps: ON, OFF, TRIP
11
Outgoing: AHU-COGEN BUILDING- 35000 CFM
11.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
11.04
Model Number: M1M 30
11.05 Indication lamps: ON, OFF, TRIP
12
Outgoing: FEEDER 30
12.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
12.04
Model Number: M1M 30
12.05 Indication lamps: ON, OFF, TRIP
12.06 Sub Outgoing:
12.06. 63A, FP, MCB-Miniature Circuit Breaker
01
13 Outgoing: SPARE
13.01
10A, MPCB, Motor Protection Circuit Breker
13.02 6A TP MPCB
13.03 Current Transformer (CT)
Ratio: 30/5A
Accuracy and burden: CL:01, 15VA
13.04
Digital Ammeter
13.05 5KW DOL Satrter
ABB
Risesun-Tiwan
6
Nos
2
Nos
2
Nos
Reshabh-India
ABB
13.06
Indication lamps: ON, OFF, TRIP, R, ES, A/M
12
Nos
ABB-India
14.01 32A, TP+N MCCB with TH. Based Rel.( O/C, S/C & ELR)
Breaking Capacity: 50KA.
2
Nos
ABB-Italy
14.02 Indication lamps: ON, OFF, TRIP
6
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
-A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
14
15
Outgoing: SPARE
Outgoing: SPARE
15.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
15.04
Model Number: M1M 30
15.05 Indication lamps: ON, OFF, TRIP
16
Outgoing: SPARE
16.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
16.04
Model Number: M1M 30
16.05 Indication lamps: ON, OFF, TRIP
1.11.
Technical Description
Sl No.
1
1.1
2
2.1
3
MLDB- Main Lighting Distribution Board
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
800A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
Incoming From: 500KVA Lightning Transformer & PCC-1-F5 ( by 800A FP On load Change Over
Switch)
3.01 800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 36KA.
1
Nos
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL5P10, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB-India
4.01 250A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
4.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
5.01 200A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
5.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
6.01 200A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
6.02 6A TP MPCB
1
Nos
ABB
4
Outgoing: 120 KVA-01 UPS for Emergency Lighting
4.03 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
4.04
Model Number: M1M 30
4.05 Indication lamps: ON, OFF, TRIP
5
Outgoing: SUB MLDB-01 at Utility Building
5.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
5.04
Model Number: M1M 30
5.05 Indication lamps: ON, OFF, TRIP
6
ABB-Italy
Outgoing: SUB MLDB-02 at CP Building
6.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
6.04
Model Number: M1M 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
7.01 400A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
7.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
8.01 400A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
8.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
9.01 200A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
9.02 6A TP MPCB
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
6.05 Indication lamps: ON, OFF, TRIP
7
Outgoing: SUB MLDB-03 at DTY Building
7.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
7.04
Model Number: M1M 30
7.05 Indication lamps: ON, OFF, TRIP
8
Outgoing: Spare
8.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
8.04
Model Number: M1M 30
8.05 Indication lamps: ON, OFF, TRIP
9
Outgoing: Spare
9.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
9.04
Model Number: M1M 30
9.05 Indication lamps: ON, OFF, TRIP
1.12.
Technical Description
Sl No.
1
MELDB- Main Emergency Lighting Distribution Board
Panel Description
QTY Unit
Brand-Origin
1.1
2
2.1
3
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
Nos
Assembled By:
Reverie-BD
250A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
Incoming From: 120 KVA-01 UPS for Emergency Lighting
3.01 250A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F) with shunt
trip
Breaking Capacity: 36KA.
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL1, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10
4
Nos
ABB-India
4.01 100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
3
Nos
ABB-Italy
4.02 Indication lamps: ON, OFF, TRIP
9
Nos
ABB-India
5.01 100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
2
Nos
ABB-Italy
5.02 Indication lamps: ON, OFF, TRIP
6
Nos
ABB-India
4
5
Indication lamps: ON, OFF, TRIP, ET
Outgoing: SUB Emergency Lighting Panel-01, 02, 03
Outgoing: Spare
1.13.
Technical Description
Sl No.
1
1.1
2
Main UPS Panel
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
Nos
Assembled By:
Reverie-BD
2.1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
1
Nos
ABB
3.07 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL1, 15VA
3.08 Multifunction Meter
Model Number: M4M 20
3.09 Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
3.10
4
Nos
ABB-India
4.01 100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
3
Nos
ABB-Italy
4.02 Indication lamps: ON, OFF, TRIP
9
Nos
ABB-India
5.01 100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
2
Nos
ABB-Italy
5.02 Indication lamps: ON, OFF, TRIP
6
Nos
ABB-India
3
250A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From: PCC-01-F4 (120KVA UPS-02, for UPS Power)
3.01 250A, TP+N MCCB with MP. Based Rel.( O/C, S/C, E/F) with shunt
trip
Breaking Capacity: 65KA.
3.02 32A TP MPCB
4
5
1
Indication lamps: ON, OFF, TRIP, ET
Outgoing: SUB UPS Panel-01, 02, 03
Outgoing: Spare
1.14. SUB MLDB-01
Technical Description
Sl No.
1
1.01
QTY Unit
Brand-Origin
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
200A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
3.01 with Shunt Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
2
Common Bus-bar
2.01 200A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
Incoming From MLDB-F1
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 200/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
21
Nos
ABB-Germany
QTY Unit
Brand-Origin
4
4.01
Outgoing:
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.15. SUB MLDB-02
Technical Description
Sl No.
1
1.01
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
200A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
3.01 with Shunt Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 200/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
18
Nos
ABB-Germany
QTY Unit
Brand-Origin
2
Common Bus-bar
2.01 200A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
4
4.01
Incoming From MLDB-F1
Outgoing:
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.16. SUB MLDB-03
Technical Description
Sl No.
1
Panel Description
1.01
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
400A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
3.01 with Shunt Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 400/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
36
Nos
ABB-Germany
QTY Unit
Brand-Origin
2
Common Bus-bar
2.01 400A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
4
4.01
Incoming From MLDB-F1
Outgoing:
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.17. SELDB-01 Sub Emegency Lighthing Distribution Board
Technical Description
Sl No.
1
1.01
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
2
Common Bus-bar
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
Incoming From MELDB-F1
3.06
Multifunction Meter
Model Number: M4M 20
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
17
Nos
ABB-Germany
QTY Unit
Brand-Origin
4
4.01
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.18. SELDB-02 Sub Emegency Lighthing Distribution Board
Technical Description
Sl No.
1
1.01
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
14
Nos
ABB-Germany
QTY Unit
Brand-Origin
2
Common Bus-bar
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
4
4.01
Incoming From Main Emergency Lightning Panel-F3
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.19. SELDB-03 Sub Emegency Lighthing Distribution Board
Technical Description
Sl No.
1
1.01
2
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
Common Bus-bar
1
Nos
1
Set
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
20
Nos
ABB-Germany
QTY Unit
Brand-Origin
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
4
4.01
Incoming From Main Emergency Lightning Panel-F3
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.20. SUB UPS Panel -01
Technical Description
Sl No.
1
1.01
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
2
Common Bus-bar
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
Incoming From Main UPS Panel F1
4
4.01
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
15
Nos
ABB-Germany
QTY Unit
Brand-Origin
1.21. SUB UPS Panel -02
Technical Description
Sl No.
1
1.01
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
1
Nos
1
Set
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
15
Nos
ABB-Germany
QTY Unit
Brand-Origin
2
Common Bus-bar
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
4
4.01
Incoming From Main UPS Panel F2
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
1.22. SUB UPS Panel -03
Technical Description
Sl No.
1
1.01
2
Panel Description
ABB Standard DB Panel
Details: As per attached Panel Catalogue
Nos
1
Set
Common Bus-bar
2.01 100A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
3
1
Incoming From Main UPS Panel F3
Coppertech/
Meghna - BD
100A, TP+N MCCB with TH. Based Rel.( O/C, S/C, E/F) with Shunt
3.01 Trip.
Breaking Capacity: 36KA.
1
Nos
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
Current Transformer (CT)
3.05 Ratio: 100/5A
CL-1, 15VA
Multifunction Meter
3.06
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3.07 Indication lamps: R,Y,B
3
Nos
ABB-India
3.08 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
19
Nos
ABB-Germany
4
4.01
ABB-Italy
Outgoing:
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
TECHNICAL SPECIFICATION
1. SUBSTATION-02 UTILITY BUILDING
1.1. SUPPLY OF PCC-04 (POY/FDY AREA - CRITICAL LOADS)
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
Assembled By:
Reverie-BD
8
Nos
1
Set
Coppertech/
Meghna - BD
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-01 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.06
Voltmeter Selector Switch
1
Nos
ABB
3.07
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL5P10, 15VA
Reverse Power Relay (32R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
Risesun-Tiwan
3.10
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CLPS, 15VA
Rotor earth fault Relay (64R)
1
Nos ABB/ Equivalent
3.11
6A TP MPCB
1
Nos
ABB
3.12
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
3.13
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
3.14
Voltage Monitoring Relay
1
Nos
ABB
3.15
6
Nos
Risesun-Tiwan
1
Nos
ABB
3.17
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.18
Ammeter Selector Switch
1
Nos
ABB
3.19
6A TP MPCB
1
Nos
ABB
-
3.08
3.09
3.16
5000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From Distribution Transformer-04 (3500KVA)
3.20
Indication lamps: R,Y,B
3
Nos
ABB-India
3.21
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Incoming From Solar Panel
9
Nos
ABB-India
1
Nos
ABB-Italy
4.02
1250A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
32A TP MPCB
1
Nos
ABB
4.03
Type-01 SPD
1
Nos
ABB/Phonix
4.04
6A TP MPCB
1
Nos
ABB
4.05
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.06
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.07
Voltage Monitoring Relay
1
Nos ABB/Equivalent
4.08
Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.10
3 Phase Digital Ammeter
1
Nos
Reshabh-India
4.11
Ammeter Selector Switch
1
Nos
ABB
4.12
6A TP MPCB
1
Nos
ABB
4.13
Indication lamps: R,Y,B
3
Nos
ABB-India
4.14
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Bus-Coupler 01 [For interconnection with PCC-05 Panel]
9
Nos
ABB-India
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Outgoing: PDB-01 for Auxilary Loads of POY/FDY Building
9
Nos
ABB-India
800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
6.02
6A TP MPCB
1
Nos
ABB
6.03
Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
4
4.01
4.09
5
5.01
-
6.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
6.05
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
7
7.01
Outgoing: Wings FDY+ Draw Unit-Feeder-01-DC Cabinet ( Line 25,26)(POY/FDY Building)
400A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
7.02
6A TP MPCB
1
Nos
ABB
7.03
Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
7.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
7.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
8
8.01
Outgoing: Wings FDY+ Draw Unit-Feeder-02-DC Cabinet ( Line 27,28)(POY/FDY Building)
400A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
6A TP MPCB
1
Nos
ABB-Italy
1
Nos
ABB
8.03
Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
8.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
8.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
8.02
9
Outgoing: Machine- Line B 16 Positions(Line 14-15)DC Cabinet ( Line 14-15)(POY/FDY Building)
9.01
315A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
9.02
6A TP MPCB
1
Nos
ABB
9.03
Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
9.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
9.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
10
Outgoing: Machine- Line A1-A2 16 Positions(Line 11,12,13)DC Cabinet ( Line
11,12,13)(POY/FDY Building)
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
10.03 Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
10.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
10.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
11
Outgoing: Machine- Line A3-A4 16 Positions(Line 16-17)DC Cabinet ( Line 16,17)(POY/FDY
Building)
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
11.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
13.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12
13
Outgoing: Ac-Box-01-Quench-AHU Panel (POY/FDY Building)
Outgoing: Ac-Box-02-Quench-AHU Panel (POY/FDY Building)
13.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
13.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
14.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
14.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Digital Ammeter
15.04
3
Nos
Risesun-Tiwan
1
Nos
ABB
15.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
Outgoing: APFCR Panel-02(500KVAR)
16
8
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Digital Ammeter
16.04
3
Nos
Risesun-Tiwan
1
Nos
ABB
16.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
14
Outgoing: Ac-Box-03-Quench-AHU Panel (POY/FDY Building)
Outgoing: APFCR Panel-01(500KVAR-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
Outgoing: Active Filter-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
17.02 6A TP MPCB
1
Nos
ABB
17.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
17.04
Model Number: MIM 30
17.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
Outgoing: Spare
18
3
Nos
Risesun-Tiwan
1
Nos
ABB
8
Nos
ABB
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
18.02 6A TP MPCB
1
Nos
ABB
18.03 Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
18.04 Multifunction Meter
Model Number: MIM 30
18.05 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
3
Nos
Risesun-Tiwan
1
Nos
ABB
7
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
19.02 6A TP MPCB
1
Nos
ABB
19.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
19.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
19.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
20.02 6A TP MPCB
1
Nos
ABB
19
ABB-Italy
Outgoing: Spare
20.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
20.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
20.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1.2. SUPPLY OF PDB-01 for Auxilary Loads of POY/FDY Building
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
4
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
800A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
& with Shunt Trip.
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06
Ammeter Selector Switch
1
Nos
ABB
3.07
Multifunction Meter
Model Number: M4M 20
1
Nos
ABB
3.08
Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL-01, 15VA
3
Nos
Risesun-Tiwan
3.09
Indication lamps: R,Y,B
3
Nos
ABB-India
4
Nos
ABB-India
200A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02
6A TP MPCB
1
Nos
ABB
4.03
Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
-
-
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
800A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PCC-04-F1
Indication lamps: ON, OFF, TRIP,ET
Outgoing: SDB-01 for Septic Tank & Auxilary Loads
4.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
4.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
125A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
5.02
6A TP MPCB
1
Nos
ABB
5.03
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
40A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
40A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
7.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
8
8.01
Outgoing: Ductable Unit-03-8TR(Spin Pack Assembly Room)
40A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
9
9.01
Outgoing: Ductable Unit-04-8TR(Spin Pack Assembly Room)
40A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: ACDB-01 for Ground Floor (0.0 MTR LVL-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
10.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: ACDB-02 for Third Floor (15.5 MTR LVL-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
5
5.01
-
9.02
Outgoing: MCC-01 (Control Room, @ 15.50 (Near Spin Finish Kitchen))
Outgoing: Ductable Unit-01-8TR(Boiler Room)
Outgoing: Ductable Unit-02-8TR(Boiler Room)
Outgoing: Data logging Control Cabinet-Line 25,26,27,-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
12.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Data logging Control Cabinet-Line 11,12,13,16,-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Data logging Control Cabinet-Line 14,-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Boiler Panel-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
14.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Lift-01(Grid No-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
15.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Lift-02(Grid No-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
15.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: RO+DI Plant-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
16.04 Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
16.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Process DM water HPN Control Panel-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
17.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
18.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
19.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
20.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
21.02 6A TP MPCB
1
Nos
ABB
21.03 Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL:01, 15VA
21.04 Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
21.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
22.1.3 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
22.1.4 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL-01, 15VA
22.1.5 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
3
Nos
ABB
1
Nos
ABB-Italy
22
Outgoing:
22.1 Incoming-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
22.1.2 6A TP MPCB
22.2
Outgoing
22.2.1 Outgoing: Multi Receptacle(Third Floor)
22.2.1. 63A, 4P MCB
1
Breaking Capacity: 10KA
22.2.2 Outgoing: Multi Receptacle(Third Floor)
22.2.2. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.3 Outgoing: Raw Power Distribution Board(POY/FDY Building)
22.2.3. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.4 Outgoing: Raw Power Distribution Board(POY/FDY Building)
22.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.5 Outgoing: Spare
22.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.6 Outgoing:Spare
22.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.7 Outgoing: Spare
22.2.7. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.8 Outgoing: Spare
22.2.8. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1.3 500KVAR APFC Panel
Sl No.
1
1.1
Technical Description
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
Nos
Assembled By:
Reverie-BD
1000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
1000A (ACB) TP, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
Indication lamps: R,Y,B
3
Nos
ABB-India
3.06
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
3 Phase Digital Voltmeter
1
Nos
Reshabh-India
-
Incoming Power Supply from PCC-01-F7
3.09
Voltmeter Selector Switch
1
Nos
ABB
3.10
Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL5P10, 15VA
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH
3
Nos
Risesun-Tiwan
5
Nos
ABB-India
1
No
Iskra-Slovenia
-
PFC Relay
16 Stages Automatic Power factor correction relay with push button,
indication lamp.
Stage -1: F-1
5.01
250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
5.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
5.03
Indication lamp: ON
1
Nos
ABB
5.04
3
Nos
Risesun-Tiwan
5.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.06
Ammeter Selector Switch
1
Nos
ABB
5.07
Auto Manual Switch
1
Nos
ABB
5.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
-
Stage -02: F-2
6.01
250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
6.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
6.03
Indication lamp: ON
1
Nos
ABB
6.04
3
Nos
Risesun-Tiwan
6.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
6.06
Ammeter Selector Switch
1
Nos
ABB
6.07
Auto Manual Switch
1
Nos
ABB
6.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
1
Nos
ABB/SIEMENS
-
Stage -03: F-3
125A Switch Fuse Unit [SFU]
7.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
7.03
Indication lamp: ON
1
Nos
ABB
7.04
3
Nos
Risesun-Tiwan
7.05
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
7.06
Ammeter Selector Switch
1
Nos
ABB
7.07
Auto Manual Switch
1
Nos
ABB
7.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
-
Stage -04: F-4
8.01
125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
8.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
8.03
Indication lamp: ON
1
Nos
ABB
8.04
3
Nos
Risesun-Tiwan
8.05
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
8.06
Ammeter Selector Switch
1
Nos
ABB
8.07
Auto Manual Switch
1
Nos
ABB
8.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
-
Stage -05: F-5
9.01
63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
9.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
9.03
Indication lamp: ON
1
Nos
ABB
9.04
3
Nos
Risesun-Tiwan
9.05
Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
9.06
Ammeter Selector Switch
1
Nos
ABB
9.07
Auto Manual Switch
1
Nos
ABB
9.08
Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
1
set
Iskra-Slovenia
9.09
Push Button: ON, OFF
2
Nos
ABB
9.10
25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
10.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
10.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
10.03 Indication lamp: ON
1
Nos
ABB
10.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
10.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
10.06 Ammeter Selector Switch
1
Nos
ABB
10.07 Auto Manual Switch
1
Nos
ABB
10.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
10.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
10.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
10.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
11.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
11.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
11.03 Indication lamp: ON
1
Nos
ABB
11.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
11.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
11.06 Ammeter Selector Switch
1
Nos
ABB
11.07 Auto Manual Switch
1
Nos
ABB
11.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
11.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
11.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
11.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
12.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
12.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
12.03 Indication lamp: ON
1
Nos
ABB
9.11
10
11
12
Stage -06: F-6
Stage -07: F-7
Stage -08: F-8
12.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
12.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
12.06 Ammeter Selector Switch
1
Nos
ABB
12.07 Auto Manual Switch
1
Nos
ABB
12.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
12.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
12.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
12.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
13.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
13.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
13.03 Indication lamp: ON
1
Nos
ABB
13.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
13.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
13.06 Ammeter Selector Switch
1
Nos
ABB
13.07 Auto Manual Switch
1
Nos
ABB
13.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
13.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
13.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
13.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
14.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
14.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14.03 Indication lamp: ON
1
Nos
ABB
14.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
14.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
14.06 Ammeter Selector Switch
1
Nos
ABB
14.07 Auto Manual Switch
1
Nos
ABB
14.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
14.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
14.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
1
set
Iskra-Slovenia
13
14
Stage -09: F-9
Stage -10: F-10
14.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
15.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
15.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15.03 Indication lamp: ON
1
Nos
ABB
15.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
15.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15.06 Ammeter Selector Switch
1
Nos
ABB
15.07 Auto Manual Switch
1
Nos
ABB
15.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
15.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
15.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
15.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
16.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
16.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
16.03 Indication lamp: ON
1
Nos
ABB
16.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
16.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
16.06 Ammeter Selector Switch
1
Nos
ABB
16.07 Auto Manual Switch
1
Nos
ABB
16.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
16.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
16.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
16.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
17.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
17.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
17.03 Indication lamp: ON
1
Nos
ABB
17.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
17.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15
16
17
Stage -11: F-11
Stage -12: F-12
Stage -13: F-13
17.06 Ammeter Selector Switch
1
Nos
ABB
17.07 Auto Manual Switch
1
Nos
ABB
17.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
17.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
17.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
18.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
18.03 Indication lamp: ON
1
Nos
ABB
18.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
18.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
18.06 Ammeter Selector Switch
1
Nos
ABB
18.07 Auto Manual Switch
1
Nos
ABB
18.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
18.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
18.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
18.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
19.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
19.03 Indication lamp: ON
1
Nos
ABB
19.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
19.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
19.06 Ammeter Selector Switch
1
Nos
ABB
19.07 Auto Manual Switch
1
Nos
ABB
19.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
19.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
19.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
19.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18
19
20
Stage -14: F-14
Stage -15: F-15
Stage -16: F-16
20.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
20.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
20.03 Indication lamp: ON
1
Nos
ABB
20.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
20.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
20.06 Ammeter Selector Switch
1
Nos
ABB
20.07 Auto Manual Switch
1
Nos
ABB
20.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
20.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
20.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
20.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.12 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
20.13 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
1.4. SUPPLY OF SDB-01 for Septic Tank-02 and Auxilary Loads
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2
Nos
Assembled By:
Reverie-BD
200A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
200A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
& with Shunt Trip.
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.06
Ammeter Selector Switch
1
Nos
ABB
-
Incoming From PDB-01-F2
3.07
Multifunction Meter
Model Number: M4M 20
1
Nos
ABB
3.08
3
Nos
Risesun-Tiwan
3.09
Current Transformer (CT)
Ratio: 200/5A
Accuracy and burden: CL-01, 15VA
Indication lamps: R,Y,B
3
Nos
ABB-India
3.10
Indication lamps: ON, OFF, TRIP,ET
4
Nos
ABB-India
4
4.01
Outgoing: Multi Receptacle(Ground Floor)
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
Outgoing: Septic Tank-02 ( Pump-02 Stand By-A TP MPCB
1
Nos
ABB
11.02 6A TP MPCB
1
Nos
ABB
11.03 3 Phase Digital Ammeter
1
Nos
Reshabh-India
11.04 Current Transformer (CT)
Ratio:
Accuracy and burden: CL-01, 15VA
11.05 Direct On Line Starter ( DOL ) for 7.5KW
3
Nos
Risesun-Tiwan
1
Nos
ABB
11.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
Outgoing: Septic Tank-02 ( Pump-01 Working-A TP MPCB
1
Nos
ABB
12.02 6A TP MPCB
1
Nos
ABB
12.03 3 Phase Digital Ammeter
1
Nos
Reshabh-India
-
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(Ground Floor)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(Ground Floor)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(First Floor)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(First Floor)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(Second Floor)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Multi Receptacle(Second Floor-A, 4P MCB
Breaking Capacity: 10KA
12.04 Current Transformer (CT)
Ratio:
Accuracy and burden: CL-01, 15VA
12.05 Direct On Line Starter ( DOL ) for 7.5KW
3
Nos
Risesun-Tiwan
1
Nos
ABB
12.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
Outgoing: PDB-01(Winding Maintenance Workshop,west side @ 0.00M-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
1
Breaking Capacity: 36KA.
Nos
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
14.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, 4P MCB
Breaking Capacity: 10KA
1
Nos
ABB-Italy
Outgoing:Spare-A, 4P MCB
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1.5. SUPPLY OF RPDB-RAW power Distribution Board (Typical)
Technical Description
Sl No.
1
1.1
2
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2.01
100A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
3
3.01
Incoming From PDB-01
3.1
QTY Unit
63A, 4P MCB
Breaking Capacity: 10KA
Assembled By:
Reverie-BD
1
No.
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
1
Nos
ABB
8
Nos
ABB-Italy
Outgoing:
3.1.1 Incoming
40A DP RCCB
100mA,10KA
3.1.2 Outgoing: CKT
16A SP MCB
Breaking Capacity: 10KA
3.1.3 Incoming
40A DP RCCB
100mA,10KA
3.1.4 Outgoing: CKT
16A SP MCB
Breaking Capacity: 10KA
3.1.5 Incoming
40A DP RCCB
100mA,10KA
3.1.6 Outgoing: CKT
16A SP MCB
Breaking Capacity: 10KA
1
Nos
8
Nos
1
Nos
8
Nos
ABB-Italy
ABB-Italy
1.6. SUPPLY OF ACDB-Air Conditioning Distribution Board(typical)
Technical Description
Sl No.
1
1.1
2
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
2.01
100A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
3
3.01
Incoming From PDB-01
3.1
QTY Unit
63A, 4P MCB
Breaking Capacity: 10KA
Assembled By:
Reverie-BD
1
No.
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
1
Nos
6
Nos
1
Nos
6
Nos
1
Nos
6
Nos
Outgoing:
3.1.1 Incoming
63A DP RCCB
100mA,10KA
3.1.2 Outgoing: CKT
20A SP MCB
Breaking Capacity: 10KA
3.1.3 Incoming
63A DP RCCB
100mA,10KA
3.1.4 Outgoing: CKT
20A SP MCB
Breaking Capacity: 10KA
3.1.5 Incoming
63A DP RCCB
100mA,10KA
3.1.6 Outgoing: CKT
20A SP MCB
Breaking Capacity: 10KA
ABB
ABB-Italy
ABB
ABB-Italy
ABB
ABB-Italy
1.7. SUPPLY OF PCC-05 (PSF SPINNING & CP - CRITICAL LOADS)
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
Assembled By:
Reverie-BD
16
Nos
1
Set
Coppertech/
Meghna - BD
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-01 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.06
Voltmeter Selector Switch
1
Nos
ABB
3.07
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL5P10, 15VA
Reverse Power Relay (32R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
Risesun-Tiwan
3.10
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CLPS, 15VA
Rotor earth fault Relay (64R)
1
Nos
ABB/Equivalent
3.11
6A TP MPCB
1
Nos
ABB
3.12
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
3.13
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
3.14
Voltage Monitoring Relay
1
Nos
ABB/Equivalent
3.15
6
Nos
Risesun-Tiwan
1
Nos
ABB
3.17
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.18
Ammeter Selector Switch
1
Nos
ABB
3.19
6A TP MPCB
1
Nos
ABB
3.20
Indication lamps: R,Y,B
3
Nos
ABB-India
3.21
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
9
Nos
ABB-India
-
3.08
3.09
3.16
5000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
(Interconnection with PCC-06)
Incoming From Distribution Transformer-04 (3500KVA)
4
4.01
Incoming From Solar Panel
1
Nos
4.02
1250A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
32A TP MPCB
1
Nos
ABB
4.03
Type-01 SPD
1
Nos
ABB/Phonix
4.04
6A TP MPCB
1
Nos
ABB
4.05
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.06
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.07
Voltage Monitoring Relay
1
Nos ABB/Equivalent
4.08
Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.10
3 Phase Digital Ammeter
1
Nos
Reshabh-India
4.11
Ammeter Selector Switch
1
Nos
ABB
4.12
6A TP MPCB
1
Nos
ABB
4.13
Indication lamps: R,Y,B
3
Nos
ABB-India
4.14
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Bus-Coupler 01 [For interconnection with PCC-05 Panel]
9
Nos
ABB-India
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
2
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
18
Nos
ABB-India
8
Nos
ABB
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
6.02
6A TP MPCB
1
Nos
ABB
6.03
Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
6.04
Multifunction Meter
Model Number: M1M 30
1
Nos
ABB
6.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
4.09
5
5.01
-
ABB-Italy
Outgoing: PDB-02 for Auxilary Loads of PSF Spinning Building.
7
7.01
Outgoing: Drives Switch Cabinet(PSF Spinning Building).
500A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
6A TP MPCB
1
Nos
ABB-Italy
1
Nos
ABB
7.03
Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
7.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
7.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
7.02
8
Outgoing: Quench Air Unit(PSF Spinning Building).
8.01
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
8.02
6A TP MPCB
1
Nos
ABB
8.03
Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
8.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
8.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
9
Outgoing: Spinning Pump Pos 1-8(PSF Spinning Building).
9.01
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
9.02
6A TP MPCB
1
Nos
ABB
9.03
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
9.04
Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
9.05
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
10
Outgoing: Spinning Pump Pos 9-16(PSF Spinning Building).
10.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
10.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
10.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
11.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
13.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
13.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
11
12
13
Outgoing: Spinning Pump Pos 17-24(PSF Spinning Building).
Outgoing: Spinning Pump Pos 25-32(PSF Spinning Building).
Outgoing: Spinning Pump Pos 33-40(PSF Spinning Building).
13.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Common Drives + Healthiness(PSF Spinning Building)-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
14.04 Multifunction Meter
Model Number: MIM 30
14.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
15.04 Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
15.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
16.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
16.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
Outgoing: APFCR Panel-03(500KVAR-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
Outgoing: Active Filter-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
17
Outgoing: Spare
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
17.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
17.04 Multifunction Meter
Model Number: MIM 30
17.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
18.02 6A TP MPCB
1
Nos
ABB
18.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
18.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
18.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
19.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
19.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
19.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
Outgoing: MCC-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
20.02 6A TP MPCB
1
Nos
ABB
20.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
20.04 Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
18
Outgoing: Spare
Outgoing: MCC-02 for Utility Loads CP Building-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
19.02 6A TP MPCB
20.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
21.02 6A TP MPCB
1
Nos
ABB
21.03 Current Transformer (CT)
Ratio: 500/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
21.04 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
21.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: MCC-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
22.02 6A TP MPCB
1
Nos
ABB
22.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
22.04 Multifunction Meter
Model Number: MIM 30
22.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
Outgoing: MCC-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
23.02 6A TP MPCB
1
Nos
ABB
23.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
23.04 Multifunction Meter
Model Number: MIM 30
23.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
Outgoing: PDB-03 For Auxilary Loads CP Building-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
24.02 6A TP MPCB
1
Nos
ABB
24.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
24.04 Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
21
Outgoing: MCC-04
24.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing:Filter Cleaning PDB at 6.5MTR LVL-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
25.02 6A TP MPCB
1
Nos
ABB
25.03 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL:01, 15VA
25.04 Multifunction Meter
Model Number: MIM 30
25.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
26.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
26.04 Digital Ammeter
1
Nos
ABB
26.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
27.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
27.04 Multifunction Meter
Model Number: MIM 30
27.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
1
Nos
ABB
8
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
Outgoing: APFCR Panel-04 (500KVAR-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
26.02 6A TP MPCB
Outgoing: Active Filter-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
27.02 6A TP MPCB
Outgoing: Spare-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
28.02 6A TP MPCB
28.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
28.04 Multifunction Meter
Model Number: MIM 30
28.05 Indication lamps: ON, OFF, TRIP, 52CS, SPRING CHARGED, TCH,
SERVICE, TEST
1
Nos
ABB
8
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
29.02 6A TP MPCB
1
Nos
ABB
29.03 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
29.04 Multifunction Meter
Model Number: MIM 30
29.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1.8. SUPPLY OF PDB-02 for Auxlilery Loads of PSF Spinning Building.
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
6
Nos
Assembled By:
Reverie-BD
630A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)&
with shunt Trip
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
3
Nos
ABB-India
-
3.09
Incoming From PCC-05-F16
3.10
4
Nos
ABB-India
100A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
100A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
100A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
6.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
7
7.01
Outgoing: Pre Heating Oven-04
100A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
7.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
8
8.01
Outgoing: Air Flow Control System POS-1-40
25A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
9
9.01
Outgoing: Main Control Cabinet Fiber Spinning Line
25A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: AK014(Hoist for Spinning M/C-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
10.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: MCC-01(PSF-5.50M Level) 81-980-MCC-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Switch Cabinet UPS (PSF drawline MCC Room-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
-
9.02
Indication lamps: ON, OFF, TRIP,ET
Outgoing: Pre Heating Oven-01
Outgoing: Pre Heating Oven-02
Outgoing: Pre Heating Oven-03
12.02 Indication lamps: ON, OFF, TRIP
3
Nos
Outgoing: Control Panel for Buffer Tank Pumps & Agitator at 13.55MTR Level-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
1
Nos
Breaking Capacity: 50KA.
ABB
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: AHU-20000 CFM(PSF Spinning Building-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
14.04 Multifunction Meter
Model Number: MIM 30
14.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
Outgoing: Ductable Unit-08-TR(For workshops & Offices) at 13.55MTR LVL-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
1
Nos
Breaking Capacity: 50KA.
ABB-Italy
15.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Lift (PSF Spinning Building-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
16.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
17.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
18.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
19.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
20.02 6A TP MPCB
1
Nos
ABB
20.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
20.04 Multifunction Meter
Model Number: MIM 30
20.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1
Nos
ABB-Italy
Outgoing:-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
21.1.2 6A TP MPCB
1
Nos
ABB
21.1.3 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
21.1.4 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL-01, 15VA
21.1.5 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
3
Nos
ABB
21.2.1 Outgoing: Multi Receptacle Ground Floor(PSF Spinning Building)
21.2.1. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
21.2.2 Outgoing: Truck Loading Stations Ground Floor(PSF Spinning Building)
21.2.2. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
21.2.3 Outgoing: Multi Receptacle First Floor(PSF Spinning Building)
21.2.3. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
21.2.4 Outgoing: Spare
21.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
21.2.5 Outgoing: Spare
21.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
21.2.6 Outgoing: Spare
21.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB
22.1.3 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
22.1.4 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL-01, 15VA
3
Nos
Risesun-Tiwan
21.2
Sub Outgoing From 125A MCCB
Outgoing:-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
22.1.2 6A TP MPCB
22.1.5 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
22.2 Sub Outgoing From 160A MCCB
22.2.1. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.2 Outgoing: Raw Power Distribution Board (PSF Spinning Building)
22.2.2. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.3 Outgoing: Raw Power Distribution Board (PSF Spinning Building)
22.2.3. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.4 Outgoing: Multi Receptacle Second Floor(PSF Spinning Building)
22.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.5 Outgoing: Multi Receptacle Third Floor(PSF Spinning Building)
22.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.6 Outgoing: Spare
22.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.4 Outgoing: Spare
22.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.5 Outgoing: Spare
22.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
22.2.6 Outgoing: Spare
22.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1.9. SUPPLY OF PDB-03 for Auxlilery Loads CP Building.
Technical Description
Sl No.
1
1.1
-
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
6
Nos
Assembled By:
Reverie-BD
630A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
Incoming From PCC-05-F33
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)&
with shunt Trip
Breaking Capacity: 65KA.
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
3
Nos
Risesun-Tiwan
3.09
Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
ABB-India
3.10
Indication lamps: ON, OFF, TRIP,ET
4
Nos
ABB-India
125A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02
6A TP MPCB
1
Nos
ABB
4.03
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
16A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
16A, TP+N MCCB with Thermal Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
7.02
6A TP MPCB
1
Nos
ABB
7.03
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
4
4.01
-
-
Outgoing: SDB-02 for HSD Tank and Auxilery Loads.
Outgoing: Control panel Effluent Pump-04 for CP(working)
Outgoing: Control panel Effluent Pump-05 for CP(Standby)
Outgoing: PDB for CP MCC room
Outgoing: Lift-01 (CP Building)
8.01
63A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
8.02
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
63A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)&ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
10.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
11.04 Multifunction Meter
Model Number: MIM 30
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
12.04 Multifunction Meter
Model Number: MIM 30
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
13.1.3 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
13.1.4 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
13.1.5 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
-
Outgoing: Lift-02 (CP Building)
Outgoing:-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 65KA.
13.1.2 6A TP MPCB
13.2
Sub Outgoing From 160A MCCB
13.2.1 Outgoing: Flame Proof Receptacle Ground Floor(CP Building)
13.2.1. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.2 Outgoing: Flame Proof Receptacle Ground Floor(CP Building)
13.2.2. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.3 Outgoing: Flame Proof Receptacle First Floor(CP Building)
13.2.3. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.4 Outgoing: Flame Proof Receptacle First Floor(CP Building)
13.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.5 Outgoing: Flame Proof Receptacle Second Floor(CP Building)
13.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.6 Outgoing: Flame Proof Receptacle Second Floor(CP Building)
13.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.7 Outgoing: Flame Proof Receptacle Third Floor(CP Building)
13.2.7. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.8 Outgoing: SPare
13.2.8. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
13.2.9 Outgoing: SPare
13.2.9. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB
14.1.3 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
14.1.4 Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL-01, 15VA
14.1.5 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
3
Nos
ABB
14.2.1 Outgoing: Flame Proof Receptacle ThirdFloor(CP Building)
14.2.1. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.2 Outgoing: Flame Proof Receptacle Fourth Floor(CP Building)
14.2.2. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
Outgoing:-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
14.1.2 6A TP MPCB
14.2
Sub Outgoing From 160A MCCB
14.2.3 Outgoing: Flame Proof Receptacle Fourth Floor(CP Building)
14.2.3. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.4 Outgoing: Multi Receptacle for S/S-02 (CP Building)
14.2.4. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.5 Outgoing: Raw Power Distribution board (CP Building)
14.2.5. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.6 Outgoing: Raw Power Distribution board (CP Building)
14.2.6. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.7 Outgoing: Spare
14.2.7. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.8 Outgoing: SPare
14.2.8. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
14.2.9 Outgoing: SPare
14.2.9. 63A, 4P MCB
1
Breaking Capacity: 10KA
1
Nos
ABB-Italy
1.10. SUPPLY OF SDB-02 for HSD Tank & Auxilery Loads
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
Assembled By:
Reverie-BD
1
No.
1
Set
Coppertech/
Meghna - BD
125A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)&
with shunt Trip
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
-
125A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PDB-03-F3
3.08
3
Nos
Risesun-Tiwan
3.09
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
ABB-India
3.10
Indication lamps: ON, OFF, TRIP,ET
4
Nos
ABB-India
4
4.01
Outgoing: Recptacle Outdoor Area (Provission)
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
ABB
-
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Recptacle Outdoor Area (Provission)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: HSD Panel
32A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 36KA.
Outgoing: HSD Tank Pump-01(Working)
7
7.01
32A TP MPCB
1
Nos
7.02
6A TP MPCB
1
Nos
ABB
7.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
7.04
3
Nos
Risesun-Tiwan
7.05
Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL - 01, 15VA
Direct Online Starter(DOL) connected to 5.5KW
7.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M
6
Nos
ABB-India
8
8.01
Outgoing: HSD Tank Pump-02(Standby)
32A TP MPCB
1
Nos
ABB
8.02
6A TP MPCB
1
Nos
ABB
8.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
8.04
3
Nos
Risesun-Tiwan
8.05
Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL - 01, 15VA
Direct Online Starter(DOL) connected to 5.5KW
8.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB-Italy
9
9.01
Outgoing: Spare
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Spare-A, 4P MCB
Breaking Capacity: 10KA
1.11. SUPPLY OF MCC-02 for Utility Loads CP Building
Technical Description
Sl No.
1
Panel Description
QTY Unit
Brand-Origin
1.1
10
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02
1000A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking
Capacity: 50KA.
32A
TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
3
Nos
ABB-India
Indication lamps: ON, OFF, TRIP, 52CS, ET, SPRING CHARGED,
TCH, SERVICE, TEST
Outgoing: CP Chilled Water Pumps-01-300M3/H(working)
9
Nos
ABB-India
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02
6A TP MPCB
1
Nos
ABB
4.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
4.04
3
Nos
Risesun-Tiwan
4.05
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 75KW
1
Nos
ABB
4.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
5.02
6A TP MPCB
1
Nos
ABB
5.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.04
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
3
Nos
Risesun-Tiwan
-
-
5
5.01
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
1000A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PCC-05-F28
Outgoing: CP Chilled Water Pumps-02(working)
5.05
VFD Connected to 75KW
1
Nos
ABB
5.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
6.02
6A TP MPCB
1
Nos
ABB
6.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
6.04
3
Nos
Risesun-Tiwan
6.05
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 75KW
1
Nos
ABB
6.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
7
7.01
Outgoing: Cooling Towers-1000 CMH
80A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
7.02
6A TP MPCB
1
Nos
ABB
7.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
7.04
3
Nos
Risesun-Tiwan
7.05
Current Transformer (CT)
Ratio: 80/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 30KW
1
Nos
ABB
7.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
100A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02
6A TP MPCB
1
Nos
ABB
8.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
8.04
3
Nos
Risesun-Tiwan
8.05
Current Transformer (CT)
Ratio: 100/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 45KW
1
Nos
ABB
8.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
6
6.01
8
8.01
9
Outgoing: CP Chilled Water Pumps-03(Standby)
Outgoing: Cooling Towers-1500 CMH
Outgoing: AHU Panel-60000 CFM(Incomer Breaker rating Shall be match with Vendor AHU Panel)
9.01
400A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
9.02
6A TP MPCB
1
Nos
ABB
9.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
9.04
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
Outgoing: VAM Chiller CP-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
10.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 3 Phase Digital Ammeter
1
Nos
Reshabh-India
11.04 Current Transformer (CT)
Ratio: 100/5A
Accuracy and burden: CL - 01, 15VA
11.05 VFD Connected to 45KW
3
Nos
Risesun-Tiwan
1
Nos
ABB
11.06 Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C,E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 3 Phase Digital Ammeter
1
Nos
Reshabh-India
12.04 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL - 01, 15VA
12.05 Multifunction Meter
Model Number: MIM 30
12.06 Indication lamps: ON, OFF, TRIP
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
ABB-India
Outgoing: Spare-A, TP+N MCCB with Thermal Based Rel.( O/C, S/C)& ELR
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
13.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
9.05
9.06
12
Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL - 01, 15VA
Multifunction Meter
Model Number: MIM 30
Indication lamps: ON, OFF, TRIP
Outgoing: Spare
1.12. SUPPLY OF SDB-03 for Septic Tank-04 & Auxilery Loads(Outdoor Type)(Incoming Power supply for
SDB-03 shall be tapped from PDB for Admin Building)
Technical Description
Sl No.
1
Panel Description
QTY Unit
Brand-Origin
1.1
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
1
No.
Assembled By:
Reverie-BD
125A, 415V, 36KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
125A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)&
with shunt Trip
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
3
Nos
Risesun-Tiwan
3.09
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
ABB-India
3.10
Indication lamps: ON, OFF, TRIP,ET
4
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB-Italy
-
-
Incoming From PDB-03-F3
Outgoing: Recptacle Outdoor Area (Provission)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Recptacle Outdoor Area (Provission)
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Septic Tank-04 (Pump-01 Working)
6
6.01
32A TP MPCB
1
Nos
ABB
6.02
6A TP MPCB
1
Nos
ABB
6.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
6.04
3
Nos
Risesun-Tiwan
6.05
Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL - 01, 15VA
Direct Online Starter(DOL) connected to 7.5KW
6.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M
6
Nos
ABB-India
8
8.01
32A TP MPCB
1
Nos
ABB
8.02
6A TP MPCB
1
Nos
ABB
8.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
ABB
Outgoing: Outgoing: Septic Tank-04 (Pump-02 Standby)
8.04
3
8.05
Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL - 01, 15VA
Direct Online Starter(DOL) connected to 5.5KW
8.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB-Italy
9
9.01
Nos
Risesun-Tiwan
ABB
Outgoing: Spare
63A, 4P MCB
Breaking Capacity: 10KA
Outgoing: Spare-A, 4P MCB
Breaking Capacity: 10KA
1.13. SUPPLY OF PCC-06 (CP-CRITICAL)
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
Assembled By:
Reverie-BD
13
Nos
1
Set
Coppertech/
Meghna - BD
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-01 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.06
Voltmeter Selector Switch
1
Nos
ABB
3.07
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL5P10, 15VA
Reverse Power Relay (32R)
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
Risesun-Tiwan
3.10
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CLPS, 15VA
Rotor earth fault Relay (64R)
1
Nos
ABB/Equivalent
3.11
6A TP MPCB
1
Nos
ABB
3.12
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
-
3.08
3.09
5000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From Distribution Transformer-06 (3500KVA)
3.13
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
3.14
Voltage Monitoring Relay
1
Nos
ABB/Equivalent
3.15
6
Nos
Risesun-Tiwan
1
Nos
ABB
3.17
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.18
Ammeter Selector Switch
1
Nos
ABB
3.19
6A TP MPCB
1
Nos
ABB
3.20
Current Transformer (CT)
Ratio: 5000/5A
Accuracy and burden: CL:01, 15VA
Indication lamps: R,Y,B
6
Nos
Risesun-Tiwan
3
Nos
ABB-India
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Incoming From Solar Panel
9
Nos
ABB-India
1
Nos
ABB-Italy
4.02
1250A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
32A TP MPCB
1
Nos
ABB
4.03
Type-01 SPD
1
Nos
ABB/Phonix
4.04
6A TP MPCB
1
Nos
ABB
4.05
415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.06
16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.07
Voltage Monitoring Relay
1
Nos
ABB/Equivalent
4.08
Current Transformer (CT)
Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: M4M 20
3
Nos
Risesun-Tiwan
1
Nos
ABB
4.10
3 Phase Digital Ammeter
1
Nos
Reshabh-India
4.11
Ammeter Selector Switch
1
Nos
ABB
4.12
6A TP MPCB
1
Nos
ABB
4.13
Indication lamps: R,Y,B
3
Nos
ABB-India
4.14
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Bus-Coupler 01 [For interconnection with PCC-05 Panel]
9
Nos
ABB-India
5000A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.16
-
4.09
5
5.01
5.02
Indication lamps: ON, OFF, TRIP,52CS,ET, SPRING CHARGED, TCH,
SERVICE, TEST
Outgoing: MCC-01
9
Nos
ABB-India
800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
6.02
6A TP MPCB
1
Nos
ABB
6.03
Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
6.05
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
7
7.01
Outgoing: MCC-03
800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
7.02
6A TP MPCB
1
Nos
ABB
7.03
Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
7.05
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
8
8.01
Outgoing: MCC-05
800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
8.02
6A TP MPCB
1
Nos
ABB
8.03
Current Transformer (CT)
Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
6
6.01
6.04
7.04
-
Outgoing: MCC-01 Utility Loads CP Building.
9.01
1000A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
9.02
6A TP MPCB
1
Nos
ABB
9.03
Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
Model Number: MIM 30
3
Nos
Risesun-Tiwan
1
Nos
ABB
Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
Outgoing: Polymer Discharge PUMP-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
10.03 Multifunction Meter
Model Number: MIM 30
10.04 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL - 01, 15VA
10.05 Indication lamps: ON, OFF, TRIP,ET
1
Nos
ABB
3
Nos
Risesun-Tiwan
4
Nos
ABB-India
Outgoing: Finisher Agitator-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 Multifunction Meter
Model Number:
11.04 Current Transformer (CT)
Ratio: 400/5A
Accuracy and burden: CL - 01, 15VA
11.05 Indication lamps: ON, OFF, TRIP,ET
1
Nos
ABB
3
Nos
Risesun-Tiwan
4
Nos
ABB-India
Outgoing: Polymr Booster PUMP for Line-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 Multifunction Meter
Model Number: MIM 30
12.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL - 01, 15VA
12.05 Indication lamps: ON, OFF, TRIP,ET
1
Nos
ABB
3
Nos
Risesun-Tiwan
4
Nos
ABB-India
9.04
9.05
ABB-Italy
Outgoing: APFCR Panel-05 ( 500 KVAR -A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
13.02 6A TP MPCB
1
Nos
ABB
13.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
13.04 Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
13.05 Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
1
Nos
ABB-Italy
14.02 6A TP MPCB
1
Nos
ABB
14.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
14.04 Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
14.05 Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
15.04 Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
ABB
15.05 Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
Outgoing: APFCR Panel-06 ( 500 KVAR -A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
Outgoing: Active Filter-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
16
Outgoing: Spare
ABB-Italy
-A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL:01, 15VA
16.04 Multifunction Meter
Model Number:
3
Nos
Risesun-Tiwan
1
Nos
ABB
16.05 Indication lamps: ON, OFF, TRIP,52CS, SPRING CHARGED, TCH,
SERVICE, TEST
8
Nos
ABB
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
17.03 Multifunction Meter
Model Number: MIM 30
17.04 Current Transformer (CT)
Ratio: 630/5A
Accuracy and burden: CL - 01, 15VA
17.05 Indication lamps: ON, OFF, TRIP,ET
1
Nos
ABB
3
Nos
Risesun-Tiwan
4
Nos
ABB-India
Outgoing: Spare-A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
18.02 6A TP MPCB
1
Nos
ABB
18.03 Multifunction Meter
Model Number: MIM 30
18.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL - 01, 15VA
18.05 Indication lamps: ON, OFF, TRIP,ET
1
Nos
ABB
3
Nos
Risesun-Tiwan
4
Nos
ABB-India
1.14. 500KVAR APFC Panel
Sl No.
1
1.1
2
Technical Description
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
Nos
Assembled By:
Reverie-BD
2.1
1
Set
Coppertech/
Meghna - BD
1000A (ACB) TP, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F]
Breaking Capacity: 65KA.
1
Nos
ABB-Italy
3.02
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
Indication lamps: R,Y,B
3
Nos
ABB-India
3.06
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.09
Voltmeter Selector Switch
1
Nos
ABB
3.10
Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL5P10, 15VA
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH
3
Nos
Risesun-Tiwan
5
Nos
ABB-India
1
No
Iskra-Slovenia
3
3.01
-
1000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming Power Supply from PCC-01-F7
PFC Relay
16 Stages Automatic Power factor correction relay with push button,
indication lamp.
Stage -1: F-1
5.01
250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
5.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
5.03
Indication lamp: ON
1
Nos
ABB
5.04
3
Nos
Risesun-Tiwan
5.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.06
Ammeter Selector Switch
1
Nos
ABB
5.07
Auto Manual Switch
1
Nos
ABB
5.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
-
Stage -02: F-2
6.01
250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
6.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
6.03
Indication lamp: ON
1
Nos
ABB
6.04
3
Nos
Risesun-Tiwan
6.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
6.06
Ammeter Selector Switch
1
Nos
ABB
6.07
Auto Manual Switch
1
Nos
ABB
6.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
-
Stage -03: F-3
7.01
125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
7.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
7.03
Indication lamp: ON
1
Nos
ABB
7.04
3
Nos
Risesun-Tiwan
7.05
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
7.06
Ammeter Selector Switch
1
Nos
ABB
7.07
Auto Manual Switch
1
Nos
ABB
7.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
-
Stage -04: F-4
8.01
125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
8.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
8.03
Indication lamp: ON
1
Nos
ABB
8.04
3
Nos
Risesun-Tiwan
8.05
Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
8.06
Ammeter Selector Switch
1
Nos
ABB
8.07
Auto Manual Switch
1
Nos
ABB
8.08
Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
1
set
Iskra-Slovenia
8.09
8.10
8.11
9
7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
Stage -05: F-5
9.01
63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
9.02
2A, SP, MCB, 10KA
1
Nos
ABB-Germany
9.03
Indication lamp: ON
1
Nos
ABB
9.04
3
Nos
Risesun-Tiwan
9.05
Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
3 Phase Digital Ammeter
1
Nos
Reshabh-India
9.06
Ammeter Selector Switch
1
Nos
ABB
9.07
Auto Manual Switch
1
Nos
ABB
9.08
Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
10.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
10.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
10.03 Indication lamp: ON
1
Nos
ABB
10.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
10.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
10.06 Ammeter Selector Switch
1
Nos
ABB
10.07 Auto Manual Switch
1
Nos
ABB
10.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
10.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
10.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
10.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
11.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
11.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
11.03 Indication lamp: ON
1
Nos
ABB
11.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
11.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
-
11
Stage -06: F-6
Stage -07: F-7
11.06 Ammeter Selector Switch
1
Nos
ABB
11.07 Auto Manual Switch
1
Nos
ABB
11.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
11.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
11.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
11.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
12.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
12.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
12.03 Indication lamp: ON
1
Nos
ABB
12.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
12.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
12.06 Ammeter Selector Switch
1
Nos
ABB
12.07 Auto Manual Switch
1
Nos
ABB
12.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
12.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
12.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
12.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
13.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
13.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
13.03 Indication lamp: ON
1
Nos
ABB
13.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
13.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
13.06 Ammeter Selector Switch
1
Nos
ABB
13.07 Auto Manual Switch
1
Nos
ABB
13.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
13.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
13.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
13.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
12
13
14
Stage -08: F-8
Stage -09: F-9
Stage -10: F-10
14.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
14.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14.03 Indication lamp: ON
1
Nos
ABB
14.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
14.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
14.06 Ammeter Selector Switch
1
Nos
ABB
14.07 Auto Manual Switch
1
Nos
ABB
14.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
14.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
14.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
14.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
15.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
15.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15.03 Indication lamp: ON
1
Nos
ABB
15.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
15.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15.06 Ammeter Selector Switch
1
Nos
ABB
15.07 Auto Manual Switch
1
Nos
ABB
15.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
15.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
15.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
15.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
16.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
16.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
16.03 Indication lamp: ON
1
Nos
ABB
16.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
16.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
16.06 Ammeter Selector Switch
1
Nos
ABB
16.07 Auto Manual Switch
1
Nos
ABB
15
16
Stage -11: F-11
Stage -12: F-12
16.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
16.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
16.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
16.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
17.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
17.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
17.03 Indication lamp: ON
1
Nos
ABB
17.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
17.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
17.06 Ammeter Selector Switch
1
Nos
ABB
17.07 Auto Manual Switch
1
Nos
ABB
17.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
17.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
17.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
18.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
18.03 Indication lamp: ON
1
Nos
ABB
18.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
18.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
18.06 Ammeter Selector Switch
1
Nos
ABB
18.07 Auto Manual Switch
1
Nos
ABB
18.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
18.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
18.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
18.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
19.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
17
18
19
Stage -13: F-13
Stage -14: F-14
Stage -15: F-15
19.03 Indication lamp: ON
1
Nos
ABB
19.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
19.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
19.06 Ammeter Selector Switch
1
Nos
ABB
19.07 Auto Manual Switch
1
Nos
ABB
19.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
19.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
19.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
19.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
20.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
20.03 Indication lamp: ON
1
Nos
ABB
20.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
20.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
20.06 Ammeter Selector Switch
1
Nos
ABB
20.07 Auto Manual Switch
1
Nos
ABB
20.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
20.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
20.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
20.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.12 Multifunction Meter
Model Number: MIM 30
1
Nos
ABB
20.13 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
TEST
7
Nos
ABB
20
Stage -16: F-16
1.15. SUPPLY OF MCC-01 for Utility Loads CP Building
Technical Description
Sl No.
1
1.1
2
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
7
Nos
Assembled By:
Reverie-BD
2.1
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02
1000A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking
Capacity: 50KA.
32A TP MPCB
1
Nos
ABB
3.03
Type-02 SPD
1
Nos
ABB/Phonix
3.04
6A TP MPCB
1
Nos
ABB
3.05
1
Nos
ABB
3.06
Multifunction Meter
Model Number: M4M 20
3 Phase Digital Ammeter
1
Nos
Reshabh-India
3.07
Ammeter Selector Switch
1
Nos
ABB
3.08
Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL - 01, 15VA
Indication lamps: R,Y,B
3
Nos
Risesun-Tiwan
3
Nos
ABB-India
Indication lamps: ON, OFF, TRIP, 52CS, ET, SPRING CHARGED,
TCH, SERVICE, TEST
Outgoing: CP Cooling Water Pumps-01 CP VAM(working)
9
Nos
ABB-India
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02
6A TP MPCB
1
Nos
ABB
4.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
4.04
3
Nos
Risesun-Tiwan
4.05
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 75KW
1
Nos
ABB
4.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
5.02
6A TP MPCB
1
Nos
ABB
5.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
5.04
3
Nos
Risesun-Tiwan
5.05
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 75KW
1
Nos
ABB
5.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
6
6.01
Outgoing: CP Cooling Water Pumps-03 CP VAM(working)
1
Nos
ABB-Italy
3
3.01
-
5
5.01
1000A, 415V, 50KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PCC-06-F42
Outgoing: CP Cooling Water Pumps-02 CP VAM(working)
160A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
6.02
6A TP MPCB
1
Nos
6.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
6.04
3
Nos
Risesun-Tiwan
6.05
Current Transformer (CT)
Ratio: 160/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 75KW
1
Nos
ABB
6.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
7
7.01
Outgoing: CP Cooling water PUMP CP Process-01 ( Working )
250A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
7.02
6A TP MPCB
1
Nos
ABB
7.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
7.04
3
Nos
Risesun-Tiwan
7.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 90KW
1
Nos
ABB
7.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
8
8.01
Outgoing: CP Cooling water PUMP-02 CP Process ( Working )
250A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02
6A TP MPCB
1
Nos
ABB
8.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
8.04
3
Nos
Risesun-Tiwan
8.05
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 90KW
1
Nos
ABB
8.06
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
250A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
9.02
6A TP MPCB
1
Nos
ABB
9.03
3 Phase Digital Ammeter
1
Nos
Reshabh-India
Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL - 01, 15VA
VFD Connected to 90KW
3
Nos
Risesun-Tiwan
1
Nos
ABB
Indication lamps: ON, OFF, TRIP,R,ES,A/M,POT
7
Nos
ABB-India
9
9.01
-
ABB
Outgoing: CP Cooling water PUMP-03 CP Process ( Standby )
TECHNICAL SPECIFICATION
1. SUBSTATION-04 COGEN BUILDING
1.1. SUPPLY OF PCC-3 (STATION COMSUMPTION AND HTM PLANT)
Technical Description
Sl No.
1
1.1
2
2.1
3
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
3200A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
9
1
Nos
Assembled By:
Reverie-BD
Set
Coppertech/
Meghna - BD
Nos
ABB-Italy
Incoming From Distribution Transformer-03 (2000KVA)
3200A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
3.01
1
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 66KA.
3.02 32A TP MPCB
3.03 Type-01 SPD
1
Nos
ABB
1
Nos
ABB/Phonix
3.04 6A TP MPCB
3.05 3 Phase Digital Voltmeter
1
Nos
ABB
1
Nos
Reshabh-India
3.06 Voltmeter Selector Switch
Current Transformer (CT)
3.07 Ratio: 3200/5A
Accuracy and burden: CL5P10, 15VA
3.08 Reverse Power Relay (32R)
Current Transformer (CT)
3.09 Ratio: 3200/5A
Accuracy and burden: CLPS, 15VA
3.10 Rotor earth fault Relay (64R)
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB/ Equivalent
3.11 6A TP MPCB
1
Nos
ABB
3.12 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
3.13 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
3.14 Voltage Monitoring Relay
Current Transformer (CT)
3.15 Ratio: 3200/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
3.16
Model Number: M4M20
Current Transformer (CT)
3.17 Ratio: 3200/5A
Accuracy and burden: CLPS, 15VA
1
Nos
ABB/ Equivalent
3
Nos
Risesun-Tiwan
1
No.
ABB
3
Nos
Risesun-Tiwan
3.18 3 Phase Digital Ammeter
3
Nos
Reshabh-India
3.19 Ammeter Selector Switch
1
Nos
ABB
3.20 6A TP MPCB
1
Nos
ABB
3.21 Indication lamps: R,Y,B
3
Nos
ABB-India
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
3.22
7
TEST
Nos
ABB-India
Nos
ABB-Italy
Nos
ABB
Incoming From INTERCONNECTION WITH PCC- 2 UTILITY
1600A (ACB) 4P, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
4.01
1
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F, U/V]
ELR
Breaking Capacity: 50KA.
4.02 32A TP MPCB
1
4.03 Type-01 SPD
1
4
Nos
ABB/Phonix
4.04 6A TP MPCB
1
Nos
ABB
4.05 415/415V, 500VA, AC, Delta/Star Control Transformer
1
Nos
CNYH
4.06 16A, 4P, 10KA, MCB
3
Nos
ABB-Germany
4.07 Voltage Monitoring Relay
Current Transformer (CT)
4.08 Ratio: 1600/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB/ Equivalent
3
Nos
Risesun-Tiwan
1
No.
ABB
4.10 3 Phase Digital Ammeter
3
Nos
Reshabh-India
4.11 Ammeter Selector Switch
1
Nos
ABB
4.12 6A TP MPCB
1
Nos
ABB
4.13 Indication lamps: R,Y,B
3
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
4.14
7
TEST
Outgoing: MCC-07 for Cooling Tower & Chiller
5
Nos
ABB-India
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB
3
Nos
Risesun-Tiwan
4.09
Multifunction Meter
Model Number: M4M 20
1250A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
5.01
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 50KA.
5.02 6A TP MPCB
Current Transformer (CT)
5.03 Ratio: 1250/5A
Accuracy and burden: CL:01, 15VA
5.04
Multifunction Meter
Model Number: M1M30
1
No.
ABB
5.05
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
7
TEST
Nos
ABB
6
Outgoing: MCC-08 for Ezhaust & Supply Fan of Generator Room
6.01
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
6.02 6A TP MPCB
Current Transformer (CT)
6.03 Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
6.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
6.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
7.02 6A TP MPCB
Current Transformer (CT)
7.03 Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
7.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
7.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
8.02 6A TP MPCB
Current Transformer (CT)
8.03 Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
8.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
8.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
9.02 6A TP MPCB
Current Transformer (CT)
9.03 Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
9.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
9.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
7
7.01
8
8.01
9
9.01
10
10.01
Outgoing: for HTM Circulation Pump-1 Working
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: for HTM Circulation Pump-2 Standby
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: MCC- 9 for Auxiliary Load of GAS Generator
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: PDB-11 for Auxiliary Load of COGEN Building
315A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
10.02 6A TP MPCB
Current Transformer (CT)
10.03 Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
10.04
Model Number: M1M30
10.05 Indication lamps: ON, OFF, TRIP
Nos
ABB
1
Nos
ABB-Italy
11.02 6A TP MPCB
Current Transformer (CT)
11.03 Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
11.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
12.02 6A TP MPCB
Current Transformer (CT)
12.03 Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
12.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Current Transformer (CT)
13.03 Ratio: 1000/5A
3
Accuracy and burden: CL:01, 15VA
Multifunction Meter
13.04
1
Model Number: M1M30
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
13.05
7
TEST
Nos
ABB
Nos
Risesun-Tiwan
No.
ABB
Nos
ABB
1
Nos
ABB-Italy
1
Nos
ABB
3
Nos
Risesun-Tiwan
11
11.01
12
12.01
13
Outgoing: PDB-11 for Load Control Board Heater-1 (HTM MCC-1 working)
315A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: PDB-11 for Load Control Board Heater-2 (HTM MCC-2 Standby)
315A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: APFCR PANEL-14 (500KVAR)
1000A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
13.01
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 85KA.
14
3
Outgoing: ACTIVE FILTER
800A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
14.01
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 85KA.
14.02 6A TP MPCB
Current Transformer (CT)
14.03 Ratio: 800/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
1
Model Number: M1M30
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
14.05
7
TEST
14.04
No.
ABB
Nos
ABB
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Current Transformer (CT)
15.03 Ratio: 1250/5A
3
Accuracy and burden: CL:01, 15VA
Multifunction Meter
15.04
1
Model Number: M1M30
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
15.05
7
TEST
Nos
ABB
Nos
Risesun-Tiwan
No.
ABB
Nos
ABB
1
Nos
ABB-Italy
16.02 6A TP MPCB
Current Transformer (CT)
16.03 Ratio: 630/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
16.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
16.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
17.02 6A TP MPCB
Current Transformer (CT)
17.03 Ratio: 315/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
17.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
17.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
15
Outgoing: SPARE
1250A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
15.01
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F]
Breaking Capacity: 50KA.
16
Outgoing: SPARE
630A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
16.01
Breaking Capacity: 50KA.
17
17.01
Outgoing: SPARE
315A, TP+N MCCB with Microprocessor Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1.2. SUPPLY OF MCC-07 (FOR COOLING TOWER & CHILLER)
Technical Description
Sl No.
1
1.1
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
9
Nos
Assembled By:
Reverie-BD
2
Common Bus-bar
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
3.03 Type-02 SPD
1
Nos
ABB
1
Nos
ABB/Phonix
3.04 6A TP MPCB
3.05 3 Phase Digital Ammeter
1
Nos
ABB
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
Current Transformer (CT)
3.07 Ratio: 1250/5A
Accuracy and burden: CL5P10, 15VA
Multifunction Meter
3.08
Model Number: M4M20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
3.09 Indication lamps: R,Y,B
3
Nos
ABB-India
Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH, SERVICE,
7
TEST
Nos
ABB-India
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
8.01
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
2.1
3
1250A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
Incoming From PCC-03-F1
1250A (ACB) TP+N, EDO Type, Air Circuit Breaker Microprocessor
with adjustable thermal over load, shunt opening & closing, charging
motor, under voltage protection and magnetic(Complete all accessories)
3.01
releases Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C,
E/F, U/V] ELR
Breaking Capacity: 50KA.
-
Outgoing: Ezhaust & Supply Fan of Generator Room
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
4.02 Indication lamps: ON, OFF, TRIP
5
5.01
Outgoing: Hot Water Fried VAM Chiller 640TR
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
5.02 Indication lamps: ON, OFF, TRIP
6
6.01
Outgoing: Exhaust Fried VAM Chiller-1 680TR
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
6.02 Indication lamps: ON, OFF, TRIP
7
7.01
Outgoing: Exhaust Fried VAM Chiller-2 680TR
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
7.02 Indication lamps: ON, OFF, TRIP
8
9
Outgoing: Exhaust Fried VAM Chiller-3 680TR
Outgoing: Exhaust Fried VAM Chiller-4 680TR
9.01
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
11.02 6A TP MPCB
Current Transformer (CT)
11.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
11.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
11.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
12.03 75KW VFD, Variable Frequency Drive
1
Nos
ABB
Current Transformer (CT)
12.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
12.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
13.03 75KW VFD, Variable Frequency Drive
1
Nos
ABB
Current Transformer (CT)
13.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
13.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
13.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB
9.02 Indication lamps: ON, OFF, TRIP
10
10.01
Outgoing: Exhaust Fried VAM Chiller 340TR
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
10.02 Indication lamps: ON, OFF, TRIP
11
11.01
12
12.01
13
13.01
14
14.01
Outgoing: Steam Fried VAM Chiller 1500TR
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Cooling Tower for VAM & Compressor-1
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Cooling Tower for VAM & Compressor-2
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Cooling Tower for VAM & Compressor-3
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
14.02 6A TP MPCB
14.03 75KW VFD, Variable Frequency Drive
1
Nos
ABB-Italy
Current Transformer (CT)
14.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
14.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
14.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
15.02 6A TP MPCB
1
Nos
ABB
15.03 75KW VFD, Variable Frequency Drive
1
Nos
ABB
Current Transformer (CT)
15.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
15.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
15.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
16.02 6A TP MPCB
1
Nos
ABB
16.03 37KW VFD, Variable Frequency Drive
1
Nos
ABB-Italy
Current Transformer (CT)
16.03 Ratio: 80/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
16.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
16.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
17.02 6A TP MPCB
1
Nos
ABB
17.03 37KW VFD, Variable Frequency Drive
1
Nos
ABB
Current Transformer (CT)
17.03 Ratio: 80/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
17.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
17.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
15
15.01
16
16.01
17
17.01
18
Outgoing: Cooling Tower for VAM & Compressor-4
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Cooling Tower for Gas Generator-1
80A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Cooling Tower for Gas Generator-2
80A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Chilled Water Pressurization
18.01
32A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
19.02 6A TP MPCB
Current Transformer (CT)
19.03 Ratio: 160/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
19.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
Nos
ABB
19.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
18.02 Indication lamps: ON, OFF, TRIP
19
19.01
20
20.01
Outgoing: Spare
160A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Spare
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
20.02 Indication lamps: ON, OFF, TRIP
21
21.01
Outgoing: Spare
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
21.02 Indication lamps: ON, OFF, TRIP
22
22.01
Outgoing: Spare
32A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
22.02 Indication lamps: ON, OFF, TRIP
1.3. SUPPLY OF PDB-11 (FOR AUXILIARY LOAD OF COGEN BUILDING)
Technical Description
Sl No.
1
1.1
2
2.1
3
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
1250A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
2
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
Nos
ABB-Italy
Nos
ABB
Nos
ABB/Phonix
Nos
ABB
Nos
Reshabh-India
Incoming From PCC-03-F6
315A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F) & with Shunt
3.01 Trip
1
Breaking Capacity: 50KA.
3.02 32A TP MPCB
1
3.03 Type-02 SPD
1
3.04 6A TP MPCB
1
3.05 3 Phase Digital Ammeter
1
3.06 Ammter Selector Switch
Current Transformer (CT)
3.07 Ratio: 315/5A
Accuracy and burden: CL5P10, 15VA
Multifunction Meter
3.08
Model Number: M4M20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
3.09 Indication lamps: R,Y,B
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
1
Nos
ABB-Italy
4.02 6A TP MPCB
Current Transformer (CT)
4.03 Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
4.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
4.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
63A, 4P MCB
Breaking Capacity: 10KA.
8
Nos
ABB-Germany
1
Nos
ABB-Italy
5.02 6A TP MPCB
Current Transformer (CT)
5.03 Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
5.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
5.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
63A, 4P MCB
Breaking Capacity: 10KA.
8
Nos
ABB-Germany
1
Nos
ABB-Italy
6.02 6A TP MPCB
Current Transformer (CT)
6.03 Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
6.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
6.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
4
4.01
-
-
7
7.01
Outgoing:
125A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing:
125A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: For SDB-6
125A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: UFT
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F) & ELR
Breaking Capacity: 50KA.
7.02 Indication lamps: ON, OFF, TRIP
8
Outgoing: Control Panel Pump-10
16A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
8.01
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
8.02 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
3
Nos
ABB
1
Nos
ABB-Italy
12.02 6A TP MPCB
Current Transformer (CT)
12.03 Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
12.04
Model Number: M1M30
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
12.05 Indication lamps: ON, OFF, TRIP
3
Nos
ABB
9
9.01
Outgoing: Control Panel Pump-11
16A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
9.02 Indication lamps: ON, OFF, TRIP
10
10.01
Outgoing: Spare
16A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
10.02 Indication lamps: ON, OFF, TRIP
11
11.01
Outgoing: Spare
63A, TP+N MCCB with TH Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
11.02 Indication lamps: ON, OFF, TRIP
12
12.01
Outgoing: Spare
125A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
1.4. SUPPLY OF MCC-09 (FOR AUXILIARY LOAD OF GAS GENERATOR)
Technical Description
Sl No.
1
1.1
2
2.1
3
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
630A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
11
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
Nos
ABB-Italy
Nos
ABB
Nos
ABB/Phonix
Nos
ABB
Incoming From PCC-03-F5
630A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F) & with Shunt
3.01 Trip
1
Breaking Capacity: 50KA.
3.02 32A TP MPCB
1
3.03 Type-02 SPD
1
3.04 6A TP MPCB
1
3.05 3 Phase Digital Ammeter
3.06 Ammter Selector Switch
Current Transformer (CT)
3.07 Ratio: 630/5A
Accuracy and burden: CL5P10, 15VA
Multifunction Meter
3.08
Model Number: M4M20
1
Nos
Reshabh-India
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
3.09 Indication lamps: R,Y,B
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
4.01
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
4.02 6A TP MPCB
1
Nos
ABB
4.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
4.04 Thermal Overload Relay
1
No.
ABB
4.05 Relay
1
No.
ABB/ Equivalent
Current Transformer (CT)
4.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
4.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
4.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
5.02 6A TP MPCB
1
Nos
ABB
5.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
5.04 Thermal Overload Relay
1
No.
ABB
5.05 Relay
1
No.
ABB/ Equivalent
Current Transformer (CT)
5.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
5.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
5.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB
4
5
5.01
6
6.01
Outgoing: Jacket Water Pump-1
Outgoing: Jacket Water Pump-2
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Jacket Water Pump-3
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
6.02 6A TP MPCB
6.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
6.04 Thermal Overload Relay
1
No.
ABB
6.05 Relay
1
No.
ABB
Current Transformer (CT)
6.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
6.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
6.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
7.02 6A TP MPCB
1
Nos
ABB
7.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
Thermal Overload Relay
1
No.
ABB
Relay
1
No.
ABB
Current Transformer (CT)
7.03 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
7.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
7.05 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
8.02 6A TP MPCB
1
Nos
ABB
8.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
8.04 Thermal Overload Relay
1
No.
ABB
8.05 Relay
1
No.
ABB
Current Transformer (CT)
8.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
8.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
8.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB
7
7.01
8
8.01
9
9.01
Outgoing: Jacket Water Pump-4
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Jacket Water Pump-5
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Jacket Water Pump-6
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
9.02 6A TP MPCB
9.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
9.04 Thermal Overload Relay
1
No.
ABB
9.05 Relay
1
No.
ABB
Current Transformer (CT)
9.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
9.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
9.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
10.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
10.04 Thermal Overload Relay
1
No.
ABB
10.05 Relay
1
No.
ABB
Current Transformer (CT)
10.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
10.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
10.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
11.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
11.04 Thermal Overload Relay
1
No.
ABB
11.05 Relay
1
No.
ABB
Current Transformer (CT)
11.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
11.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
11.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
1
Nos
ABB
10
10.01
11
11.01
12
12.01
Outgoing: Jacket Water Pump-7
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Jacket Water Pump-8
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Jacket Water Pump-9
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
12.02 6A TP MPCB
12.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
12.04 Thermal Overload Relay
1
No.
ABB
12.05 Relay
1
No.
ABB
Current Transformer (CT)
12.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
12.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
13.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
13.04 Thermal Overload Relay
1
No.
ABB
13.05 Relay
1
No.
ABB/ Equivalent
Current Transformer (CT)
13.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
13.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
13.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
14.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
14.02 6A TP MPCB
Current Transformer (CT)
14.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
14.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
14.05 4KW DOL Satrter
1
No.
ABB
14.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
15.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
15.02 6A TP MPCB
Current Transformer (CT)
15.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
13
13.01
14
15
Outgoing: Jacket Water Pump-10
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: LT Water Pump-01
Outgoing: LT Water Pump-02
15.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
15.05 4KW DOL Satrter
1
No.
ABB
15.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
16.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
16.02 6A TP MPCB
Current Transformer (CT)
16.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
16.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
16.05 4KW DOL Satrter
1
No.
ABB
16.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
17.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
17.02 6A TP MPCB
Current Transformer (CT)
17.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
17.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
17.05 4KW DOL Satrter
1
No.
ABB
17.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
18.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
18.02 6A TP MPCB
Current Transformer (CT)
18.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
18.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
18.05 4KW DOL Satrter
1
No.
ABB
18.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
19.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
19.02 6A TP MPCB
1
Nos
ABB
16
17
18
19
Outgoing: LT Water Pump-03
Outgoing: LT Water Pump-04
Outgoing: LT Water Pump-05
Outgoing: LT Water Pump-06
Current Transformer (CT)
19.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
19.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
19.05 4KW DOL Satrter
1
No.
ABB
19.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
20.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
20.02 6A TP MPCB
Current Transformer (CT)
20.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
20.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
20.05 4KW DOL Satrter
1
No.
ABB
20.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
21.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
21.02 6A TP MPCB
Current Transformer (CT)
21.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
21.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
21.05 4KW DOL Satrter
1
No.
ABB
21.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
22.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
22.02 6A TP MPCB
Current Transformer (CT)
22.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
22.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
22.05 4KW DOL Satrter
1
No.
ABB
22.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
No.
ABB-Italy
20
21
22
23
Outgoing: LT Water Pump-07
Outgoing: LT Water Pump-08
Outgoing: LT Water Pump-09
Outgoing: LT Water Pump-10
23.01 10A, MPCB, Motor Protection Circuit Breker
23.02 6A TP MPCB
Current Transformer (CT)
23.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
23.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
23.05 4KW DOL Satrter
1
No.
ABB
23.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
24.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
24.02 6A TP MPCB
Current Transformer (CT)
24.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
24.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
24.05 1.5KW DOL Satrter
1
No.
ABB
24.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
25.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
25.02 6A TP MPCB
Current Transformer (CT)
25.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
25.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
25.05 1.5KW DOL Satrter
1
No.
ABB
25.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
26.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
26.02 6A TP MPCB
Current Transformer (CT)
26.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
26.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
26.05 1.5KW DOL Satrter
1
No.
ABB
26.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
24
25
26
27
Outgoing: Pre Lube Pump-1
Outgoing: Pre Lube Pump-2
Outgoing: Pre Lube Pump-3
Outgoing: Pre Lube Pump-4
27.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
27.02 6A TP MPCB
Current Transformer (CT)
27.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
27.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
27.05 1.5KW DOL Satrter
1
No.
ABB
27.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
28.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
28.02 6A TP MPCB
Current Transformer (CT)
28.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
28.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
28.05 1.5KW DOL Satrter
1
No.
ABB
28.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
29.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
29.02 6A TP MPCB
Current Transformer (CT)
29.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
29.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
29.05 1.5KW DOL Satrter
1
No.
ABB
29.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
30.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
30.02 6A TP MPCB
Current Transformer (CT)
30.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
30.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
30.05 1.5KW DOL Satrter
1
No.
ABB
30.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
28
29
30
Outgoing: Pre Lube Pump-5
Outgoing: Pre Lube Pump-6
Outgoing: Pre Lube Pump-7
31
Outgoing: Pre Lube Pump-8
31.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
31.02 6A TP MPCB
Current Transformer (CT)
31.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
31.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
31.05 1.5KW DOL Satrter
1
No.
ABB
31.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
32.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
32.02 6A TP MPCB
Current Transformer (CT)
32.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
32.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
32.05 1.5KW DOL Satrter
1
No.
ABB
32.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
33.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
33.02 6A TP MPCB
Current Transformer (CT)
33.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
33.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
33.05 1.5KW DOL Satrter
1
No.
ABB
33.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
34.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
34.02 6A TP MPCB
Current Transformer (CT)
34.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
34.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
34.05 1.5KW DOL Satrter
1
No.
ABB
32
33
34
Outgoing: Pre Lube Pump-9
Outgoing: Pre Lube Pump-10
Outgoing: SPARE
34.05 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
35.01 6A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
35.02 6A TP MPCB
Current Transformer (CT)
35.03 Ratio: 6/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
35.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
35.05 1.5KW DOL Satrter
1
No.
ABB
35.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
36.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
36.02 6A TP MPCB
Current Transformer (CT)
36.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
36.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
36.05 4KW DOL Satrter
1
No.
ABB
36.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
37.01 10A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
37.02 6A TP MPCB
Current Transformer (CT)
37.03 Ratio: 10/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
37.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
37.05 4KW DOL Satrter
1
No.
ABB
37.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
38.02 6A TP MPCB
1
Nos
ABB
38.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
38.04 Thermal Overload Relay
1
No.
ABB
35
36
37
38
38.01
Outgoing: SPARE
Outgoing: SPARE
Outgoing: SPARE
Outgoing: SPARE
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
38.05 Relay
1
No.
ABB
Current Transformer (CT)
38.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
38.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
38.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
32A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
39.01
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
39.02 6A TP MPCB
1
Nos
ABB
39.03 15KW Magnetic Contactor
3
Nos
ABB-Bulgaria
39.04 Thermal Overload Relay
1
No.
ABB
39.05 Relay
1
No.
ABB
Current Transformer (CT)
39.06 Ratio: 32/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
39.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
39.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
39
Outgoing: SPARE
1.5. 500KVAR APFC Panel
Sl No.
1
1.1
Technical Description
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
5
Nos
Assembled By:
Reverie-BD
1000A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
Set
Coppertech/
Meghna - BD
1
Nos
ABB-Italy
3.02 32A TP MPCB
1
Nos
ABB
3.03 Type-02 SPD
1
Nos
ABB/Phonix
3.04 6A TP MPCB
1
Nos
ABB
3.05 Indication lamps: R,Y,B
3
Nos
ABB-India
2
2.1
Incoming Power Supply from PCC-01-F-A (ACB) TP, EDO Type, Air Circuit Breaker Microprocessor with
adjustable thermal over load, shunt opening & closing, charging motor,
under voltage protection and magnetic(Complete all accessories) releases
Fixed mounted, LSIG protections, 2 NO+2 NC. [O/C, S/C, E/F]
Breaking Capacity: 65KA.
3.06 3 Phase Digital Ammeter
1
Nos
3.07 Ammeter Selector Switch
1
Nos
ABB
3.08 3 Phase Digital Voltmeter
1
Nos
Reshabh-India
3.09 Voltmeter Selector Switch
1
Nos
ABB
3.10 Current Transformer (CT)
Ratio: 1000/5A
Accuracy and burden: CL5P10, 15VA
3.11 Indication lamps: ON, OFF, TRIP, SPRING CHARGED, TCH
3
Nos
Risesun-Tiwan
5
Nos
ABB-India
1
No
Iskra-Slovenia
5.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
5.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
5.03 Indication lamp: ON
1
Nos
ABB
5.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
5.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
5.06 Ammeter Selector Switch
1
Nos
ABB
5.07 Auto Manual Switch
1
Nos
ABB
5.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
5.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
5.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
5.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
2
set
Iskra-Slovenia
6.01 250A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
6.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
6.03 Indication lamp: ON
1
Nos
ABB
6.04 Current Transformer (CT)
Ratio: 250/5A
Accuracy and burden: CL5P10, 15VA
6.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
6.06 Ammeter Selector Switch
1
Nos
ABB
6.07 Auto Manual Switch
1
Nos
ABB
6.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
6.09 Push Button: ON, OFF
2
set
Iskra-Slovenia
2
Nos
ABB
6.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
2
set
Iskra-Slovenia
PFC Relay
4
4.01 16 Stages Automatic Power factor correction relay with push button,
indication lamp.
5
6
Reshabh-India
Stage -1: F-1
Stage -02: F-2
6.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
2
set
Iskra-Slovenia
7.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
7.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
7.03 Indication lamp: ON
1
Nos
ABB
7.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
7.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
7.06 Ammeter Selector Switch
1
Nos
ABB
7.07 Auto Manual Switch
1
Nos
ABB
7.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
7.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
7.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
7.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
8.01 125A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
8.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
8.03 Indication lamp: ON
1
Nos
ABB
8.04 Current Transformer (CT)
Ratio: 125/5A
Accuracy and burden: CL5P10, 15VA
8.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
8.06 Ammeter Selector Switch
1
Nos
ABB
8.07 Auto Manual Switch
1
Nos
ABB
8.08 Capacitor Duty Contactor with Damping Resistor for 50KVAR Capacitor
switching.
8.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
8.10 50KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
8.11 7% Detuned Aluminum Winding Harmonic Reactor for 50kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
9.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
9.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
9.03 Indication lamp: ON
1
Nos
ABB
9.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
9.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
7
8
9
Stage -03: F-3
Stage -04: F-4
Stage -05: F-5
9.06 Ammeter Selector Switch
1
Nos
ABB
9.07 Auto Manual Switch
1
Nos
ABB
9.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
9.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
9.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
9.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
10.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
10.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
10.03 Indication lamp: ON
1
Nos
ABB
10.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
10.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
10.06 Ammeter Selector Switch
1
Nos
ABB
10.07 Auto Manual Switch
1
Nos
ABB
10.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
10.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
10.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
10.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
11.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
11.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
11.03 Indication lamp: ON
1
Nos
ABB
11.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
11.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
11.06 Ammeter Selector Switch
1
Nos
ABB
11.07 Auto Manual Switch
1
Nos
ABB
11.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
11.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
11.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
11.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
10
11
12
Stage -06: F-6
Stage -07: F-7
Stage -08: F-8
12.01 63A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
12.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
12.03 Indication lamp: ON
1
Nos
ABB
12.04 Current Transformer (CT)
Ratio: 63/5A
Accuracy and burden: CL5P10, 15VA
12.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
12.06 Ammeter Selector Switch
1
Nos
ABB
12.07 Auto Manual Switch
1
Nos
ABB
12.08 Capacitor Duty Contactor with Damping Resistor for 25KVAR Capacitor
switching.
12.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
12.10 25KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
12.11 7% Detuned Aluminum Winding Harmonic Reactor for 25kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
13.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
13.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
13.03 Indication lamp: ON
1
Nos
ABB
13.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
13.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
13.06 Ammeter Selector Switch
1
Nos
ABB
13.07 Auto Manual Switch
1
Nos
ABB
13.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
13.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
13.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
13.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
14.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
14.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
14.03 Indication lamp: ON
1
Nos
ABB
14.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
14.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
14.06 Ammeter Selector Switch
1
Nos
ABB
14.07 Auto Manual Switch
1
Nos
ABB
13
14
Stage -09: F-9
Stage -10: F-10
14.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
14.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
14.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
14.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
15.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
15.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15.03 Indication lamp: ON
1
Nos
ABB
15.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
15.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
15.06 Ammeter Selector Switch
1
Nos
ABB
15.07 Auto Manual Switch
1
Nos
ABB
15.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
15.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
15.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
15.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
16.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
16.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
16.03 Indication lamp: ON
1
Nos
ABB
16.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
16.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
16.06 Ammeter Selector Switch
1
Nos
ABB
16.07 Auto Manual Switch
1
Nos
ABB
16.08 Capacitor Duty Contactor with Damping Resistor for 15KVAR Capacitor
switching.
16.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
16.10 15KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
16.11 7% Detuned Aluminum Winding Harmonic Reactor for 15kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
17.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
17.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
15
16
17
Stage -11: F-11
Stage -12: F-12
Stage -13: F-13
17.03 Indication lamp: ON
1
Nos
ABB
17.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
17.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
17.06 Ammeter Selector Switch
1
Nos
ABB
17.07 Auto Manual Switch
1
Nos
ABB
17.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
17.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
17.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
17.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
18.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
18.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
18.03 Indication lamp: ON
1
Nos
ABB
18.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
18.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
18.06 Ammeter Selector Switch
1
Nos
ABB
18.07 Auto Manual Switch
1
Nos
ABB
18.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
18.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
18.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
18.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
19.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
19.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
19.03 Indication lamp: ON
1
Nos
ABB
19.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
19.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
19.06 Ammeter Selector Switch
1
Nos
ABB
19.07 Auto Manual Switch
1
Nos
ABB
19.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
19.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
18
19
Stage -14: F-14
Stage -15: F-15
19.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
19.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20.01 32A Switch Fuse Unit [SFU]
1
Nos
ABB/SIEMENS
20.02 2A, SP, MCB, 10KA
1
Nos
ABB-Germany
20.03 Indication lamp: ON
1
Nos
ABB
20.04 Current Transformer (CT)
Ratio: 32/5A
Accuracy and burden: CL5P10, 15VA
20.05 3 Phase Digital Ammeter
3
Nos
Risesun-Tiwan
1
Nos
Reshabh-India
20.06 Ammeter Selector Switch
1
Nos
ABB
20.07 Auto Manual Switch
1
Nos
ABB
20.08 Capacitor Duty Contactor with Damping Resistor for 10KVAR Capacitor
switching.
20.09 Push Button: ON, OFF
1
set
Iskra-Slovenia
2
Nos
ABB
20.10 10KVAR, 415V, 50Hz, TP dry type Resin Filled Heavy Duty Power
Capacitors with built in discharge resister.
20.11 7% Detuned Aluminum Winding Harmonic Reactor for 10kVAR
Capacitor
1
set
Iskra-Slovenia
1
set
Iskra-Slovenia
20
Stage -16: F-16
1.6. SUPPLY OF SDB-06 (FOR SINGLE STORIED MOSQUE SECURITY)
Technical Description
Sl No.
1
1.1
2
2.1
3
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 3B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
125A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
1
No.
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
Incoming From PDB-11-F3
125A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F) WITH
3.01 SHUNT TRIP
Breaking Capacity: 36KA.
1
Nos
ABB-Italy
3.02 6A TP MPCB
Current Transformer (CT)
3.03 Ratio: 125/5A
Accuracy and burden: CL:01, 15VA
Multifunction Meter
3.04
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
3.05 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB
4
Outgoing: SINGLE STORIED MOSQUE
-
63A, 4P MCB
Breaking Capacity: 10KA.
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
1
Nos
ABB-Italy
Outgoing: SECURITY OFFICE
63A, 4P MCB
Breaking Capacity: 10KA.
Outgoing: CMS 1 & 2
32A, 4P MCB
Breaking Capacity: 10KA.
Outgoing: WEIGHTING SCALE
32A, 4P MCB
Breaking Capacity: 10KA.
Outgoing: SPARE
63A, 4P MCB
Breaking Capacity: 10KA.
Outgoing: SPARE
63A, 4P MCB
Breaking Capacity: 10KA.
Outgoing: SPARE
32A, 4P MCB
Breaking Capacity: 10KA.
1.7. SUPPLY OF MCC-08 (FOR EXHAUST & SUPPLY FAN OF GENERATOR ROOM)
Technical Description
Sl No.
1
1.1
2
2.1
3
QTY Unit
Brand-Origin
Panel Description
Separation form: Form 4B, Type-2
IP: 42
Model: System Pro E
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
Common Bus-bar
630A, 415V, 65KA, For 1 Sec, TPN+PE Copper Bus-bar
8
Nos
Assembled By:
Reverie-BD
1
Set
Coppertech/
Meghna - BD
Nos
ABB-Italy
Nos
ABB
Nos
ABB/Phonix
Incoming From PCC-03-F2
630A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F) & with Shunt
3.01 Trip
1
Breaking Capacity: 50KA.
3.02 32A TP MPCB
1
3.03 Type-02 SPD
1
3.04 6A TP MPCB
3.05 3 Phase Digital Ammeter
1
Nos
ABB
1
Nos
Reshabh-India
3.06 Ammter Selector Switch
Current Transformer (CT)
3.07 Ratio: 630/5A
Accuracy and burden: CL5P10, 15VA
Multifunction Meter
3.08
Model Number: M4M 20
1
Nos
ABB
3
Nos
Risesun-Tiwan
1
No.
ABB
3.09 Indication lamps: R,Y,B
3
Nos
ABB-India
3.10 Indication lamps: ON, OFF, TRIP, ET
4
Nos
ABB-India
1
Nos
ABB-Italy
4.02 6A TP MPCB
1
Nos
ABB
4.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
4.04 Thermal Overload Relay
1
No.
ABB
4.05 Relay
1
No.
ABB
Current Transformer (CT)
4.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
4.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
4.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
5.02 6A TP MPCB
1
Nos
ABB
5.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
5.04 Thermal Overload Relay
1
No.
ABB
5.05 Relay
1
No.
ABB
Current Transformer (CT)
5.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
5.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
5.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
6.02 6A TP MPCB
1
Nos
ABB
6.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
6.04 Thermal Overload Relay
1
No.
ABB
6.05 Relay
1
No.
ABB
4
4.01
5
5.01
6
6.01
Outgoing: Supply Fan-01 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-02 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-03 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Current Transformer (CT)
6.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
6.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
6.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
7.02 6A TP MPCB
1
Nos
ABB
7.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
7.04 Thermal Overload Relay
1
No.
ABB
7.05 Relay
1
No.
ABB
Current Transformer (CT)
7.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
7.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
7.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
8.02 6A TP MPCB
1
Nos
ABB
8.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
8.04 Thermal Overload Relay
1
No.
ABB
8.05 Relay
1
No.
ABB
Current Transformer (CT)
8.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
8.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
8.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
9.01
Breaking Capacity: 50KA.
1
Nos
ABB-Italy
9.02 6A TP MPCB
1
Nos
ABB
9.03 18.5KW Magnetic Contactor
3
Nos
ABB-Bulgaria
9.04 Thermal Overload Relay
1
No.
ABB
7
7.01
8
8.01
9
Outgoing: Supply Fan-04 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-05 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-06 For Generator Room (Working)
9.05 Relay
1
No.
ABB
Current Transformer (CT)
9.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
9.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
9.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
10.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
10.04 Thermal Overload Relay
1
No.
ABB
10.05 Relay
1
No.
ABB
Current Transformer (CT)
10.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
10.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
10.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
11.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
11.04 Thermal Overload Relay
1
No.
ABB
11.05 Relay
1
No.
ABB
Current Transformer (CT)
11.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
11.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
11.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
12.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
10
10.01
11
11.01
12
12.01
Outgoing: Supply Fan-07 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-08 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: Supply Fan-09 For Generator Room (Working)
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
12.04 Thermal Overload Relay
1
No.
ABB
12.05 Relay
1
No.
ABB
Current Transformer (CT)
12.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
12.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
12.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
13.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
13.04 Thermal Overload Relay
1
No.
ABB
13.05 Relay
1
No.
ABB
Current Transformer (CT)
13.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
13.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
13.08 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
14.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
14.02 6A TP MPCB
Current Transformer (CT)
14.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
14.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
14.05 7.5KW DOL Satrter
1
No.
ABB
14.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
15.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
15.02 6A TP MPCB
Current Transformer (CT)
15.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
15.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
13
Outgoing: Supply Fan-10 For Generator Room (Standby)
13.01
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
14
15
Outgoing: Exhaust Fan-01 For Generator Room (Working)
Outgoing: Exhaust Fan-02 For Generator Room (Working)
15.05 7.5KW DOL Satrter
1
No.
ABB
15.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
16.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
16.02 6A TP MPCB
Current Transformer (CT)
16.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
16.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
16.05 7.5KW DOL Satrter
1
No.
ABB
16.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
17.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
17.02 6A TP MPCB
Current Transformer (CT)
17.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
17.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
17.05 7.5KW DOL Satrter
1
No.
ABB
17.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
18.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
18.02 6A TP MPCB
Current Transformer (CT)
18.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
18.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
18.05 7.5KW DOL Satrter
1
No.
ABB
18.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
19.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
19.02 6A TP MPCB
Current Transformer (CT)
19.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
16
17
18
19
Outgoing: Exhaust Fan-03 For Generator Room (Working)
Outgoing: Exhaust Fan-04 For Generator Room (Working)
Outgoing: Exhaust Fan-05 For Generator Room (Working)
Outgoing: Exhaust Fan-06 For Generator Room (Working)
19.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
19.05 7.5KW DOL Satrter
1
No.
ABB
19.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
20.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
20.02 6A TP MPCB
Current Transformer (CT)
20.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
20.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
20.05 7.5KW DOL Satrter
1
No.
ABB
20.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
21.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
21.02 6A TP MPCB
Current Transformer (CT)
21.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
21.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
21.05 7.5KW DOL Satrter
1
No.
ABB
21.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
22.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
22.02 6A TP MPCB
Current Transformer (CT)
22.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
22.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
22.05 7.5KW DOL Satrter
1
No.
ABB
22.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
23.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
23.02 6A TP MPCB
1
Nos
ABB
20
21
22
23
Outgoing: Exhaust Fan-07 For Generator Room (Working)
Outgoing: Exhaust Fan-08 For Generator Room (Working)
Outgoing: Exhaust Fan-09 For Generator Room (Working)
Outgoing: Exhaust Fan-10 For Generator Room (Stand By)
Current Transformer (CT)
23.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
23.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
23.05 7.5KW DOL Satrter
1
No.
ABB
23.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
1
Nos
ABB-Italy
24.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
24.04 Thermal Overload Relay
1
No.
ABB
24.05 Relay
1
No.
ABB
Current Transformer (CT)
24.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
24.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
24.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
1
Nos
ABB-Italy
25.02 6A TP MPCB
1
Nos
ABB
-KW Magnetic Contactor
3
Nos
ABB-Bulgaria
25.04 Thermal Overload Relay
1
No.
ABB
25.05 Relay
1
No.
ABB
Current Transformer (CT)
25.06 Ratio: 40/5A
Accuracy and burden: CL:01, 15VA
3
Nos
Risesun-Tiwan
25.07 01 No. Digital Ammeter
1
Nos
Reshabh-India
25.08 Indication lamps: ON, OFF, TRIP, R, ES, E/M, POT
7
Nos
ABB-India
26.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
26.02 6A TP MPCB
Current Transformer (CT)
26.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
24
24.01
25
25.01
26
Outgoing: SPARE
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: SPARE
40A, TP+N MCCB with MP Based Rel.( O/C, S/C, E/F)
Breaking Capacity: 50KA.
Outgoing: SPARE
26.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
26.05 7.5KW DOL Satrter
1
No.
ABB
26.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
27.01 16A, MPCB, Motor Protection Circuit Breker
1
No.
ABB-Italy
27.02 6A TP MPCB
Current Transformer (CT)
27.03 Ratio: 16/5A
Accuracy and burden: CL:01, 15VA
1
Nos
ABB
3
Nos
Risesun-Tiwan
27.04 01 No. Digital Ammeter
1
Nos
Reshabh-India
27.05 7.5KW DOL Satrter
1
No.
ABB
27.06 Indication lamps: ON, OFF, TRIP, R, ES, A/M
6
Nos
ABB-India
27
Outgoing: SPARE
TECHNICAL SPECIFICATION
1.1. LDB-1 For LAB
Technical Description
Sl No.
1
2.01
3
Brand-Origin
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
2
QTY Unit
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
1
Nos
ABB-Italy
6
Nos
ABB-Germany
1
Nos
ABB-Italy
6
Nos
ABB-Germany
1
Nos
ABB-Italy
6
Nos
ABB-Germany
QTY Unit
Brand-Origin
Incoming From SUB MLDB-3
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10KA.
Outgoing: PHASE-R
40A DP RCCB- Residual Current Circuit breaker
3.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
3.02 Sub Outgoing:
3.03
4
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-Y
40A DP RCCB- Residual Current Circuit breaker
4.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
4.02 Sub Outgoing:
4.03
5
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-B
40A DP RCCB- Residual Current Circuit breaker
5.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
5.02 Sub Outgoing:
5.03
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
1.2. RPDB-1
Technical Description
Sl No.
1
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
2
2.01
3
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
QTY Unit
Brand-Origin
Incoming From PDB for LAB, Storage & Admin Building
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
Outgoing: PHASE-R
40A DP RCCB- Residual Current Circuit breaker
3.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
3.02 Sub Outgoing:
3.03
4
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-Y
40A DP RCCB- Residual Current Circuit breaker
4.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
4.02 Sub Outgoing:
4.03
5
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-B
40A DP RCCB- Residual Current Circuit breaker
5.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
5.02 Sub Outgoing:
5.03
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
1.3. LDB-2 For Storage
Technical Description
Sl No.
1
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
2
2.01
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
Incoming From SUB MLDB 3
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
3
Outgoing: PHASE-R
40A DP RCCB- Residual Current Circuit breaker
3.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
1
Nos
ABB-Italy
8
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
QTY Unit
Brand-Origin
3.02 Sub Outgoing:
3.03
4
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-Y
40A DP RCCB- Residual Current Circuit breaker
4.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
4.02 Sub Outgoing:
4.03
5
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-B
40A DP RCCB- Residual Current Circuit breaker
5.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
5.02 Sub Outgoing:
5.03
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
1.4. ELDB-1 For Lab & Storage
Technical Description
Sl No.
1
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
2
2.01
3
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
1
Nos
ABB-Italy
6
Nos
ABB-Germany
Incoming From SEL DB-3
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
Outgoing: PHASE-R
32A DP RCCB- Residual Current Circuit breaker
3.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
3.02 Sub Outgoing:
3.03
4
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-Y
32A DP RCCB- Residual Current Circuit breaker
4.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
1
Nos
ABB-Italy
6
Nos
ABB-Germany
1
Nos
ABB-Italy
6
Nos
ABB-Germany
QTY Unit
Brand-Origin
4.02 Sub Outgoing:
4.03
5
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-B
32A DP RCCB- Residual Current Circuit breaker
5.01 Sensityvity: 30mA
Breaking Capacity: 10KA.
5.02 Sub Outgoing:
5.03
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
1.5. UPSDB-1
Technical Description
Sl No.
1
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
2
2.01
3
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
1
Nos
ABB-Italy
8
Nos
ABB-Germany
Incoming From SUB UPS Panel-3
32A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10KA.
Outgoing: PHASE-R
32A DP RCCB- Residual Current Circuit breaker
3.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
3.02 Sub Outgoing:
3.03
4
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-Y
32A DP RCCB- Residual Current Circuit breaker
4.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
4.02 Sub Outgoing:
4.03
5
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
Outgoing: PHASE-B
32A DP RCCB- Residual Current Circuit breaker
5.01 Sensityvity: 100mA
Breaking Capacity: 10KA.
1
Nos
ABB-Italy
8
Nos
ABB-Germany
QTY Unit
Brand-Origin
5.02 Sub Outgoing:
5.03
16A SP MCB-Miniature Circuit Breaker
Breaking Capacity: 10kA
1.6. SLDB (Steet Lighting DB)
Technical Description
Sl No.
1
Panel Description
Separation form: Form 3B
IP: 42
Model: System Pro E
1.01
Total Type Tested (TTA)
Brand-Origin: ABB-Italy
Details: As per attached Panel Catalogue
1
No.
Assembled By:
Reverie-BD
1
Nos
ABB-Germany
2.02 Current Transformer, ratio 63/5A with suitable accuracy and burden.
3
Nos
Risesun-Tiwan
2.03 3 Phase Digital Ammeter
1
Nos
Rishab-India
2.04 Ammeter Selectror Switch
1
Nos
ABB
2.05 Magnetic Contactor
1
Nos
ABB-Bulgaria
2.06 ASTRONOMICAL TIMER
1
Nos
2.07 PHOTO SENSOR
1
Nos
2.08 AUTO/MANUAL Switch
1
Nos
ABB
12
Nos
ABB-
2
2.01
3
Incoming From SUB MLDB
63A 4P MCB-Miniature Circuit Breaker
Breaking Capacity: 10 KA.
Reputed China
Brand
Reputed China
Brand
Outgoing:
16A 4P RCBO- Residual Current Circuit breaker with Overcurrent
3.01 Protection
Sensityvity: 100mA