Architectural Drawings-14
GENERAL NOTES:
A. ARCHITECTURAL
WALL
FLOOR
FINISH
FINISH
1. ALL DIMENSIONS ARE IN MILLIMETERS UNLESS OTHERWISE STATED
FF1
WF1
2. ALL LEVELS ARE IN METERS UNLESS OTHERWISE STATED.
CF1
SK1
NOTES :
a.
ALL ALUMINUM SHALL CHROMATED BEFORE STOVE ENAMELING WITH
c.
ALL ALUMINUM SECTIONS SHALL PRESENT CLEAR STRAIGHT & SHARPLY
DEFINED LINES, FREE FROM DEFECTS AND IMPERFECTIONS THAT MAY
IMPAIR STRENGTH.
d.
THE FINISHED SURFACE SHALL PRESENT A CLEAR SURFACE FREE FROM
ALLOY DEFECTS, DIE MARKS, SCRATCHES, STREAKS OR OTHER BLEMISHES.
e.
ALL ALUMINUM WORKS SHALL BE SUPPLIED ONLY BY RECOGNIZED
SYSTEM / MANUFACTURER AND SHALL BE INSTALLED BY QUALIFIED
AND EXPERIENCED WORKMEN AS APPROVED BY THE ENGINEER.
f
CONTRACTORS MUST PROVIDE AND FIX ALL NECESSARY SILICONE
SEALANTS TO EFFECTIVELY SEAL JOINTS BETWEEN MASONRY AND
ALUMINUM FRAMES.
g
DOOR AND FRAMES SHALL BE MANUFACTURER STANDARD SYSTEMS OF
EXTRUSIONS NOT LESS THAN 3 MM THICK.
POLYESTER BASED PAINT.
b.
3. THE ARCHITECTURAL DRAWINGS MUST BE READ IN CONJUNCTION
WITH THE SPECIAL CONDITIONS, THE TECHNICAL SPECIFICATIONS,
THE GENERAL CONDITIONS AND ANY ADDITIONS OR WRITTEN
CEILING
SKIRTING
FINISH
FINISH
CONTRACTOR MUST SUBMIT SHOP DRAWINGS SHOWING ALL DETAILS,
LAYOUTS, THICKNESS OF METAL, EXPANSION JOINT... ETC.
CEILING TILE LAYOUT SHALL BE DONE IN ACCORDANCE WITH THE A/C
AND ELECTRICAL REQUIREMENTS, ALL FOR ENGINEER'S APPROVAL.
INSTRUCTIONS, IN CASE OF ANY CONTRADICTION, THE ENGINEER
G
MUST BE ADVISED IMMEDIATELY.
1
c.
GRILL CALL OUT / REFERENCE
ALL COLORS SHALL BE FOR ENGINEERS APPROVAL.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO CHECK ALL THE
DRAWINGS AND VERIFY ALL DIMENSIONS AND LEVELS ON SITE.
THE CONTRACTOR MUST SUBMIT TO THE ENGINEER ALL DETAILED
D2. EXTRUDED TILES
W
1
WINDOW CALL OUT / REFERENCE
EXTRUDED TILES SHALL BE IN PLAIN COLORS AND PRODUCED WITH
DRAWINGS NEEDED PRIOR TO STARTING THE WORK. ALL WORK MUST
BE PERFORMED TO THE HIGHEST STANDARDS OF WORKMANSHIP AND
D
TO THE ENTIRE SATISFACTION OF THE ENGINEER.
1
4. ALL MATERIALS MUST MEET AMERICAN OR BRITISH EQUIVALENT
KEY-BACK PROFILE COMPLYING WITH THE GERMAN STANDARD
DOOR CALL OUT / REFERENCE
EL.
STANDARDS, UNLESS SPECIFIED OTHERWISE. WRITTEN APPROVAL OF
FLOOR PLAN ELEVATION LEVEL
THE ENGINEER MUST BE OBTAINED PRIOR TO ORDERING OR
BRINGING TO SITE ANY MATERIALS.
SPECIFICATION OF DIN 1866 OR EQUIVALENT AS FOLLOWS :
1.
TO BE ACID AND ALKALI RESISTANT.
2.
AVERAGE WATER ABSORPTION NOT BE MORE THAN 1.5%.
EL.
SECTION ELEVATION LEVEL
5. WHERE THE WORKS INCLUDE AN EXTENSION OR ALTERATION OF AN
EXISTING BUILDING, IT IS THE CONTRACTOR'S RESPONSIBILITY TO
CHECK AND VERIFY ALL RELEVANT, AS- BUILT DIMENSIONS AND LEVELS
ON SITE PRIOR TO STARTING THE NEW WORK. WHERE NECESSARY,
THE CONTRACTOR MUST ALSO CHECK THE EXTERNAL DETAILS,
DIMENSIONS, LEVELS, ETC. OF THE EXISTING BUILDING AND
MUST EXHIBIT THE UTMOST CARE TO ENSURE THAT THE NEW
WORKS ARE IN FULL CONFORMITY WITH THE EXISTING BUILDING,
OR AS SHOWN ON THE DRAWINGS AND AS INSTRUCTED BY THE
ENGINEER.
3.
AVERAGE BENDING STRENGTH NOT TO BE LESS THAN 33MPa.
4.
AVERAGE COMPRESSION STRENGTH NOT TO BE LESS THAN 200MPa.
5.
SCRATCH RESISTANT.
6.
TILES HAVE TO BE SUITABLE FOR HEAVY DUTY PURPOSES AS
A
-
CUTTING SECTION SYMBOL
(SECTION MARK)
RECOMMENDED BY THE MANUFACTURER FOR SIMILAR BUILDING
SHEET NUMBER
1
-
ELEVATION NUMBER
D3. BUILDING WATER AND DRAINAGE PIPING
ELEVATION SYMBOL
1.
SHEET NUMBER
A
ALL WATER SUPPLY PIPES SHALL BE 'ABS'.
3.
WHERE GULLY TRAPS ARE NOT PROVIDED, CONTRACTOR MUST
BLOCK WALL
300
OF PRIME, HIGH -GRADE CLASS 1 MILD ANNEALED STEEL FREE FROM
SLAB THICKNESS
SURFACE IMPERFECTIONS WITH LOUVERS TOP & BOTTOM,
(230x305x915mm) 'LYON' OR APPROVED SIMILAR.
N
COLOR SHALL BE AS APPROVED BY THE ENGINEER.
NORTH ARROW
THRESHOLD TO BE PROVIDED AT TOILET / KITCHEN DOOR LOCATION
D5. DEMOUNTABLE PARTITIONS (IF REQUIRED)
SHALL BE NATURAL STONE TYPE, MARBLE OR GRANITE.
C. SPECIFICATIONS ON FINISHES
MASTER KEY PROVIDED TO GIVE ACCESS THROUGH ANY LOCK WITHIN
1.
ALL FINISHES FOR ENGINEERS APPROVAL PRIOR TO INSTALLATION.
CHANNEL STEEL SECTIONS (STUDS & CHANNEL) AGAINST CEILING
C1. FLOORS
MASTER KEYS FOR EACH BUILDING AND FIVE GRAND MASTER KEYS
FF1
150 x 150 x 12 mm THK FULLY VITRIFIED UNGLAZED ROUGH
AND FLOOR, 'DEKO' OR APPROVED SIMILAR.
2.
TILES WITH ACID RESISTANT GROUT.
3.
B. ABBREVIATIONS, SYMBOLS & NOTATION :
FF2
REINFORCED CONCRETE
DIAMETER
EL
ELEVATION
NOTES ON DOORS
a2. ROLL-UP DOOR SHALL BE PROVIDED WITH WEATHERSTRIPPING, STEEL
GUIDES AND HOOD ENCLOSURE SHALL BE PRIME PAINT FINISHED. ALL
EXPOSED SURFACES SHALL BE POLYESTER POWDER COATED.
a3. THE SECTIONAL OVERHEAD DOOR SHALL BE ELECTRICALLY OPERATED
BY A MOTOR UNIT OF THE INDUSTRIAL TYPE AS PER THE MANUFACTURER'S
RECOMMENDATION.
AGAINST ADJOINING PARTITIONS, THE PARTITION SHALL BE
b.
FLOOR DRAIN
FF
FLOOR FINISH
FFL
FINISH FLOOR LEVEL
DPM
DAMP PROOF MEMBRANE
FINISHED WITH ANODIZED ALUMINUM PROFILES, AGAINST A
FULL EPOXY PAINT- 1 COAT EPOXY PRIMER, 1 EPOXY
WHEN A SUSPENDED CEILING IS FITTED ON BOTH SIDES OF
TOP COATS, "ICI GLIDDEN CO." OR APPROVED SIMILAR
C2. WALLS
DOORS WIDTH
CONCRETE CEILING, A STEEL SECTION ALONE SHALL BE USED
SPRAY TEXTURE MIDDLE COAT AND 2 POLYURETHANE
THE PARTITION.
4.
BOTH SIDES OF THE PARTITION SHALL BE LINED WITH 2 LAYERS
GLASS REINFORCED CONCRETE
GLASS FIBER REINFORCED PLASTIC
HT
HIGH TENSION
150 x 150 GLAZED PLAIN COLORED EXTRUDED TILES, 6mm THK MIN.
WITH TEXTURED WALL COVERING AND HELD BY ANODIZED
WITH ACID RESISTANT 2030mm. HIGH FROM FINISHED FLOOR
ALUMINUM SECTIONS FIXED TO THE STEEL POSTS WITH SELF
LEVEL AND ABOVE THAT TO CEILING EPOXY ACRYLIC COATING
TAPPING SCREWS WHICH SHALL BE CONCEALED BY COLORED
(1 COAT EPOXY PRIMER, 1 SPRAY TEXTURE MIDDLE COAT AND
PVC INSERTS FITTED INTO THE ALUMINUM SECTIONS.
OR APPROVED SIMILAR.
WF3
METER
mm
MILLIMETER
2 COATS MATT EMULSION PAINT) OVER PLASTER, NATIONAL PAINTS
UPVC
UNPLASTICISED POLYVINYL CHLORIDE
OR APPROVED SIMILAR.
RC
REINFORCED CONCRETE
RM
ROOM
RWP
RAIN WATER PIPE
SD
SECTIONAL OVERHEAD DOOR
WATER & BOIL PROOF
SRL
STRUCTURAL ROOF LEVEL
$ACCUSER$
$TI
M E$
$DATE$
$FI
LE$
User:
at :
on :
usi
ng
:
FINISHED PAVING LEVEL
FINISHED ROOF LEVEL
FGL
FINISHED GROUND LEVEL
SSL
STRUCTURAL SLAB LEVEL
1.9 MM
DOORS OVER 1220 MM
2.7 MM
b2. FOR EXTERNAL DOORS, FIRE RATED PAINTED STEEL ACCESS PANEL:
47 MM THICK FOAMED-IN-PLACED POLYURETHANE CORE INSULATED
WITH A FACE SHEET OF 16 GAUGE AND 14 GAUGE FOR DOOR FRAMES
WITH WEATHERSTRIPPING.
TENDER DOCUMENT
A
22-FEB-15
REV.
DATE
ISSUED FOR TENDER
WAM
DESCRIPTION
APPR'D
Client
b3. FOR INTERNAL DOORS, FIRE RATED PAINTED STEEL ACCESS PANEL:
47 MM THICK FOAMED-IN-PLACED POLYURETHANE CORE INSULATED
WITH A FACE SHEET OF 16 GAUGE AND 16 GAUGE FOR DOOR FRAMES
WITH WEATHERSTRIPPING.
b4. FOR EXTERNAL DOORS SHALL BE PROVIDED WITH NON-REMOVABLE
LOOSE PIN HINGES.
c.
1.
CF1
FLAT ACRYLIC FINISH (1 COAT PRIMER / SEALER, 2 COATS STUCCO,
Consultant
3.
SK1
EPOXY PAINT 100MM HIGH.
D. MATERIALS SPECIFICATION
DOORS AND WINDOWS SHALL BE OF THE DIMENSIONS AND SIZES AS SHOWN
ON THE DRAWINGS. ROUGH OPENINGS ARE OPENINGS IN WALLS.
DOOR HARDWARE
c.1. FOR DOOR HARDWARE, REFER TO STANDARD SPECIFICATIONS.
Project / Contract
2.
C4. SKIRTING
4.
ALL UNITS SHALL BE INSTALLED IN THE POSITIONS ASSIGNED TO THEM,
PLUMB SQUARE, LEVEL AND IN ALIGNMENT WITH THE SURROUNDING
WORK. THEY SHALL BE SECURELY FIXED AND ALL MOVABLE PARTS
FUNCTIONING PROPERLY.
CONTRACTOR MUST SUBMIT SHOP DRAWINGS, SHOWING ALL DETAILS,
LAYOUTS AND THICKNESS OF METAL, JOINTING, EXPANSION JOINT
SPACING AND PROCEDURES TO BE FOLLOWED INSTALLATION,
FOR ENGINEERS APPROVAL.
JEBEL ALI HILLS
ROADS & INFRASTRUCTURE
PACKAGE 5
Drawing Title
PROPOSED IRRIGATION AND
ALL IRONMONGERY SHALL BE DRAWN FROM A SINGLE MANUFACTURER'S
RANGE AND SHALL MATCH IN COLOR, FINISH AND OTHER PROPERTIES,
'MODRIC' OR APPROVED SIMILAR.
FIRE PUMP STATION
ARCHITECTURAL NOTES
D1. FALSE CEILING (IF REQUIRED)
5.
FOR DOORS AND WINDOWS SPECIFICATION, REFER TO STANDARD
SPECIFICATIONS.
6.
NOTES ON ALUMINUM DOORS AND WINDOWS
600 x 600 x 15MM GYPSUM TILES FALSE CEILING SYSTEM SHALL BE
INSTALLED BY USING UPPER AND LOWER RUNNERS. THE LOWER RUNNERS
BEING SECURED AT RIGHT ANGLES TO THE UPPER ONES. THE POSITION
OF LUMINARIES AND OTHER FITTING MUST BE TAKEN INTO CONSIDERATION
FRL
1.6 MM
OVER 945 MM AND UP TO
1220,EXTERIOR DOORS
FIRE CLASSIFICATION : FR - 60 (ACCORDING TO BS 476).
C3. CEILING
1.
FPL
945 MM OR LESS
D6. DOORS AND WINDOWS
MIMIC CONTROL CENTER
WBP
6.
EPOXY POLYSULFIDE (1000 MICRON THICK)
m
UNINTERRUPTED POWER SUPPLY
(ACCORDING TO BS 2750 AND BS 5821).
MIDDLE COAT AND 2 EPOXY ACRYLIC TOP COATS "ICI GLIDDEN CO."
MCC
TYPICAL
THE PARTITIONS SHALL BE INSULATED WITH 50mm. MINERAL WOOL.
AIRBORNE SOUND INSULATION : Rw= 52db AND DnT, W = 48db
JANITOR
UPS
5.
EPOXY ACRYLIC COATING-1 COAT EPOXY PRIMER, 1 SPRAY TEXTURE
JAN
TYP
FRAME
WHILE THE OUTER PLASTERBOARD LAYER SHALL BE COVERED
WF1
2 EPOXY ACRYLIC TOP COATS) OVER PLASTER
GRP
LAYER SHALL BE SCREWED DIRECTLY TO THE STEEL FRAME,
ALL COLORS SHALL BE FOR ENGINEERS APPROVAL.
WF2
GRC
STEEL DOORS
b1.FABRICATED FRAME
OF 13mm. PLASTERBOARD PANELS. THE INNER PLASTERBOARD
FD
SECTIONAL OVERHEAD DOORS (ROLL-UP DOOR)
a1. THE SECTIONAL OVERHEAD DOOR IS DIVIDED INTO 42mm THICK SECTIONS.
EACH SECTION HAS A HEIGHT OF 500mm. AND IS MANUFACTURED FROM
INNER AND OUTER STUCCO EMBOSSED SHEETS, PROCESS LAMINATED INTO
A STRONG SANDWICH CONSTRUCTION CORE OF POLYURETHANE GIVING A
SECTION "U" VALUE OF 0.4 W/M 2 C. INTERMEDIATE SEALING BETWEEN
SECTIONS,TOP,BOTTOM AND SIDE SEALS OF RUBBER.THE DOOR SHALL HAVE
A NATURAL ALUMINUM FINISH DOOR 'MODEL 342 CRAWFORD' OR APPROVED
SIMILAR.
THE PARTITIONS SHALL BE FINISHED AGAINST THE FLOOR WITH A
PVC SKIRTING.
NON SLIP SURFACE, 12 mm THK. PLAIN COLORED EXTRUDED
DIA
ALL WINDOWS TYPE OPENING SHALL BE FITTED WITH NEOPRENE SEALS
AND WOOL PILE WEATHERSTRIPPING IN GROOVES EXTRUDED WITH
THE SECTIONS. WINDOWS SHALL BE SUPPLIED COMPLETE WITH ALL
NECESSARY GLAZING BEADS, GASKETS, FIXING LUGS, AND OTHER
AS REQUIRED.
DEMOUNTABLE PARTITIONS SHALL CONSIST OF GALVANIZED STEEL
FRAME WITH VERTICAL POSTS. THE POSTS SHALL BE PLACED IN
CAPABLE OF GAINING ACCESS TO ALL BUILDINGS. EACH DOOR SHALL
AIR CONDITIONING
c.
a.
AND DRY AREAS MEET, ALL AS APPROVED BY THE ENGINEER.
ACRYLONITRILE-BUTADIENE-STYRENE
PROVIDE NON-VISIBLE CENTRAL NEOPRENE GASKET AS PER 'DIN 7863'
OR APPROVED SIMILAR TO ALL WINDOW PANE OPENING TO PREVENT
WATER FROM ENTERING INSIDE THE ROOMS. GASKET MUST NOT BE
EXPOSED TO SUNLIGHT.
9.
AS APPROVED BY THE ENGINEER
A/C
b.
D4. STEEL LOCKERS :
12. ALL DOORS SHALL HAVE RC LINTELS AND ALL WINDOWS SHALL
ABS
PROVIDE INTEGRAL MOSQUITO SCREEN ON THE OPENING OF
NON-FIXED WINDOW PANE.
SINKS AND URINALS, ALL AS APPROVED BY THE ENGINEER.
STEEL LOCKERS SHALL BE DOUBLE TIER AND SHALL BE MADE
RC
NOTES ON WINDOWS
a.
OPENING
11. ALL WALLS MUST BE PLASTERED BEFORE FIXING TILES.
FOR ALL BUILDINGS.
GLASS MUST REST ON PURPOSE MADE PVC GLAZING BLOCKS TO
SUIT SECTIONS DESIGN.
PROVIDE TRAPS AND CLEAN OUTS FOR ALL LAVATORIES, CLEANER'S
OUT AS RECOMMENDED BY THE APPROVED MANUFACTURER.
10. WHERE A FALSE CEILING IS SPECIFIED, WALL FINISHES SHALL
CONTINUE 200mm ABOVE THE FALSE CEILING LEVEL. STRUCTURAL SLAB
CEILING SHALL NOT BE PLASTERED.
BE PROVIDED WITH FIVE (5) KEYS TOGETHER WITH FIVE(5) SUB
d.
ALL DRAINAGE PIPES SHALL BE 'UPVC' AND SHALL BE CONCRETE
2.
COORDINATE GRID
9. WHERE EPOXY COATING IS SPECIFIED SAME SHALL BE CARRIED
THE BUILDING.IN ADDITION, A GRAND MASTER KEY SHALL BE
GLASS SHALL BE FIXED INTO FRAMES BY MEANS OF EXTRUDED NEOPRENE
GLAZING GASKETS OF PROPER PROFILES, SECTION AND SIZES TO FIT THE
VARIOUS ALUMINUM SECTIONS AND TO ENSURE A TIGHT AND WATERPROOF
SEAL AGAINST THE GLASS.
8.
FINAL SMOOTH OR TYROLEAN COAT AS SHOWN ON THE DRAWINGS.
14. DOOR LOCKS SHALL BE SUITED WITHIN BUILDINGS AND A SUB
ALL GLAZING BELOW 300mm SHALL BE TOUGHENED GLASS.
c.
ENCASED.
8. PLASTER ALL INTERNAL & EXTERNAL FACES OF CONCRETE
13. CONTRACTOR MUST ALLOW FOR PROVIDING THRESHOLDS WHERE WET
ALL ALUMINUM DOOR'S GLAZING SHALL BE 8mm THK CLEAR GLASS.
b.
TYPES.
7. ALL PLASTER TO BE AS SPECIFIED WITH ONE BASE AND ONE
HAVE R,C, LINTELS AND SILLS AS SHOWN ON THE DRAWINGS AND
NOTES ON GLAZING
a.
SECTION NUMBER
6. ALL BLOCK WALL TO BE HOLLOW BLOCK EXCEPT WHERE
OTHERWISE INDICATED ON THE DRAWINGS OR INSTRUCTED BY THE
ENGINEER.
BLOCK WORK.
7.
a.
ALL ALUMINUM WORK SHALL BE HEAVY DUTY BRONZE ANODIZED ALUMINUM.
UNLESS OTHERWISE SPECIFIED.
b.
ALL ALUMINUM WORKS WITH ANODIZED FINISH SHALL HAVE
22 MICRONS COATING.
WHEN SETTING OUT THE UPPER GRID. THE FALSE CEILING MUST BE
INSTALLED AS PER THE MANUFACTURER'S RECOMMENDATION.
CONTRACT No:
JOB No:
350655
DRAWN
DESIGNED
CHECKED
AH
MS
LB
WAM
DATE
ACTUAL SIZE
HORZ SCALE :
25-NOV-2014
Drawing No.
AR_IR_851_12_12_001
APPROVED
A1
Rev.
A