SPECIFICATIONS:
THE SITE
ALL ELECTRICAL WORKS SHALL BE DONE IN ACCORDANCE WITH THE PROVISIONS OF THE LATEST EDITION
OF THE PHILIPPINE ELECTRICAL CODE. THE LAWS AND ORDINANCES OF THE LOCAL CODE ENFORCING
AUTHORITIES AND REQUIREMENTS OF THE LOCAL POWER.
THE CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES REQUIRED FOR THE WORK AND SHALL
FURNISH THE OWNER THROUGH THE ENGINEERS FINAL CERTIFICATE OF ELECTRICAL INSPECTION AND
APPROVED FROM PROPER GOVERNMENT AUTHORITIES FOR COMPLETE WORK.
ALL MATERIALS TO BE USED SHALL BE NEW AND INSTALLED IN APPLICATION FOR WHICH THEY ARE INTENDED.
ALL ELECTRICAL WIRING AND INSTALLATIONS SHALL BE OF RSC/PVC ELECTRICAL CONDUIT.
ALL METALLIC CONDUITS, CABINETS AND EQUIPMENT SHALL BE PROPERLY GROUNDED AND BONDED. ALL
RECEPTACLE OUTLETS AND BRANCH CIRCUIT GROUND WIRES SHALL BE ADEQUATELY GROUNDED TO THE BOX BY MEANS OF
GROUNDING LUGS.
ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL ENGINEER.
Ø RSCP
SERVICE EQUIPMENT SHALL BE 200 A, 2P, 250 MCCB.
V I C I N I T Y
M A P
scale
NTS
FEEDER LINE
MAIN FEEDER
100mm² THW. Cu.
WIRE IN 1''
M
RSC
SCHEDULE OF LOADS
MARK
14 CEILING LIGHT OUTLET
17 CEILING LIGHT OUTLET
3.5MM sq. THW / 20MM
3.5MM sq. THW / 20MM
PIPE
PIPE
9 CONVINIENCE OUTLET
3.5MM sq. THW / 20MM
8 CONVINIENCE OUTLET
3.5MM sq. THW / 20MM
PIPE
PIPE
RANGE
3.5MM sq. THW / 20MM
REFRIGERATOR
5.5MM sq. THW / 20MM
PIPE
PIPE
AIRCON UNIT
5.5MM sq. THW / 20MM
AIRCON UNIT
5.5MM sq. THW / 20MM
PIPE
PIPE
AIRCON UNIT
5.5MM sq. THW / 20MM
SPARE
5.5MM sq. THW / 20MM
PIPE
PIPE
DESCRIPTION
VOLTS
NO.OF
UNITS
WATTS
AMPERE
CIRCUIT
BREAKER
C-1
CEILING LIGHT OUTLET
230
14
1400
6.08
20AT
C-2
CEILING LIGHT OUTLET
230
17
1700
7.39
20AT
3.5MM sq. THW / 20MM
C-3
CONVENIENCE OUTLET
230
9
3240
14.08
30AT
5.5MM sq. THW / 20MM
C-4
CONVENIENCE OUTLET
230
8
2800
12.17
30AT
5.5MM sq. THW / 20MM
C-5
RANGE
230
1
3000
13.04
30AT
5.5MM sq. THW / 20MM
C-6
REFRIGERATOR
230
1
1500
6.52
30AT
5.5MM sq. THW / 20MM
C-7
AIRCON UNIT
230
1
1000
4.34
30AT
5.5MM sq. THW / 20MM
C-8
AIRCON UNIT
230
1
1000
4.34
30AT
5.5MM sq. THW / 20MM
C-9
AIRCON UNIT
230
1
1000
4.34
30AT
5.5MM sq. THW / 20MM
C-10
SPARE
C-11
SPARE
TOTAL:
72.3 AMPS
COMPUTATION OF LOAD
TOTAL COMPUTED LOADS = 72.3 AMPS
=72.3 AMPS(1.25)
= 90.37 AMPS
SPARE
5.5MM sq. THW / 20MM
NO. OF WIRE / SIZE OF
CONDUCTOR
3.5MM sq. THW / 20MM
USE:
150 AT CKT BREAKER
100mm2 THW. CU.
WIRE IN 1'' RSC
PIPE
SINGLE LINE DIAGRAM
IMPORTANT
CERTIFIED BY:
PREPARED BY THE OFFICE OF:
ELECTRICAL ENGINEER
LOCATION:
PRC NO.:
PTR NO.:
VALIDITY:
DATE:
TIN NO.:
PLACE:
ALL DESIGNS, SPECIFICATIONS AND
COPIES THEREOF, PREPARED AND
FURNISHED BY THE ARCHITECT IN
C ON N EC TI ON W IT H THIS P ROJE CT , ARE
INSTRUMENTS OF PROFESSIONAL
SERVICE. AS INSTRUMENTS OF
PRO FESS ION AL SE RVICE, TH EY ARE THE
PR OP ER TY O F TH E A RC HI TECT
WHETHER THE WORK FOR WHICH THEY
ARE MADE M AY BE EXEC UTED OR NOT,
AND ARE NOT TO BE REPRODUCED
OR USED ON OTHER WORK EXCEPT
BY WRITTEN AG REE MEN T WITH
T H E
A R C H I T E C T .
PROJECT TITLE:
TWO (2) STOREY THREE (3) BEDROOM
RESIDENTIAL HOUSE
LOCATION:
LOT 7, BLOCK3 , BRGY. TABUNAN,
BAGO CITY, NEG. OCC.
OWNER:
RONALD G. STIESS & LORES MAE B. STIESS
REVISIONS:
SHEET CONTENTS:
AS SHOWN
SHEET NO.:
E
1