Acacia Lane
SINGLE FAMILY RESIDENCE ADDITION
Owner:
DRAWING SCHEDULE
APPLICABLE CODES
CODE COMPLIANCE
TITLE
C-S COVER SHEET
THIS BUILDING IS DESIGNED IN ACCORDANCE WITH
THE FOLLOWING CODES AND APPLICABLE
SECTIONS AND REQUIREMENTS:
ZONING DATA:
GN
GENERAL NOTES
2012 VIRGINIA CONSTRUCTION CODE
2012 VIRGINIA RESIDENTIAL CODE
2012 VIRGINIA FIRE PROTECTION CODE
2012 VIRGINIA ENERGY CONSERVATION CODE
2012 INTERNATIONAL BUILDING CODE
2012 INTERNATIONAL RESIDENTIAL CODE
CODE ITEM
PROJECT INFORMATION
BUILDING DATA:
ALLOWED/REQUIRED
PROPOSED/PROVIDED
EROSION AND SEDIMENT CONTROL NOTES AND SITE PLAN
C-2
EROSION AND SEDIMENT CONTROL DETAILS
D-1
EXISTING BASEMENT & FIRST FLOOR DEMOLITION PLAN
D-2
EXISTING SECOND FLOOR & ROOF DEMOLITON PLAN
LOT WIDTH (MIN)
100'
100'
D-3
EXISTING NORTH AND EAST ELEVATION
GROSS FLOOR AREA
(FOOTPRINT)
1,681 SF
2,422 SF
ARCHITECTRUAL NOTES & PROPOSED BASEMENT PLAN
SINGLE FAMILY RESIDENCE:
LOT:
SQUARE:
LOT AREA:
R-2C
R-2C
USE GROUP
R-3
R-3
USE TYPE
RESIDENTIAL
RESIDENTIAL
CONSTRUCTION TYPE
3B
3B
GROSS FLOOR AREA
3,121 SF
3,121 SF
CONSTRUCTION
KITCHEN EXTENSION
KITCHEN EXTENSION
NUMBER OF STORIES
2 STORIES
2 STORIES
NUMBER OF EXITS
4
4
CORRIDOR WIDTH
N/A
N/A
SITE AREA
-
PROJECT DESCRIPTION/
SCOPE OF WORK
313 SF EXTENTION TO KITCHEN AND ENTRYWAY, TO INCLUDE PERGOLA FOR FRONT ENTRY AND
DECK ON EAST SIDE OF BUILDING
PROPOSED
PROPOSED FIRST FLOOR PLAN
GARAGE
(FOOTPRINT)
489 SF
A-3
PROPOSED LIGHTING PLAN
NUMBER OF STORIES
2 STORIES
2 STORIES
A-4
PROPOSED ROOF PLAN
OVERALL BUILDING
HEIGHT
35'-0"
16'-0"
N/A
75%
A-5
PROPOSED NORTH & SOUTH ELEVATIONS
PERCENTAGE OF LOT
A-6
PROPOSED EAST ELEVATION
OCCUPANCY
A-7
PARTITON WALL SECTIONS
F.A.R
N/A
N/A
FRONT YARD
25'
25'
SIDE YARD
8' TOTAL MIN - 24'
8' TOTAL MIN - 24'
REAR YARD
25'
25'
CLOSED COURT YARD
COURT YARD
N/A
N/A
DOOR, WINDOW & ROOM FINISH SCHEDULES
PROPOSED/PROVIDED
ZONING DESIGNATION
A-2
A-8
ALLOWED/REQUIRED
APPLICABLE
BUILDING CODE
APPLICABLE
ZONING CODE
C-1
A-1
CODE ITEM
PROJECT TYPE:
INTERIOR, EXTERIOR RENOVATION
FACILITY USES:
RESIDENTIAL SPACE
APPLICABLE FIRE
FIRE PROTECTION
EXTERIOR WALLS 2HRS
EXTERIOR WALLS 2HRS
MAIN STRUCTURAL
MATERIALS
MASONRY & WOOD
MASONRY & WOOD
CRITICAL FIRE RATED
ELEMENTS
1 HOUR SEPARATION
2 HOUR SEPARATION
TOTAL PROGRAM AREA:
313 SF
GROSS BUILDING AREA:
LEVEL 1:
887 SF
LEVEL 2:
842 SF
BASEMENT: 1392 SF
TOTAL:
3,121 SF
15%
NET to GROSS RATIO: 1.12
PARKING SPACES:
2
APPLICABLE ENERGY
CODE
REMARKS:
INDOOR RECREATION
OUTDOOR RECRATION
N/A
N/A
ROOF STRUCTURE
COMPOSITION SHINGLE
COMPOSITION SHINGLE
PARKING
1 DETACHED GARAGE
1 DETACHED GARAGE
REMARKS:
N
200 FT
LOCATION MAP
N
2000 FT
VICINITY MAP
PROJECT ID #: INF-010-DRG-001
PERMIT SET
PROJECT No. 010
MARCH 17, 2015
NO.
DATE
ISSUE
GENERAL NOTES
DESIGN LOADS
SHOP DRAWINGS
DESIGN LIVE LOADS
THE GENERAL CNTRACTOR (OR CONSTRUCTION MANAGER) SHALL SUBMIT SHOP DRAWING FOR ALL
STRUCTURAL ELEMENTS SHOWN ON THE CONTRACT DOCUMENTS FOR APPROVAL (ONE REPRODUCIBLE PLUS NOT
MORE THAN TWO PRINTS). THE STRUCTURAL ENGINEER WILL NOT BE RESPONSIBLE FOR THE STRUCTURAL
CERTIFICATION AND DESIGN OF THE PROJECT IF GENERAL CONTRACTOR FAILS TO OBTAIN APPROVAL OF
THE SHOP DRAWINGS. THE GENERAL CONTRACTOR SHALL INFORM THE STRUCTURAL ENGINEER IN WRITING
CONCERNING DEVIATIONS AND/OR OMISSION FROM THE CONTRACT DOCUMENTS AT THE TIME OF SHOP
DRAWINGS SUBMISSION. THE GENERAL CONTRACTOR SHALL REVIEW ALL SHOP DRAWINGS AND SHALL MAKE ALL
CORRECTIONS HE DEEMS NECESSARY BEFORE SUBMISSION. THE GENERAL CONTRACTOR SHALL STATE ON THE
SHOP DRWAINGS THAT CONTRACT DOCUMENT REQUIREMENTS HAVE BEEN MET AND THAT ALL DIMENSIONS,
CONDITIONS AND QUANTITIES HAVE BEEN REVIEWED AND VERIFIED AS SHOWN AND/OR CORRECTED ON THE
SHOP DRAWINGS.
THE FOLLOWING DESIGN LIVE LOADS HAVE BEEN USED, AS SPECIFIED IN CHAPTER 16 OF THE VIRGINA CONSTRCTION CODE,
THE 2010 ASCE-7 AND CHAPTER 3 OF THE 2012 VIRGINIA RESIDENTIAL CODE.
FLOOR LIVE LOAD (SECTION 1607.1)
FLOORS
40 LBS./SQ. FT.
PARTITION LOAD
20 LBS./SQ. FT.
STAIRS
40 LBS./SQ. FT.
SLAB ON GRADE
100 LBS./SQ. FT.
FLOORS ARE DESIGNED FOR THE UNIFORMLY DISTRIBUTED LIVE LOADS NOTED ABOVE OR ACTUAL
CONCENTRATED LOADS, WHERE SUCH LOADING GOVERNS.
CONCRETE (CAST-IN-PLACE)
EXISTING WOOD FRAMED FLOORS AND FIRST FLOOR CONCRETE SLAB WERE VERIFIED FOR 40 LBS./SQ. FT.
LIVE LOAD AND 20 LBS./SQ. FT. PARTITION LOAD.
ROOF SNOW LOAD
Pg = 30.0
Ce = 0.9
I = 1.0
REQUIRED Pf = (0.7) (1) (30) = 21 PSF
ADDITIONAL LOADS DUE TO SNOW DRIFT AND SLIDING SNOW HAVE BEEN
CONSIDERED WHERE APPLICABLE.
WIND LOAD (SECTION 1603.5)
BASIC WIND SPEED
90 MPH
WIND LOAD IMPORTANCE FACTOR 1.0
WIND EXPOSURE CATEGORY
EXPOSURE B
EXCAVATION SHORING AND BRACING, UNDERPINNING
DESIGN AND INSTALLTION OF EXCVATION SUPPORT SYSTEM (SHORING AND BRACING, AND UNDERPINNING OF
EXISTING BUILDING FOUNDATIONS), SHALL BE PERFORMED UNDER DIRECT SUPERVISION OF A SPECIALIST.
PRIOR TO STARTING THE WORK, THE CONTRACTOR SHALL SUBMIT PROPOSED DESIGN OF SHEETING,
UNDERPINNING, SHORING AND BRACING, COMPLETE WITH CALCULATIONS, DRAWINGS AND OTHER DATA INCLUDING
SEQUENCE OF OPERATIONS, PREPARED AND CERTFIED BY A REGISTERED PROFESSIONAL ENGINEER.
THE EXCAVATION SITE SHALL BE PROTECTED AGAINST CAVING AND UNACCEPTABLE MOVEMENT OF SOIL AT ALL
TIMES. WHEREVER SHEETING AND SHORING IS REQUIRED, IT SHALL BE SO LOCATED AS TO CLEAR ALL
PERMANENT CONSTRUCTION AND PERMIT THE PROPER FORMING AND FINISHING OF CONCRETE SURFACES, AND
SHALL BE ANCHORED AND BRACED TO RESIST EARTH AND HYDROSTATIC PRSSURE.
SHEETING AND SHORING RETAINING EARTH ON WHICH THE SUPPORT AND/OR STABLITY OF EXISTING
STRUCTURES IS DEPENDENT MUST BE LEFT IN PLACE AT THE COMPLETION OF THE WORK, AND SHALL BE
STEEL OR CONCRETE. IF WOOD IS USED AS PART OF THE SHEETING, SHORING AND BRACING SYSTEM NEAR
EXISTING DEBRIS, IT MUST BE REMOVED PRIOR TO THE PLACEMENT OF BACKFILL.
EXCAVATION BRACING OR TEMPORARY BRACING OF EXISTING WALLS TO REMAIN MUST CLEAR COLUMNS, FLOOR
FRAMING CONSTRUCTION, AND OTHER PERMANENT WORK, AND CARE SHALL BE TAKEN TO SET WALES AND
BRACES ACCURATELY SO AS TO AVOID UNNECESSARY SHIFTING OF BRACES. SHOULD IT BECOME NECESSARY
TO MOVE A BRACE, A NEW BRACE SHALL BE INSTALLED PROPERLY PRIOR TO REMOVAL OF THE
ORIGINAL BRACE. BRACING SHALL NOT BE CAST INTO OR INCLUDED IN PERMANENT CONCRETE WORK, EXCEPT
AS SPEFICALLY APPROVED BY THE ENGINEER, IN EACH OF WHICH CASE THE PROPER KEYS, CUTOFFS,
WATERSTOPS AND WATERPROOFING MUST BE PROVIDED. WHER USED , ALL INTERNAL BRACING SHALL BE
INSTALLED (POSTED AND TIED) SO AS TO PREVENT SPREADING OR DISTORTION OF THE BRACED FRAMES.
CARE SHALL BE TAKEN TO PROPERLY SUPPORT HORIZONTAL WALES TO PREVENT UNACCEPTABLE MOVEMENT OR
OVERTURNING DUE TO THRUST FROM THE BRACING. THE CONTRACTOR SHALL INSURE THAT EFFICIENT MEANS
ARE PROVIDED TO PROPERLY TRANSFORM EXTERNAL
FORCES FROM THE SHEETING AND SHORING TO THE INTENAL BRACING. FILLER AND WEDGES SHALL BE
LEVEL OF BRACING, AND MAINTAINED IN A MANNER AS FOR THE BRACING SYSTEM TO BE PROPERLY STRESSED
AT ALL TIMES. ALL ABUTTING ENDS OF BRACING SHALL BE IN FULL BEARING ACROSS THE ENTIRE SECTION
OF THE MEMBER.
CONCRETE DESIGN AND DETAILING SHALL CONFORM TO THE REQUIREMENTS OF ACI 318 AND ACI 301, LATEST
EDITIONS. CONTRACTOR SHALL SUBMIT MIX DESIGNS ACCOMPANIED BY APPROPRIATE GRAPHS AND
BACKGROUND DATA FOR APPROVAL. MIX DESIGN SHALL INDICATE 7 AND 28 DAYS STRENGTHS, CEMENT
CONTENT, AIR CONTENT, WATER-CEMENT RATIO, AMOUNT OF FINE AND COARSE AGGREGATES, AND ADMIXTURES.
MINIMUM ULTIMATE COPRESSIVE STRENGH OF CONCRETE AT 28 DAYS SHALL BE AS FOLLOWS, UNLESS NOTED
OTHERWISE.
SLAB ON GRADE
3000 PSI
WALLS AND PIERS
4000 PSI
GRADE BEAMS
3000 PSI
PEA-GRAVEL CONCRETE (GROUT)
2500 PSI (FOR FILLING CMU UNITS)
ALL OTHER CONCRETE
3000 PSI
ALL EXTERIOR CONCRETE AND CONCRETE EXPOSED TO WEATHER SHALL BE AIR RETAINED.
SLABS POURED ON GRADE SHALL BE MINIMUM 5" THICK, PLACED OVER VAPOR BARRIER AND 5" OF WASHED
GARVEL UNLESS NOTED OTHERWISE. SLABS ON GRADE SHALL BE REINFORCED WITH 6x6 - W1.4xW1.4
WELDED WIRE FABRIC PLACED AT MID DEPTH OF SLAB. LAP WELDED WIRE FABRIC ONE FULL MESH AT ENDS
AND SIDES.
PROVIDE KEYED CONSTRUCTION JOINTS AT COLUMN CENTERLINES AND CENTERLINES OF 30'-0" OR LARGER
BAYS, UNLESS OTHERWISE SHOWN ON THE DRAWINGS. PROVIDE DIAMOND OR ROUND SHAPE ISOLATION JOINTS
AROUND COLUMN BASES. POUR CONCRETE INTO ISOLATION JOINTS AROUND COLUMN BASES AFTER SLAB ON
GRADE IS POURED
ALL CONCRETE WORK, REINFORCING PLACEMENT, FORMWORK AND SHORING SHALL BE INSPECTED UNDER THE
SUPERVISION OF A REGISTERED PROFESSIONAL ENGINEER. CONCRETE QUALITY CONTROL, INSPECTION AND
TESTING SHALL BE IN STRICT ACCORDANCE WITH THE PROJECT SPECIFICATIONS, AS WELL AS LOCAL BUILDING
CODE REQUIREMENTS.
USE OF ADDICTIVE SHALL NOT BE PERMITTED UNLESS SPECIFICALLY APPROVED BY THE STRUCTURAL ENGINEER.
USE OF ADDICTIVE CONTAINING CALCIUM CHLORIDE SHALL NOT BE PERMITTED (OVER GALVANIZED METAL DECK)
(IN POST-TENSIONED CONCRETE).
THE CONCRETE PROTECTION FOR REINFORCCEMENT (CAST-IN-PLACE CONCRETE)
ALL EXISTING ACTIVE SEWER, WATER, GAS, ELECTRIC AND OTHER UTILITY SERVICES AND STRUCTUIRES SHALL BE
LOCATED BY THE CONTRACTOR AND PROTECTED AT ALL TIMES.
STRUCTURAL STEEL
STRUCTURAL STEEL SHALL CONFORM TO THE LATEST EDITION OF THE AISC "SPECIFICATION FOR THE DESIGN,
FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDING". STEEL IDENTIFIED AS GRADE 50 SHALL
CONFORM TO ASTM A572, GRADE 50 (FY = 36 KSI). STEEL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
STEEL TUBE SHALL CONFORM TO ASTM A500, GRADE B. ALL OTHER STEEL SHALL CONFORM TO
ASTM A36 (FY = 36 KSI).
BOLTED, WELDED AND COMBINATION CONNECTIONS SHALL BE DETAILED IN ACCORDANCE WITH "FRAMED BEAM
CONNECTION" USING TWO WEB ANGLES AS SHOWN IN THE LATEST EDITION OF THE AISC "MAUAL OF STEEL
CONSTRUCTION" (ALLOWABLE STRESS DESIGN).
SEATED CONNECTION SHALL BE DETAILED IN ACCORDANCE WITH "SEATED BEAM CONNETIONS" AS SHOWN IN
THE LATEST EDITION OF THE AISC "MANUAL OF STEEL CONSTRUCTION", AND MAY BE USED TO CONNECT STEEL
JOIST TO COLUMN FLANGES OR STEEL BEAMS TO GIRDERS AND GIRDERS TO COLUMN. PROVIDED WELDED
STABILIZER PLATES OR ANGLES AT TOP OF BEAMS AT ALL SEATED CONNECTIONS.
STEEL CONNECTIONS AT ENDS OF MEMBERS SHALL BE DESIGNED (FOR THE REACTION NOTED ON THE
DRAWINGS) FOR THE FRACTION OF THE "ALLOWABLE UNIFORM LOAD" AS GIVEN IN THE AISC MANUAL FOR THE
MEMBER, THE SPAN AND GRADE OF STEEL, AS FOLOWS:
FOOTING
PLACE COMPACTED FILL REQUIRED TO BRING SUBGRADE TO PROPER ELEVATION PRIOR TO FOUNDATION WORK.
BOTTOM OF ALL EXTERIOR FOOTING SHALL BE A MINIMUM OF 2'-6" BELOW FINISHED EXTERIOR GRADE,
UNLESS A LOWER ELEVATION IS NOTED. FOOTING ELEVATIONS NOTED ARE EXTIMATED BASED ON AVAILABLE
GEOTECHNICAL AND GRADING INFORMATION.
ALL FOUNDATION SUBGRADES SHALL BE INSPECTED AND APPROVED UNDER THE SUPERVISION OF A REGISTERED
PROFESSIONAL ENGINEER PRIOR TO BEING CONCRETED. FOOTING MAY BE LOWERED TO ACHIEVE BEARING
CAPACITY, IF REQUIRED, SUBJECT TO REVIEW AND APPROVAL OF THE STRUCTURAL ENGINEER.
LATERAL BRACING OF STRUCUTURAL ELEMENTS
PROVIDE ADEQUATE BRACING AND SHORING FOR BASEMENT, RETAINING AND PIT WALLS. BRACE BASEMENT AND
PIT WALLS UNTIL SUPPORTING FLOORS ABOVE ARE IN PLACE AND HAVE ATTAINED DESIGN STRENGTH. DO NOT
BACKFILL WALLS UNTIL AFTER FLOORS AT THE TOP AND BASE OF THE WALLSS ARE IN PLACE. WHERE
BACKFILL IS REQUIRED ON BOTH SIDES OF A WALL, BACKFILL BOTH SIDES SIMULTANEOUSLY WITH THE GRADE
DIFFERENCE NOT EXCEED 2'-0" AT ANY TIME.
LATERALLY BRACE BUILDING WALLS IN AN APPROVED MANNER AT A MAXIMUM HORIZONTAL SPACING OF 8'-0"
O.C. (6'-0" O,C.) BRACING SHALL REMAIN IN PLACE UNTIL ROOF OR FLOOR MEMBERS HAVE BEEN SECURELY
ANCHORED TO THE WALL.
PROVIDED ADEQUATE BRACING AND GUY-WIRING FOR STEEL FRAME AND MEMBERS DURING STEEL ERECTION AND
CONCRETE WORK ON DECK. STEEL FRAME SHALL BE PLUMB WITHIN AISC TOLERANCES AND PROJECT
SPECIFICATION REQUIREMENTS.
WALLS SUPPORTED BY OR CONNECTED TO STEEL FLOOR MEMBERS SHALL NOT BE PLACED UNTIL PERMANET
ANCHORAGE AND BRACING SYSTEMS HAVE BEEN INSTALLED, AND UNTIL CONCRETE WORK FOR FLOOR DECK IS
COMPLETED. WALLS AND PARAPETS SUPPORTED BY OR CONNECTED TO STEEL ROOF BEAMS SHALL NOT BE
PL.ACED UNTIL ROOF DECK INSTALLATION IS COMPLETE.
METAL PLATE CONNECTED WOOD TRUSSES SHALL BE DESIGNED AND FABRICATED IN ACCODANCE WITH THE
REQUIREMENTS OF ANSI/TPI 1-1995, "NATIONAL DESIGNED STANDARD FOR METAL PLATE CONNECTED WOOD
TRUSS CONSTRUCTION", AMERICAN FOREST & PAPER ASSOCIATION'S " NATIONAL DESIGN SPECIFICATION FOR
WOOD CONSTRUCTION", AND APPLICABLE BUILDING CODE AS REFERENCED. THE TRUSS MANUFACTURER SHALL
DESIGN WOOD TRUSSES FOR THE SPAN, PROFILE AND LOADS/LOADING CONDITIONS SPECIFIED ON THE
DRAWINGS. STANDARD TEMPERATURE AND MOISTURE CONDITIONS SHALL BE ASSUMED UNLESS SPECIFICALLY
NOTED OTHERWISE.
TRUSS MANUFACTURER SHALL FURNISH DESIGN DRAWINGS BEARING THE SEAL AND REGISTRATION NUMBER OF
A PROFESSIONER ENGINEER LICENSED IN MARYLAND. DRAWINGS SHALL INCLUDE AT A MINIMUM THE
INFORMATION SPECIFIED IN SECTION 2303.4.1 OF THE 2000 INTERNATIONAL BUILDING CODE, AND SHALL BE
APPROVED THE ARCHITECT AND ENGINEER OF RECORD PRIOR TO TRUSS FABRICATION. LUMBER USED AS
TRUSS MEMBERS SHALL BE IDENTIFIED BY THE GRADE MARK OF A LUMBER INSPECTION BUREAU OR AGENCY
APPROVED BY BOARD OF REVIEW OF AMERICAN LUMBER STANDARDS COMMITTEE. METAL CONNECTOR PLATES
SHALL BE MANUFACTURED BY A COMPANY MAINTAINING A RESEARCH REPORT WITH THE GOVERNING MODEL
CODE AGENCY AND SHALL MEET OR EXCEED APPLICABLE STEEL SPECIFICATIOINS.
EMBEDDED ITEMS/ELEVATOR BEAMS
ANCHOR BOLTS, BEARING PLATES, INSERTS, LEVELING PLATES AND MISCELLANEOUS ITEMS SHALL BE LOCATED
AND BUILT INTO CONNECTING WORK USING PRESET TEMPLATES. BEARING PLTES SHALL BE SET IN FULL
BEDS OF NON-SHRINK GROUT AFTER LEVELING AND ADJUSTMENT.
OPENINGS AND PIPE SLEEVES
SIZE AND LOCATION OF ALL OPENING SHALL BE COORDINATED WITH ARCHITECTURAL, ELETRICAL, MECHANICAL
AND PLUMBING DRAWINGS. FORM OPENINGS AND PROVIDE PIPE SLEEVES WHEN POURING CONCRETE. HOLES
LARGER THAN 2" IN DIAMETER SHALL NOT BE CUT INTO SLABS WITHOUT PERMISSION OF THE STRUCTURAL
ENGINEER. ARRNGE REINFORCING AROUND OPENINGS AS SHOWN IN TYPICAL DETAILS. EMBEDDED PIPE OR
CONDUITS SHALL BE SPACED AT LEAST THREE DIAMETERS ON CENTERS, UNLESS OTHERWISE NOTED.
EXCESSIVE CROSSING OVER OF CONDUITS IN SLAB WILL NOT BE PERMITTED. PIPE SLEEVES SHALL NOT BE
SPACED CLOSER THAN 8" CLEAR FROM ANY COLUMN UNLESS NOTED ON DRAWINGS. PLACE SLAB BARS TO
CLEAR SLEEVES AND MAINTAIN 1 1/2" CLEAR SPACING BETWEEN BARS. WHERE SLEEVES ARE CLOSELY SPACED
IN A GROUP SHALL BE TREATED AS AN OPENING AND REINFORCED ACCORDINGLY. WHERE
FLOORS ARE PENETRATED BY OPENNINGS, SEAL THE OPENING TO MAINTAIN THE INTEGRITY OF FIRE RATING.
LINTELS
STEEL: IN SINGLE-WYTHE AND COMPOSITE MASONRY WALLS PROVIDE ONE STEEL ANGLE
FOR EACH 4" OF WALL THICKNESS IN MASONRY WALLS ACCORDING TO THE FOLLOWING
SCHEDULE,
OPENINGS UP TO 3'-0" L 3 X 3 1/2 X 1/4 (3 1/2 LEG HORIZONTAL)
3'-1" TO 5'-0" L 4 X 3 1/2 X 5/16
"
5'-1" TO 8'-0" L 5 X 3 1/2 X 3/8
"
WHERE CAVITY WALLS ARE UTILIZED, PLACE ANGLE UNDER CMU AS PER SCHEDULE ABOVE,
AND UNDER BRICK PLUS CAVITY SPACE AS PER SCHEDULE BELOW.
(USE FOR 1" CAVITY WIDTH)
OPENINGS UP TO 3'-0" L 4 X 3 X 1/4 (4" LEG HORIZONTAL)
3'-1" TO 5'-0" L 4 X 4 X 5/16
'
5'-1" TO 8'-1" L 6 X 4 X 5/16
"
(USE FOR 2" CAVITY WIDTH)
OPENINGS UP TO 3'-0" L 5 X 3 X 1/4 (5" LEG HORIZONTAL WITH STEEL
3'-1" TO 5'-0" L 5 X 5 X 5/16
5'-1" TO 8'-0" L 5 X 5 X 3/8
"
"
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
DOUBLE LINTEL AND SPACERS SHALL BE WELDED EACH TO EACH OTHER AT 12" O.C. MAX.
PRECAST CONCRETE: WHERE STEEL LINTELS ARE NOT INDICATED PROVIDE PRECAST
CONCRETE LINTELS IN NON-BEARING WALLS WITH OPENINGS UP TO 8'-0" ACCORDING
TO THE FOLLOWING SCHEDULE. (CONCRETE STRENGTH = 4,000 PSI).
4"
6"
8"
12"
WALLS 4" X 8" WITH 1 - #4 TOP AND BOTTOM
WALLS 6" X 8" WITH 1 - #5 TOP AND BOTTOM
WALLS 8" X 8" WITH 2 - #4 TOP AND BOTTOM
WALLS TWO 6" X 8" WITH 1 - #5 TOP AND BOTTOM EACH
PROVIDE #3 TIES AT 8" O.C. IN PRECAST CONCRETE LINTELS.
LINTELS SHALL BEAR A MINIMUM OF 6 INCHES (8 INCHES) AT EACH END ON A MINIMUM
OF 8 INCH DEPTH OF BRICK OR SOLID MASONRY, UNLESS OTHERWISE NOTED.
SEAL
REINFORCING STEEL
REINFORCING BARS SHALL BE DEFORMED BILLET STEEL COFORMING TO ASTM A615, GRADE 60. ALL WELDED
WIRE FABRIC SHALL CONFORM TO ASTM A-185. REINFORCING BAR MATS SHALL ALSO CONFORM TO ASTM
A184. BARS SHALL BE BRANDED BY THE MANUFACTURER WITH BAR SIZE GRADE OF STEEL AND CERTIFIED
MILL REPORTS SHALL BE SUBMITTED FOR RECORD. REINFORCING STEEL SHALL BE DETAILED IN ACCORDANCE
WITH THE ACI "MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES", LATEST
EDITION.
PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER FOR REINFORCEMENT:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH (FOOTINGS, GRADE
BEAM BOTTOMS): 3"
FORMED CONCRETE EXPOSED TO EARTH OR WEATHER (PIERS, GRADE BEAM SIDES, WALLS AND EXTERIOR
SLABS):
#6 BAR OR LARGER: 2"
#5 BAR, W31 OR D31 WIRE AND SMALLER: 1 1/2"
SLABS, WALLS, JOISTS:
ALL BRACING SHALL BE MAINTAINED UNTIL STRUCTURAL ELEMENTS ARE REBRACED BY OTHER BRACING OR
UNTIL THE PERMANENT FLOOR CONSTRUCTION IS ABLE TO WITHSTAND THE LATERAL EARTH AND GROUND WATER
PRESSURES. REMOVE SHEETING, SHORING AND BRACING IN A MANNER TO AVOID HARMFUL DISTURBANCE TO
UNDERLYING SOILS AND DAMAGE TO BUILDINGS, STRUCTURES, PAVEMENTS,FACILITIES AND UTILITIES. WHERE
SHEETING IS ANCHORED TO THE SOILS IT RETAINS, ALL PRESTRESSED TIEBACK RODS SHALL BE RELIEVED OF
STRESS AT ANCHOREAGES ONCE NEW WALLS ARE POURED AND SUPPORTED LATERALLY IN A
PERMANET MANNER BY THE NEW CONSTRUCTION.
PROVIDE 2" NORMINAL THICKNESS FULL DEPTH SOLID HORIZONTAL BLOCKING FOR JOISTS AND RAFTER AT
ENDS AT SUPPORTTS. SOLID BLOCKING MAY BE OMITTED WHEN JOISTS FRAME INTO A SUPPORTING
HEADERS. LAP JOIST FRAMING FROM OPPOSITE SIDES OVER A BEAM, GIRDER OR WALL 4" MINIMUM OR BUTT
JOISTS END TO END AND SCAP WITH METAL STRAPS OVER OR WOOBD BLOCKS. USE APPROVED METAL HANGERS
TO SUPPORT JOISTS FRAMING INTO THE SIDES OF WOOD BEAMS. JOIST CARRYING PARTITION PARALLEL TO
JOISTS SHALL BE DOUBLED.
#14 AND #18 BARS: 1 1/2"
#11 BAR AND SMALLER: 3/4" (UNLESS NOTED OTHERWISE)
WELDED WIRE MESH SHALL BE PLACE AT MID- DEPTH OF SLAB OR 2 INCHES BELOW THE TOP SURFACE,
WHICHEVER IS LESS.
LUMBER AND WOOD PRODUCTS
LUMBER SHALL COMPLY WITH THE RQUIREMENTS OF THE AMERICAN FOREST & PAPER ASSOCIATION'S
"NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION (NDS)".
LUMBER SHALL BE SOUTHERN PINE NO. 2 OR APPROVED EQUIVALENT WITH ALL ALLOWABLE DESIGN VALUES
GREATER THAN OR EQUAL TO SOUTHERN PINE NO. 2 AS LISTED IN THE NDS. LUMBER SHALL HAVE A
MAXIMUM MOISTURE CONTENT OF 19% AT DELIVERY:.
PROVIDE CORNERS BARS AT JUNCTIONS OF CONCRETE WALLS. GRADE BEAMS AND WALL FOOTINGS AND LAP
WITH WALL REINFORCING AS SHOWN IN TYPICAL DETAILS.SIZE AND SPACING OF CORNER BARS TO BE SAME AS
HORIZONTAL WALL REINFORCING, UNLESS SHOWN OTHERWISE. WHERE CONTNUOUS BARS ARE CALLED FOR,
THEY SHALL RUN CONTINUOSLY AROUND CORNERS AND LAPPED AS NECESSARY.PROVIDE STANDARD HOOKS AT
DISCONTINUOUS ENDS. TENSION COMPRESSION LAP SPLICES SHALL NOT BE LESS THAN THE SPLICE
LENGTHS AS GIVEN IN ACI-318. GENERALLY LAP TOP BARS AT MID SPAN AND BOTTOM BARS AT SUPPORTS.
PROVIDE PLACING ACCESSORIES IN ACCORDANCE WITH ACI RECOMMENDATIONS.
MISCELLANEOUS STEEL
MISCELLANEOUS STRUCTURAL STEEL SHALL CONFORM TO THE LATEST EDITION OF THE AISC " SPECIFICATION FOR
THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS" AND SHALL BE ASTM A36.
BOLTS SHALL BE HIGH STRENGTH 3/4" DIAMETER CONFORMING TO ASTM A325. WELDING SHALL BE DONE
ONLY BY CERTIFIED WELDERS. WELD IN ACCORDANCE WITH THE AWA "STANDARD CODE FOR ARC AND GAS
WELDING IN BUILDING CONSTRUCTION". STRUCTURAL STEEL SURFACES CAST INTO CONCRETE SHALL BE
UNPAINTED.
SUBMIT STRUCTURAL STEEL SHOP DRAWINGS SHOWING COMPLETE DIMENSIONS AND DETAILS FOR APPROVAL
PRIOR TO FABRICATION. THE STRUCTURAL STEEL SUBCONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING.
VERIFICTION, AND FOR COORDINATION OF DIMENSIONS AND DETAILS WITH THE STRUCTURAL AND OTHER
PORTIONS OF THE CONTRACT DRAWINGS. THE STRUCTURAL CONTRACT DRAWINGS SHALL NOT BE REPRODUCED
AS SHOP DRAWINGS UNLESS THE STRUCTURAL ENGINEER'S APPROVAL IS OBTAINED IN WRITING.
WOOD STRUCTURAL PANELS (PLYWOOD OR ORIENTED STRAND BOARD) SHALL COMPLY WITH THE AMERICAN
PLYWOOD ASOCIATION'S "PLYWOOD DESIGN SPECIFICATION" AND THE DEPARTMENT OF COMMERCE'S
PERFORMANCE STANDARD (PS) 1 OR 2.
HEADER WILL BE FASTEN TO POSTS WITH METAL CAPS SUCH AS AC AND ACE OR HH BY SIMPSON OR
APPROVED EQUAL. ALTERNATELY WOOD POSTS MAYBE INSTALLED TIGHT UNDER WOOD BEAMS AND CUT SO
THAT THE BEAM BEARING IS UNIFORM ON THE POST AND METAL CAP ELIMINATED.
PRESERVATIVE-TREATED WOOD SHALL CONFORM TO THE APPLICABLE STANDARD OF THE AWPA.
ROOF TRUSS SHALL HAVE HURRICANE TIES SUCH AS H2.5 BY SIMPSON OR APPROVED EQUAL. GIRDER
TRUSSES SHALL HAVE TWO TIES AT EACH END.
STUD BEARING WALLS AND EXTERIOR STUD WALLS SHALL HAVE CONTINUOS HORIZONTAL WOOD BLOCKING AT
MID-HEIGHT BETWEEN FLOOR AND ROOF LEVELS. STUDS AND POSTS SHALL BE ONE CONTINUOUS MEMBER
BETWEEN BASE PLATE AND DOUBLE TOP PLATES BETWEEN FLOOR LEVELS AND BETWEEN FLOOR LEVEL AND
ROOF DIAPHRAGMS. ALL DOUBLE STUDS SHALL BE NAILED TO EACH OTHER AT 8 INCH MAXIMUM SPACING
FULL- HEIGHT. EXTERIOR BUILDING CORNERS IN STUD WALLS SHALL BE BRACED WITH DIAGONALLY PLACED
METAL STRAPS OR PLYWOOD SHEATHING NAILED OR SCREWED TO STUDS.
ALL DOUBLE (OR MORE) RAFTERS, JOISTS, AND BEAMS SHALL BE MECHANICALLY FASTENED OR NAILED TO
EACH OTHER TO ACT AS A SINGLE UNIT WHEN LOADED. MULTIPLE-PLY MEMBERS SHALL BE NAILED TOGETHER
WITH TWO HORIZONTAL ROWS OF 20d NAILS SPACED 32" ON CENTER, ONE ROW NEAR THE TOP EDGE AND
ONE ROW NEAR THE BOTTOM EDGE, AT A MINIMUM.
WOOD COLUMNS AND POST SHALL BE FRAMED TO TRUE END BEARINGS. AND SHALL BE POSITIVELY
ANCHORED TO FOUNDATION WITH APPROVED POST BASES TO SUPPORT COLUMN OR SECURELY IN
POSITION AND PROTECT BASE FROM DETERIORATION. COLUMNS AND POST OF TREATED WOOD MAY BE PLACED
DIRECTLY ON CONCRETE OR MASONRY. USE TREATED WOOD FOR ALL FLOOR JOISTS AND BEAMS WHICH ARE
EXPOSED OR WITHINN 18" OF THE GROUIND, OR ;IN PERMANENT; CONTACT WITH; EARTH;.}
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
ALL HARDWARE ATTACHMENTS AND BEAMS IN THE TRUSS SYSTEM SHALL BE SUPPLIED BY THE TRUSS
MANUFACTURER.
OT SU
BALCONY POSTS SHALL HAVE POST BASES SUCH AS ABA OR ABU BY SIMPSON OR SIMILAR.
PROVIDE COLUMN CAPS, WHERE BEAMS FRAME TO COLUMNS, SUCH AS CC/ECC BY SIMPSON OR APPROVED
EQUAL. CAPS SHALL HAVE ENOUGH LENGTH TO PROVIDE A MINIMUM OF 4" OF BEARING LENGTH FOR EACH
BEAM.
ALLOWABLE BENDING STRESS, Fb = 2,200 PSI
ALLOWABLE SHEAR STRESS, Fv = 285 PSI
ALLOWABLE COMPRESSION STRESS STERSS PERPENDICULAR TO GRAIN, Fcp = 750 PSI
MODULUS OF ELASTICITY, E = 1,800,000 PSL
PARALLEL STRAND LUMBER (PSL) SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES;
ALLOWABLE BENDING STRESS, Fb = 2,400 PSI
ALLOWABLE COMPRESSION STRESS PARALLEL TO GRAIN, Fc = 2,500 PSLI
MODULUS OF ELASTICITY, E = 1,800,000 PSI
INFORMALCRAFT LLC
HARDWARE ATTACHMENT
GLUED LAMINATED TIMBERS SHALL BE MANUFACTURED AND IDENTIFIED AS REQUIRED IN ANSI/AITC A 190.1-92
"AMERICAN NATIONAL STANDARD, STRUCTURAL GLUED LAMINATED TIMBER" AND ASTM D 3737. GLUED
LAMINATED BEAMS SHALL BE VISUALLY GRADED SOUTHERN PINE, COMBINATION 16F-V3 OR GREATER FOR
BEAMS AND COMBINATION 47 OR GREATER COLUMNS.
STRUCTURAL COMPOSITE LUMBER (LVL AND PSL) SHALL HAVE STRUCTURAL CAPACITIES ESTABLISHED AND
MONITORED IN ACCORDANCE WITH ASTM D 5456. LAMINATED VENEER LUMBER (LVL) SHALL HAVE THE
FOLLOWING MINIMUM PROPERTIESS:
KEY PLAN
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
PROVIDE TWO METAL STRAPS AND BEAM/GIRDER TRUSSES AT THE TOP FLOOR. USE LTS18 OR
TS18 BY SIMPSON OR APPROVED EQUAL.
JOIST/.BEAM HANGERS
JOIST/BEAM HANGERS SHALL HAVE LOAD CARRYING CAPACITY NOT LESS THAN THE SHEAR CAPACITY OF THE
JOIST/BEAM BEING CARRIED BY THE HANGER.
MASONRY
CONCRETE BLOCK USED IN WALLS CONFORM TO ASTM C-90, f'm=1500 PSI. BRICK SHALL CONFORM
TO ASTM C62 AND ASTM C216, AS APPLICABLE. MORTAR FOR MASONRY SHALL CONFORM TO ASTM C270,
TYPE N. (EXCEPT THAT TYPE S MORTAR SHALL BE USED AT LOAD BEARING MASONRY STIAR AND ELEVATOR
WALLS).
PROJECT No:
REINFORCED MASONRY WALLS SHALL BE BUILT SO THAT ALL CELLS LINE UP. WEBS OF UNITS TO BE
REINFORCED SHALL BE FILLED WITH CEMENT GROUT OR PEA-GRAVEL CONCRETE AND UNITS SHALL HAVE FULL
MORTAR COVERAGE.
DRAWING TITLE:
GENERAL NOTES
PROVIDE CONTINUOUS HORIZONTAL JOINT REINFORCING, "DUR-0-WALL" OR EQUIVALENT, IN ALL MASONRY
WALLS AT 16" O.C. VERTICALLY AT MORTAR JOINTS ABOVE AND BELOW AN OPENING, AND AT HORIZONTAL
JOINTS WITH WALL TIES TO STEEL BEAMS. WHERE WALLS ABUT EACH OTHER AND AT OUTSIDE CORNERS,
PROVIDE PREFABRICATED TEE-TYPE AND CORNER TRUSS TIES. DISCONTINUE JOINT REINFORCING AT CONTROL
JOINTS. PROVIDE ADJUSTABLE MASONRY ANCHORS TO BEAMS. COLUMNS (AND WALLS) ABUTTING MASONRY AT
16" O.C. HORIZONTALLY OR VERTICALLY.
PROVIDE KEYED VERTICAL CONTROL JOINTS IN MASONRY WALLS AS PER ARCHITECTURAL DRAWINGS, BUT NOT
TO EXCEED 40 FT. O.C.
MASONRY FACADE SUSPENDED FROM OR SUPPORTED ON CONCRETE SLAB AND BEAMS SHALL NOT BE ERECTED
UNTIL PERMANENT ALIGNMENT AND ANCHORAGE OF SHELF ANGLES SUSPENDED HARDWARE IS COMPLETED,
ALL TEMPORARY AND PERMANENT BRACING (WHERE REQUIRED) IS INSTALLED AND ALL SHORES AND RESHORES
ARE REMOVED.
MASONRY ANCHORS
SCALE:
SPANDREL BEAMS AND COLUMNS SHALL BE ANCHORED TO MASONRY WALLS WITH
DUR -0-WALL, INC. #D/A 913 3/16"x1 1/4" GALV. MASONRY ANCHORS, AND SHALL BE
SUPPLIED WITH #D/A 901 11 GA.. SHOP PAINTED, WELDED STEEL CHANNELS OR EQUIVALENT.
COLUMNS OPPOSITE CONTROL JOINTS SHALL ANCHOR ON EACH SIDE OF THE CONTROL
JOINT AS SHOWN IN THE TYPICAL DETAILS. MASONRY ANCHORS AT OPENING WEB JOIST
SHALL BE DUR-0-WAL, INC. # D/A 610 1/4"x1 1/4" GALV. ANCHORS OR EQUIVALENT.
GROUT MASONRY CELLS SOLID AT ANCHOR LOCATIONS.
1/4" = 1'-0"
CN
CONSTRUCTION DOCUMENTS
MAY 17, 2015
STANDARD EROSION CONTROL NOTES
SEDIMENT AND EROSION CONTROL MEASURES SHALL BE INSTALLED BEFORE
THE START OF ANY EXCAVATION AND/OR CONSTRUCTION AS PER STANDARDS
AND SPECIFICATIONS FOR SOIL EROSION AND SEDIMENT CONTROL FOR THE
DISTRICT OF COLUMBIA. IF AN ON-SITE INSPECTION REVEALS FURTHER
EROSION CONTROL MEASURES ARE NECESSARY, THE SAME SHALL BE
PROVIDED.
ALL 2.
DEBRIS IS TO BE REMOVED FROM SITE.
ALLEY
3. AND/OR STREETS/SIDEWALKS SHALL BE SWEPT CLEAN AT ALL TIMES
DURING DEMOLITION, EXCAVATION AND CONSTRUCTION.
ALL 4.
CATCH BASINS AND DRAIN AREAS SHALL BE PROTECTED DURING
EXCAVATION AND CONSTRUCTION.
5. CATCH BASINS OR DRAINS BECOME CLOGGED AS A RESULT OF
IF ANY
DEMOLITION, EXCAVATION OR CONSTRUCTION THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ITS CLEANING.
6. SEDIMENT TRAP/SEDIMENT TANK HAS REACHED 67% CAPACITY,
WHEN
CLEANING OUT OF SAME IS REQUIRED.
ANY7.STOCKPILING, REGARDLESS OF LOCATION SHALL BE STABILIZED AND
COVERED WITH PLASTIC OR CANVAS, AFTER ITS ESTABLISHMENT AND FOR
DURATION OF THE PROJECT.
AFTER
8. RAZING OR DEMOLITION, THERE IS THE NEED FOR GROUNDCOVER TO
PREVENT EROSION AND SEDIMENT RUNOFF FROM OCCURRING. SUCH AS
APPLYING SEED, SOD, PAVE, BRICKBAT OR MULCH, ETC.
THE9.SITE'S APPROVAL LETTER, APPROVED EROSION AND SEDIMENT CONTROL
PLANS, DAILY LOG BOOKS AND TEST REPORTS SHALL BE AVAILABLE AT THE
SITE FOR INSPECTION BY AUTHORIZED OFFICIALS OF DCRA RESPONSIBLE FOR
PROJECT.
TEMPORARY
SEDIMENT CONTROL DEVICES MAY BE REMOVED, WITH
10.
PERMISSION OF DCRA INSPECTOR, WITHIN THIRTY (30) CALENDAR DAYS
FOLLOWING ESTABLISHMENT OF PERMANENT STABILIZATION IN ALL
PERMANENT AND TEMPORARY SEEDING, SODDING AND MULCHING
I.
SITE PREPARATION
PERMANENT OR TEMPORARY STABILIZATION SHALL BE COMPLETED WITHIN (A)
SEVEN CALENDAR DAYS AS TO THE SURFACE OF ALL SEDIMENT CONTROL
PRACTICES SUCH AS DIVERSIONS, GRADE STABILIZATION STRUCTURES, BERMS,
DIKES, GRASSED WATERWAYS, SEDIMENT BASINS, PERIMETER SLOPES, AND ALL
SLOPES GREATER THAN 3 HORIZONTAL TO 1 VERTICAL (3:1) AND (B) FOURTEEN
DAYS AS TO ALL OTHER DISTURBED OR GRADED AREAS ON THE PROJECT SITE.
II. SEEDBED PREPARATION AND SEEDING APPLICATION
THE TOP LAYER OF SOIL SHALL BE LOOSENED, LIMED AND FERTILIZED BY
RAKING, DISCING OR HARROWING OR OTHER ACCEPTABLE MEANS BEFORE
SEEDING. FLAT AREAS AND SLOPES UP TO 3 TO 1 GRADE SHALL BE LOOSE AND
FRIABLE TO A DEPTH OF AT LEAST 3 INCHES SLOPES STEEPER THAN
3 TO 1 SHALL HAVE THE TOP 1-3 INCHES OF SOIL LOOSE
AND FRIABLE BEFORE SEEDING. FLAT AREAS AND SLOPES UP TO 3 TO 1 GRADE
SHALL BE LOOSE AND FRIABLE TO A DEPTH OF AT LEAST 3 INCHES
SLOPES STEEPER THAN 3 TO 1 SHALL HAVE THE TOP 1-3 INCHES
OF SOIL LOOSE AND FRIABLE BEFORE SEEDING.
APPLY SEED UNIFORMLY WITH A CYCLONE SEEDER, DRILL CULTIPACKER,SEEDER OR
HYDROSEEDER ON A FIRM MOIST SEEDBED.
III. SOIL AMENDMENTS
LIME AND FERTILIZE ACCORDING TO SOIL TESTS. IN LIEU OF SOIL TEST APPLY
THE FOLLOWING:
DOLOMITIC
LIMESTONE
2 TONS PER ACRE OR 92 LBS/1,000
(PERMANENT AND SODDING SQ.FT.)
FERTILIZER
1 TON PER ACRE OR 46 LB/1,000
(TEMPORARY) 10-10-10 OR EQUIVALENT AT
1,000 LBS PER ACRE OR 23 LBS PER
1,000 SQ. FT. (PERMANENT AND SODDING)
USED TEMPORARILY FOR SEDIMENT CONTROL SHALL BE CONVERTED TO THE
PERMANENT CONFIGURATION WITHIN THIS TIME PERIOD AS WELL.
CONTRIBUTORY DRAINAGE AREAS. STORMWATER MANAGEMENT STRUCTURES
SEED:
SEDIMENT REMOVED FROM TRAPS (AND BASINS) SHALL BE PLACED AND
STABILIZED IN APPROVED AREAS, BUT NOT WITHIN A FLOODPLAIN, WETLAND
OR TREE-SAVE AREA. WHEN PUMPING SEDIMENT LADEN WATER, THE
DISCHARGE MUST BE DIRECTED TO A SEDIMENT TRAPPING DEVICE PRIOR TO
RELEASE FROM THE SITE. A SUMP PIT MAY BE USED IF SEDIMENT TRAPS
THEMSELVES ARE BEING PUMPED OUT.
DATES:
LEAST 42 INCHES HIGH, HAVE POSTS SPACED NO FARTHER
APART THAN 8 FEET, HAVE MESH OPENINGS NO GREATER THAN
2 INCHES IN WIDTH AND 4 INCHES IN HEIGHT WITH
A MINIMUM OF 14 GAUGE WIRE. SAFETY FENCE MUST BE MAINTAINED AND
IN GOOD CONDITION AT ALL TIMES.
SEDIMENT CONTROL FOR UTILITY CONSTRUCTION FOR AREAS OUTSIDE OF
DESIGNED CONTROLS OR AS DIRECTED BY ENGINEER OR DCRA INSPECTOR:
(A) CALL "MISS UTILITY" AT- HOURS PRIOR TO THE
START OF WORK.
(B) EXCAVATED TRENCH MATERIAL SHALL BE PLACED ON THE HIGH SIDE OF
THE TRENCH.
(C) TRENCHES FOR UTILITY INSTALLATION SHALL BE BACKFILLED,
COMPACTED AND STABILIZED AT THE END OF EACH WORKING DAY. NO
MORE TRENCHES SHALL BE OPENED THAN CAN BE COMPLETED THE SAME
DAY, UNLESS;
(D) TEMPORARY SILT FENCE SHALL BE PLACED IMMEDIATELY DOWNSTREAM
OF ANY DISTURBED AREA INTENDED TO REMAIN DISTURBED FOR MORE
THAN ONE DAY.
OFF-SITE SPOIL, WASTE, OR BORROW AREAS IN THE DISTRICT OF COLUMBIA OR
ON FEDERAL PROPERTY MUST HAVE PRIOR APPROVAL BY DCRA. ALL WASTE
AN BORROW AREAS OFF-SITE MUST BE PROTECTED BY SEDIMENT CONTROL
MEASURES AND STABILIZED IN ACCORDANCE WITH THE ORDINANCES AND
REGULATIONS OF THE JURISDICATION WHERE THE SPOIL, WASTE, OR BORROW
AREA IS LOCATED/STABILIZED.
DATE
ISSUE
LIQUID MULCH BINDER SHALL BE RAPID CURING CUTBACK ASPHALT APPLIED
AT A RATE OF 200 GAL/ACRE OR 5 GAL. PER 1,000 SQ. FT.
SLOPES 8 FEET OR MORE HIGH USE 348 GAL./ACRE
OR 8 GAL./1,000 SQ. FT.
VII. SODDING
CLASS OF TURFGRASS SOD SHALL BE MARYLAND OR VIRGINIA STATE CERTIFIED
OR MARYLAND OR VIRGINIA STATE APPROVED SOD. SOD SHALL BE
HARVESTED, DELIVERED AND INSTALLED WITHIN A PERIOD OF 36 HOURS. SOD
IS TO BE LAID WITH THE LONG EDGES PARALLEL TO THE CONTOUR WITH
STAGGERED JOINTS WITH ALL ENDS TIGHTLY ABUTTING AND NOT
OVERLAPPING. SOD SHALL BE ROLLED AND THOROUGHLY WATERED WITHIN
EIGHT HOURS OF INSTALLATION. DAILY WATERING TO MAINTAIN 4 INCH
DEPTH OF MOISTURE FOR THE FIRST WEEK IS REQUIRED IN THE ABSENCE OF
RAINFALL. SOD IS NOT TO BE APPLIED ON FROZEN GROUND.
IX. MAINTENANCE
0'
A. IRRIGATION - WHEN SOIL MOISTURE BECOMES DEFICIENT, IRRIGATE TO
PREVENT LOSS OF STAND OF PROTECTIVE VEGETATION.
B. REPAIRS - IF STAND IS INADEQUATE FOR EROSION CONTROL, OVERSEED AND
FERTILIZE USING HALF OF THE RATES ORIGINALLY APPLIED. IF STAND IS OVER
60% DAMAGED, REESTABLISH FOLLOWING ORIGINAL RATES AND PROCEDURES.
8'
16'
32'
SCALE: 1/4"= 1'-0"
NOTE: USE OF THIS INFORMATION DOES NOT PRECLUDE MEETING ALL OF THE
REQUIREMENTS OF THE 1987 DISTRICT OF COLUMBIA DEPARTMENT OF
CONSUMER AND REGULATORY AFFAIRS STANDARDS AND SPECIFICATIONS FOR
SOIL EROSION AND SEDIMENT CONTROL VEGETATIVE PRACTICES.
STANDARD EROSION AND SEDIMENT CONTROL MEASURES AND SEQUENCE
IV. SEDIMENT CONTROL PRACTICES, SEEDING
VEGETATIVE
STABILIZATION SHALL BE PERFORMED IN ACCORDANCE WITH THE
11.
DCRA STANDARDS AND SPECIFICATIONS FOR SOIL EROSION AND SEDIMENT
CONTROL. REFER TO APPROPRIATE SPECIFICATIONS FOR TEMPORARY SEEDING,
PERMANENT SEEDING, MULCHING, SODDING AND GROUND COVERS.
WHERE DEEMED APPROPRIATE BY THE ENGINEER OR INSPECTOR, SEDIMENT
BASINS AND TRAPS MAY NEED TO BE SURROUNDED WITH AN APPROVED
SAFETY FENCE. THE FENCE MUST CONFORM TO LOCAL ORDINANCES AND
REGULATIONS. THE DEVELOPER OR OWNER SHALL CHECK WITH LOCAL
GUILDING OFFICIALS ON APPLICABLE SAFETY REQUIREMENTS. WHERE SAFETY
FENCE IS DEEMED APPROPRIATE AND LOCAL ORDINANCES DO NOT SPECIFY
FENCING SIZES AND TYPES, THE FOLLOWING SHALL BE USED AS A MINIMUM
STANDARD: THE SAFETY FENCE MUST BE MADE OF WELDED WIRE AND AT
NO.
VEGETATIVE STABILIZATION
V.
"KENTUCKY 31" TALL FESCUE 60 LBS/ACRE OR 1.38 LBS/1,000
SQ. FT AND ITALIAN (ANNUAL) RYEGRASS 40 LBS/ACRE
OR .91 LBS/1,000 SQ. FT.
1/2 - 10/31
5/1 - 8/14 WITH IRRIGATION.
TEMPORARY SEEDING: PER GROWING SEASON
SEED:
DATES:
SEED:
DATES:
1.
ALL EROSION AND SEDIMENT CONTROL MEASURES SHALL BE PLACED PRIOR TO
OR AS THE FIRST STEP IN GRADING.
2.
PROVIDE TEMPORARY STONE CONSTRUCTION ENTRANCE WHERE SHOWN.
PROVIDE WATER SOURCE AND HOSE TO CLEAN ALL EQUIPMENT LEAVING SITE.
3.
INSTALL SILT FENCE AS SHOWN.
4.
NO DISTURBED AREA WILL BE DENUDED FOR MORE THAN 7 CALENDAR DAYS.
INSTALL THE NECESSARY TEMPORARY OR PERMANENT VEGETATIVE
STABILIZATION MEASURES TO ACHIEVE ADEQUATE EROSION AND SEDIMENT
ITALIAN OR PERENNIAL RYEGRASS 40 LBS/ACRE
OR .92 LBS/1,000 SQ. FT.
2/1 - 4/30 AND 8/15 - 11/30
CONTROL.
5.
ALL CONSTRUCTION TO BE INSPECTED DAILY BY THE CONTRACTOR, AND ANY
DAMAGED SILTATION OR EROSION CONTROL DEVICES OR MEASURES WILL BE
REPAIRED AT THE CLOSE OF THE DAY.
MILLET 40 LBS/ACRE OR
0.92 LBS/1,000 SQ. FT.
5/1 - 8/14
SEAL
6.
ALL SILT FENCE TO BE MAINTAINED IN WORKING CONDITION.
TO BE MAINTAINED IN WORKING CONDITION.
7.
STABILIZED CONSTRUCTION ENTRANCES TO BE PERIODICALLY SUPPLEMENTED
WITH ADDITIONAL STONE AS NEEDED.
8.
CONTROLS CAN BE REMOVED AFTER THEIR CONTRIBUTING BASINS HAVE BEEN
PERMANENTLY STABILIZED, AND APPROVAL OF INSPECTOR IS OBTAINED.
KEY PLAN
VI. PERMANENT SEEDING
A. RESIDENTIAL AND HIGH MAINTENANCE AREAS
1. KENTUCKY BLUEGRASS, "PLUSH", "BIRKA", "PARADE", "VANTAGE",
"COLUMBIA", "MERION", "ADELPHI", "SOUTH DAKOTA", "KENBLUE". ANY THREE
VARIETIES AT 30 LBS. TO MAKE 90 LBS/ACRE OR 2 LBS/1,000
SQ.FT. AND RED FESCUE - "PENNLAWN" OR JAMESTOWN
10 LBS/1000 SQ.FT.
DATES:
2/1 - 4/30 AND 8/15 - 10/31.
2. "KENTUCKY 31" TALL FESCUE
220-260 LBS/ACRE OR
5-6 LBS/1,000 SQ. FT.
DATES:
2/1 - 10/31
5/1 - 8/14 IRRIGATION REQUIRED.
B. LOW MAINTENANCE AND MINING AREAS
"KENTUCKY 31" TALL FESCUE
40 LBS/ACRE OR 0.92 LBS/1,000 SQ. FT.
AND "INTERSTATE" SERICEA LESPEDEZA
(INOCULATED)20 LBS/ACRE OR 0.46 LBS/1,000 SQ. FT.
DATES: 2/1 - 4/30 AND 8/15 - 10/31
C. GENERAL AND LARGE ACREAGE
"KENTUCKY 31" TALL FESCUE
60 LBS./ACRE OR 1.38 LBS/1,000 SQ.FT.(0.5 kg/100 sq.m)
VII. MULCHING
ALL SEEDINGS REQUIRE MULCHING. USE MULCH ONLY DURING NON-SEEDING
DATES UNTIL SEEDING CAN BE DONE.
MULCH SHALL BE UNROTTED, UNCHOPPED SMALL GRAIN STRAW APPLIED AT A
RATE OF 1 TO 2 TONS/ACRE OR 70-90 LBS/1,000
SQ.FT. (2 BALES) MULCH MATERIALS SHALL BE
RELATIVELY FREE OF ALL KINDS OF WEED BEDS AND SHALL BE FREE OF PROHIBITED
NOXIOUS WEEDS. SPREAD MULCH UNIFORMLY MECHANICALLY OR BY HAND.
MULCH ANCHORING SHALL BE ACCOMPLISHED IMMEDIATELY AFTER MULCH PLACEMENT
TO MINIMIZE LOSS BY WIND OR WATER. THIS MAY BE DONE BY MULCH NETTINGS,
MULCH ANCHORING TOOL, PEG AND TWIN OR LIQUID MULCH BINDERS.
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
GENERAL NOTES
Owner:
1. ALL WORK AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE
V.A. CODES, REGULATIONS AND STANDARDS
2. CONTRACTOR SHALL OBTAIN ALL REQURED V.A PERMITS, INSPECTIONS
AND APPROVALS PRIOR TO STARTING THE WORK.
3. CONTRACTOR SHALL MAINTAIN THE WORK AREA IN A SAFE MANNER AT
ALL TIMES. ALL V.A. AND OSHA SAFTEY STANDARDS AND MEASURES
SHALL BE EXCERCISED AT ALL TIMES DURING THE DURATION OF THE
CONSTRUCTION.
4. THE SITE WORK AREA SHALL BE RESTRICTTED TO AUTHORIZED
PERSONS ONLY, AT ALL TIMES DURING THE DURATION OF THE
CONSTRUCTION.
5. THE CONTRACTOR SHALL BE HELD FULLY LIABLE FOR DAMAGE TO
PUBLIC SPACE , UTILITIES AND THE ADJOINING PROPERTIES.
6. THE CONTRACTOR SHALL CONTACT ALL REQUIRED UTILITY COMPANIES
AND VERIFY THE DISCONNECTING OF NATURAL GAS LINES, WATERLINES,
AND ELECTRIC LINES PRIOR TO DIGGING.
PROJECT ID# INC-010-DRG-001
7. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, GRADES, ELEVATIONS,
UTILITIES, EXISTING AND PROPOSED INSTALLATIONS AND SCOPE OF
WORK SCHEDULED AT THE SITE.
DRAWING TITLE:
8. INSTALL ALL EROSION AND SEDIMENT CONTROL DEVICES AND
MEASURES DESIGNATED BY THE NUMBERED ITEMS AND NOTES
DESIGNATED HEREIN ON THIS SHEET, AT LOCATIONS SHOWN ON THE
PLAN. EROSION AND SEDIMENT CONTROL DEVICES SHOWN ON THIS
SHEET WITHOUT NUMBERS ARE NOT REQUIRED TO BE INSTALLED AT
THIS SITE. ALL NOTES AND SYMBOLS SHALL BE MADE APPLICABLE FOR
THIS PROJECT.
PROJECT No:
DRAWING TITLE:
EROSION AND
SEDIMENT CONTROL
NOTES AND SITE PLAN
LEGEND
STABILIZED CONSTRUCTION ENTRANCE
EXISTING CONTOUR
SILT FENCE
CONCRETE PAVED AREA
LIMIT OF DISTURBANCE
SCALE:
SEWER LINE
WATER LINE
CLEAN OUT
SILT FENCE & LIMIT OF DISTURBANCE
(ENDING AT SAME LINE)
PROPOSED CONTOUR
INV.=76.75
INVERT ELEVATION
1/4" = 1'-0"
C-1
CONSTRUCTION DOCUMENTS
MAY 17, 2015
NO.
SILT FENCE DETAIL
STABILIZED CONSTRUCTION ENTRANCE
DETAIL
TO CENTER
STREET SWEEPING
ISSUE
CONCRETE BLOCK
CURB INLET
GRAVEL FILTER
36" MIN. LENGTH FENCE POST,
DRIVEN A MIN.OF 16"(406 MM)INTO
GROUND.
10 MAXIMUM CENTER
STRING BINDER
6
4
STRAW BALE DIKE DETAIL
DATE
1. STREETS WITHIN ONE MILE (1.6km) SHALL BE INSPECTED DAILY, ANY
WIRE SCREEN
DROPPED SOIL, DUST AND/OR DEBRIS SHALL BE REMOVED.
CURB GUTTER
UNDISTURBED
GROUND
FLOW
16" MIN. HEIGHT OF
GEOTEXTILE CLASS F
FLOW
EXIST. PAVEMENT
EARTH FILL
PIPE AS NECESSARY
** GEOTEXTILE CLASS 'C'
OR BETTER
FLOW
SBD
3. ROADS SHALL BE SWEPT ON A WEEKLY BASIS (MINIMUM) DURING ALL ON
CURB INLET SEDIMENT FILTER
(NOT TO SCALE)
1. TWO CONCRETE BLOCKS SHALL BE PLACED ON THEIR SIDES ABUTTING THE CURB AT
EITHER SIDE OF THE INLET OPENING.
2. A 2 INCH BY 4 INCH STUD SHALL BE CUT AND PLACED THROUGH THE OUTER HOLES
OF EACH SPACER BLOCK TO HELP KEEP THE FRON BLOCKS IN PLACE.
FENCE POST SECTION
MIN. 20"
GROUND
UNDISTURBED
GROUND
FILTER
CLOTH
FLOW
EMBED GEOTEXTILE CLASS F
A MIN. OF 8"
VERTICALLY INTO THE GROUND
ENTRANCE BALES A MINIMUM
OF 4" INTO
THE GROUND
2X4 WOOD STUD
HAUL ROUTES.
36" MIN. FENCE
POST LENGTH
BOUND BALES
PLACED ON
CONTOUR
INLET
WIRE SCREEN
AND OFF SITE HAULING OPERATIONS FOR UP TO ONE MILE (1.61km) ALONG
PROFILE
ANGLE FIRST STAKE TOWARD THE
PREVIOUSLY PLACED BALE
SILTED WATER
TOTAL DUST AND DIRT ON PAVED SURFACES.
MIN.6" OF 2"-3"
AGGREGATE OVER
LENGHT AND WIDTH
OF STRUCTURE
EXISTING GROUND
PERSPECTIVE VIEW
2. VACUUM TYPE STREET CLEANER SHALL BE USED TO EFFECTIVELY REMOVE
5:1
5:1
WOVEN WIRE FENCE
BEDDING DETAIL
MOUNTABLE BERM
(6" MIN)
50' MIN.
8" MIN. DEPTH IN
GROUND
4"
VERTICAL FACE
OVERFLOW
3'
10'
MIN.WIDTH
TOP VIEW
5. TWO TO THREE INCH STONE SHALL BE FILED AGAINST THE WIRE TO THE TIP OF THE BARRIER
AS SHOWN.
EXISTING
PAVEMENT
10' MIN.
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
6. IF THE STONE FILTER BECOMES CLOGGED WITH SEDIMENT SO THAT IT NO LONGER
ADEQUATELY PERFORMS ITS FUNCTION, THE STONE MUST BE PULLED AWAY FROM THE
BLOCKS, CLEANED AND REPLACED.
10' MIN.
STANDARD SYMBOL
STANDARD SYMBOL
SF
4. WIRE MESH SHALL BE PLACED OVER THE OUTSIDE VERTICAL FACE (WEBBING) OF THE
CONCRETE BLOCKS TO PREVENT STONE FROM BEING WASHED THROUGH THE HOLES IN THE
BLOCKS. CHICKEN WIRE OR HARDWARE BLOCK WITH 21 INCH OPENINGS SHALL BE USED.
10' MIN.
FENCE POST DRIVEN A
MIN. OF 16"
INTO THE GROUND
CROSS SECTION
3. CONCRETE BLOCKS SHALL BE PLACED ON THEIR SIDES SCROSS THE FRONT OF THE
INLES AND ABUTTING THE SPACER BLOCKS AS ILLUSTRATED.
50'MIN.
LENGTH
PLAN VIEW
SCE
POST
2 REBARS OR 2" x 2"
DRIVEN 12" TO 18"
INTO THE GROUND
STAKES ARE TO BE DRIVEN FLUSH
WITH THE TOP OF THE BALES
FLOW
UNDISTURBED
GROUND
SECTION B
STAPLE
SECTION A
STAPLE
LIST OF STANDARD SYMBOLS
JOINING TWO ADJACENT SILT
FENCE SECTIONS
ANCHORING DETAIL
EROSION AND SEDIMENT CONTROL
MEASURES AND SEQUENCE
4
SILT FENCE
STANDARDS AND SPECIFICATIONS
FOR DUST CONTROL
CONSTRUCTION SPECIFICATION
SILT FENCE DESIGN CRITERIA
1. BALES SHALL BE PLACED AT THE TOE OF A SLOPE, ON THE
CONTOUR, AND IN A ROW WITH THE ENDS OF EACH BALE TIGHTLY
ABUTTING THE ADJACENT BALES.
SLOPE STEEPNESS
2. EACH BALE SHALL BE ENTRENCHED IN THE SOIL A MINIMUM OF 4"
AND PLACED SO THE BINDINGS ARE HORIZONTAL.
3. BALES SHALL BE SECURELY ANCHORED IN PLACE BY EITHER TWO
STAKES OR RE-BARS DRIVEN THROUGH THE BALE 12" TO 18" INTO
THE GROUND. THE FIRST STAKE IN EACH BALE SHALL BE DRIVEN
TOWARD THE PREVIOUSLY LAID BALE AT AN ANGLE TO FORCE THE BALES
TOGETHER. STAKES SHALL BE DRIVEN FLUSH WITH THE TOP OF THE
BALE.
(MAXIMUM)
SLOPE LENGTH
(MAXIMUM)
SILT FENCE LENGTH
FLATTER THAN 50:1
50:1 TO 10:1
10:1 TO 5:1
UNLIMITED
125 FT.
100 FT.
UNLIMITED
1,000 FT.
750 FT.
5:1 TO 3:1
60 FT.
500 FT.
3:1 TO 2:1
40 FT.
250 FT.
2:1 AND STEEPER
20 FT.
125 FT.
NOTE: IN AREAS OF LESS THAN 2% SLOPE AND SANDY SOILS (USDA GENERAL
CLASSIFICATION SYSTEM,SOIL CLASS A) MAXIMUM SLOPE LENGTH AND
SILT FENCE LENGTH WILL BE UNLIMITED. IN THESE AREAS SILT FENCE
MAY BE THE ONLY PERIMETER CONTROL REQUIRED.
1. FENCE POST SHALL BE A MINIMUM OF 36' LONG DRIVEN 16"
MINIMUM INTO THE GROUND. WOOD POST SHALL BE 1 1/2"
SQUARE (MINIMUM) CUT, OR 1 3/4" DIAMETER (MINIMUM)
ROUND AND SHALL BE OF SOUND QUALITY HARDWOOD. STEEL POST WILL BE
STANDARD T OR U SECTION WEIGHTING NOT LESS THAN 1.00 POUND PER
LINEAR FOOT.
2. GEOTEXTILE SHALL BE FASTENED SECURELY TO EACH FENCE POST WITH WIRE
TIES OR STAPLES AT TOP AND MID-SECTION AND SHALL MEET THE FOLLOWING
REQUIREMENTS FOR GEOTEXTILE CLASS F:
TENSILE STRENGTH
TENSILE MODULUS
FLOW RATE
FILTERING EFFICIENCY
50 LBS/IN. (MIN)
20 LBS/IN (MIN.)
0.3 GAL FT/MIN.(MAX)
2
75% (MIN.)
TEST: MSMT 509
TEST: MSMT 509
TEST: MSMT 322
TEST: MSMT 322
3. WHERE ENDS OF GEOTEXTILE FABRIC COME TOGETHER, THEY SHALL BE
OVERLAPPED, FOLDED AND STAPLED TO PREVENT SEDIMENT BYPASS.
4. SILT FENCE SHALL BE INSPECTED AFTER EACH RAINFALL EVENT AND MAINTAINED
WHEN BULGES OCCUR OR WHEN SEDIMENT ACCUMULATION REACHES 50% OF
THE FABRIC HEIGHT.
SILT BAG FOR PUMPED DIRTY WATER
1. THE CONTRACTOR SHALL CONDUCT OPERATIONS AND MAINTAIN THE PROJECT
SITE SO AS TO MINIMIZE THE CREATION AND DISPERSION OF DUST. DUST
CONTROL SHALL BE USED THROUGHOUT THE WORK AT THE SITE.
2. WIDTH - 10' MINIMUM, SHOULD BE FLARED AT THE EXISTING ROAD
TO PROVIDE A TURNING RADIUS.
3. GEOTEXTILE FABRIC (FILTER CLOTH) SHALL BE PLACED OVER THE EXISTING
GROUND PRIOR TO PLACING STONE.
4. STONE - CRUSHED AGGREGATE (2" TO 3") OR RECLAIMED
OR RECYCLED CONCRETE EQUIVALENT SHALL BE PLACED AT LEAST 6"
CONSTRUCTION SPECIFICATIONS
5. ALL BALES SHALL BE REMOVED WHEN THE SITE HAS BEEN
STABILIZED. THE TRENCH WHERE THE BALES WERE LOCATED SHALL BE
GRADED FLUSH AND STABILIZED.
1. LENGTH - MIN. OF 50' RAMP x 30' RAMP FOR SINGLE
RESIDENCE LOT.
DEEP OVER THE LENGTH AND WIDTH OF THE ENTRANCE.
4. STRAW BALE DIKES SHALL BE INSPECTED FREQUENTLY AND AFTER
EACH RAIN EVENT AND MAINTENANCE PERFORMED AS NECESSARY.
SILT FENCE
SILT BAG FOR PUMPED DIRTY WATER
5. SURFACE WATER - ALL SURFACE WATER FLOWING TO OR DIVERTED TOWARD
CONSTRUCTION ENTRANCES SHALL BE PIPED THROUGH THE ENTRANCE,
MAINTAINING POSITIVE DRAINAGE. PIPE INSTALLED THROUGH THE STABILIZED
CONSTRUCTION ENTRANCE SHALL BE PROTECTED WITH A MOUNTABLE BERM
WITH 5:1 SLOPES AND MIN. OF 6" OF STONE OVER THE PIPE.
PIPE HAS TO BE SIZED ACCORDING TO THE DRAINAGE. WHEN THE SCE IS
LOCATED AT A HIGH SPOT AND HAS NO DRAINAGE TO CONVEY, A PIPE WILL
NOT BE NECESSARY. PIPE SHOULD BE SIZED ACCORDING TO THE AMOUNT
OF RUNOFF TO BE CONVEYED. A 6" MIN. WILL BE REQUIRED.
2. THE CONTRACTOR MUST PROVIDE CLEAN WATER, FREE FROM SALT, OIL AND
OTHER DELETERIOUS MATERIAL TO BE USED FOR ON-SITE DUST CONTROL.
3.
THE CONTRACTOR SHALL SUPPLY WATER SPRAYING EQUIPMENT CAPABLE OF
ACCESSING ALL WORK AREAS.
4.
THE CONTRACTOR SHALL IMPLEMENT STRICT DUST CONTROL MEASURES
DURING ACTIVE CONSTRUCTION PERIODS ON-SITE. THESE CONTROL MEASURES
WILL GENERALLY CONSIST OF WATER APPLICATIONS THAT SHALL BE APPLIED A
MINIMUM OF ONCE PER DAY DURING DRY WEATHER OR MORE OFTEN AS
REQUIRED TO PREVENT DUST EMISSIONS.
5.
SCE
8. WASHING - WHEELS SHALL BE CLEANED TO REMOVE SEDIMENT PRIOR TO
ENTRANCE ONTO PUBLIC RIGHT-OF-WAY WHEN WASHING IS REQUIRED. IT
SHALL BE DONE ON AN AREA STABILIZED WITH STONE WHICH DRAINS INTO
A APPROVED SEDIMENT TRAPPING DEVICE.
SS-2
SD-12
PIPE SLOPE DRAIN
GSS-3
PSD-12
PERIMETER DIKE/SWALE
INLET PROTECTION
DIVERSION
KEY PLAN
GRASSED WATERWAY
LINED WATERWAY
ROCK OUTLET PROTECTION
SUBSURFACE DRAIN
VEHICLE WASH AREA
STONE OUTLET STRUCTURE
A. APPLY WATER WITH EQUIPMENT CONSISTING OF TANK, SPRAY BAR,PUMP
WITH DISCHARGE PRESSURE GAUGE.
B.
P.O BOX 932
LAUREL, MD, 20725
M:--
C. DISPERSE WATER THROUGH NOZZLES ON SPRAY BAR AT 20 PSI (137.8kPa),
MINIMUM. KEEP AREAS DAMP WITHOUT CREATING NUISANCE CONDITIONS
SUCH AS PONDING.
6.
INFORMALCRAFT LLC
DIGITAL CONCEPTS
ARRANGE SPRAY BAR HEIGHT, NOZZLE SPACING AND SPRAY PATTERN TO
PROVIDE COMPLETE COVERAGE OF GROUND WITH WATER.
Owner:
FOR WATER APPLICATION TO SOIL SURFACES DURING DEMOLITION AND/OR
EXCAVATION, THE CONTRACTOR SHALL:
A.
APPLY WATER WITH EQUIPMENT CONSISTING OF A TANK, PUMP WITH
DISCHARGE GAUGE, HOSES AND MIST NOZZLES.
B.
LOCATE TANK AND SPRAYING EQUIPMENT SO THAT THE ENTIRE EXCAVATION
AREA CAN BE MISTED WITHOUT INTERFERING WITH DEMOLITION AND/OR
EXCAVATION EQUIPMENT OR OPERATIONS. KEEP AREAS DAMP WITHOUT
CREATING NUISANCE CONDITIONS SUCH AS PONDING.
C.
APPLY WATER SPRAY IN A MANNER TO PREVENT MOVEMENT OF SPRAY
BEYOND THE SITE BOUNDARIES.
9. PERIODIC INSPECTION AND NEEDED MAINTENANCE SHALL BE PROVIDED
AFTER EACH RAIN.
DETAIL 19 - STONE OUTLET STRUCTURE
GRADE STABILIZATION STRUCTURES
TSOS
6. LOCATION - A STABILIZED CONSTRUCTION ENTRANCE SHALL BE LOCATED AT
EVERY POINT WHERE CONSTRUCTION TRAFFIC ENTERS OR LEAVES A
CONSTRUCTION SITE. VEHICLES LEAVING THE SITE MUST TRAVEL OVER THE
ENTIRE LENGTH OF THE STABILIZED CONSTRUCTION ENTRANCE.
7. MAINTENANCE - THE ENTRANCE SHALL BE MAINTAINED IN CONDITION WHICH
WILL PREVENT TRACKING OR FLOWING OF SEDIMENT ONTO PUBLIC RIGHTS-OFWAY THIS MAY REQUIRE PERIODIC TOP DRESSING WITH ADDITIONAL STONE AS
CONDITIONS DEMAND AND REPAIR AND/OR CLEANOUT OF ANY MEASURES
USED TO TRAP SEDIMENT. ALL SEDIMENT SPILLED, DROPPED, WASHED OR
TRACKED ONTO PUBLIC RIGHTS-OF-WAY MUST BE REMOVED IMMEDIATELY.
FOR WATER APPLICATION TO UNDISTURBED SOIL SURFACES, THE CONTRACTOR
SHALL:
B-3
A-2
TEMPORARY SWALE
STABILIZED CONSTRUCTION ENTRANCE
CONSTRUCTION SPECIFICATIONS
SEAL
SBD
STRAW BALE DIKE
STRAW BALE DIKE
B-3
A-2
EARTH DIKE
FLOW
FLOW
VEHICLE
WASH AREA
STABILIZED
CONSTRUCTION ENTRANCE
DETAIL 19 - STONE OUTLET STRUCTURE
PROJECT ID# INC-010-DRG-001
3 VEHICLE WASH DETAIL
Construction Specifications
NOT DRAWN TO SCALE
FLOW
II. SPECIFICATIONS FOR SILT BAG 10'x15'(3.05 m x 4.57 m), 12 1/2'x15',
(3.81 m x 4.54 m), AND 15'x15' (4.54 m x 4.54 m) SIZES.
1. Crushed stone shall be used. Gravel may be used if crushed
stone is not available. The stone shall be 2"-3" in size.
2. The crest of the stone dike shall be at least 6" lower than the
lowest elevation of the top of the earth dike and shall be level.
I. INSTALLATION/USE
PROPERTIES
TEST METHOD
UNITS / METRIC
WEIGHT
GRAB TENSIL
PUNCTURE
FLOW RATE
PERMITIVITY
UV RESISTANCE
ASTM D-3776
ASTM D-4632
ASTM D-4833
ASTM D-4491
ASTM D-4991
ASTM D-4355
OZ./YD.
LBS.
LBS.
GAL./MIN./FT
-1
SEC.
%
WOVEN
(gm/m)
(kg)
(kg)
2 (l/min./m )
2
- -
(54.5)
40
-
1. UNFOLD THE SILT BAG AND SIT INSIDE THE FABRICATED
BOX (WOOD, METAL, OR PLASTIC).
EARTH
DIKE
2. INSERT PUMP DISCHARGE HOSE INTO HANDY
SEWN-IN SPOUT AND SECURE WITH THE ATTACHED
STRAPS.
FLOW
3. The stone outlet structure shall be embedded into the soil a
minimum of 4".
2' MINIMUM
TOP WIDTH
4. The minimum length of the crest of the stone outlet structure
shall be 6'.
5. The stone outlet structure shall be inspected after each rain.
Stone shall be replaced when the structure ceases to function
and ponding results.
STANDARD SYMBOL
3. CONNECT OUTFALL PIPE OR HOSE TO THE OUTLET PIPE
OF BOX AND RUN TO THE NEAREST CATCH BASIN.
STONE
TSOS
PERSPECTIVE VIEW
7. The drainage area to this structure shall be less than 1/2 acre.
III. MAINTENANCE
1. REPLACE THE SILT BAG AFTER IT IS FILLED WITH
SILT.
L = 6'
LEVEL CREST
6" MINIMUM
6" MINIMUM
12" MINIMUM
m
'
15
)
FILTER BAG
(4
.5
7
6" WEIR
(152.4 MM)
1'
EMBED BAFFLE BOARD
4" MINIMUM INTO GROUND
BRICKBATS
3" TO 4" DEPTH PRIOR TO
COMPACTION OF BRICKBATS
DENUDED EARTH
SECTION VIEW
BRICKBAT DETAIL
NOT DRAWN TO SCALE
6. The baffle board shall be extended one foot into the dike,
staked and embedded 4" into the existing ground.
4. PUMP DIRTY WATER INTO BAG. THE BAG COLLECTS
THE SILT AS THE CLEAN WATER GENTLY FILTERS
OUT FROM ALL SIDES.
IN
DRAWING TITLE:
PROJECT No:
STANDARDS AND SPECIFICATIONS
FOR
BRICKBAT GROUND COVER
DEFINITIONS:
2' MINIMUM
TEMPORARY GROUND COVER CONSISTING OF BROKEN BRICK (1/2 PIECE OR SMALLER)
PLACED OVER DENUDED EARTH.
18" MINIMUM
DRAWING TITLE:
EROSION AND
SEDIMENT CONTROL
DETAILS
GROUND LINE
PERFORATIONS
FOR DEWATERING
2" X 10" X 12' BAFFLE BOARD
1" HOLES ON
6" CENTERS
CROSS SECTION
(0.30 m)
10-15'
(3.05 m TO 4.57 m)
OUT
2' (0.61 m)
U.S. DEPARTMENT OF AGRICULTURE
SOIL CONSERVATION SERVICE
PAGE
C - 11 - 2
U.S. DEPARTMENT OF AGRICULTURE
SOIL CONSERVATION SERVICE
PAGE
C - 11 - 2
SCALE:
1/4" = 1'-0"
C-2
CONSTRUCTION DOCUMENTS
MAY 17, 2015
NO.
SELECTIVE DEMOLITION NOTES
DATE
ISSUE
EXIST. DECK
1. THE SCOPE OF THIS WORK SHALL BE SELECTIVE DEMOLITION.
AREAS OF WALLS, FLOORS, CEILINGS, FIXTURES, ELECTRICAL,
MECHANICAL, STRUCTURAL AND NON-STRUCTURAL SHALL BE REMOVED
AS DELINEATED AND / OR NOTED HEREON.
CLEAN AND SANITIZE ALL AREAS OF THE BUILDING.
THIS SELECTIVE DEMOLITION DOES NOT INCLUDE WORK WITHIN PUBLIC SPACE.
2. ALL DEMOLITION WORK SHALL BE PERFORMED IN COMPLIANCE WITH
APPLICABLE CODES AND WITH LOCAL AND OSHA REQUIREMENTS.
3. CONTRACTOR SHALL OBTAIN ALL REQUIRED LICENSES AND PERMITS
PRIOR TO STARTING DEMOLITION WORK.
0'
8'
16'
32'
CONTRACTOR SHALL OBTAIN ALL REQUIRED INSPECTIONS AND APPROVALS
SCALE: 1/4"= 1'-0"
4. INSTALL PROPER BRACING, SHORING AND SUPPORT FOR STRUCTURAL
COMPONENTS AT AREAS TO BE DEMOLISHED AND AREAS SCHEDULED
TO REMAIN. INSTALL BEAMS AND COLUMNS AS NEEDED AND DIRECTED BY
SUN ROOM
THE ARCHITECT TO SAFELY MAINTAIN EXISTING AREAS OF THE STRUCTURE
SCHEDULED TO REMAIN.
5. THE DEMOLITION CONTRACTOR SHALL NOTIFY THE ARCHITECT FOR DIRECTIVES,
DN
PRIOR TO STARTING DEMOLITION WORK.
SEAL
EXIST.ELEC.
METER TO BE
RELOCATED
6. PREPARE ALL DEMOLITION AREAS TO RECEIVE THE NEW CONSTRUCTION.
EXIST. WINDOWS TO
BE REMOVED
7. ALL MECHANICAL, PLUMBING AND ELECTRICAL DEMOLITION
DINING ROOM
SHALL BE DONE BY A LICENSED PLUMBER AND ELECTRICIAN, RESPECTIVELY.
LIVING ROOM
DEMOLITION SYMBOLS
KEY PLAN
EXISTING WALL TO REMAIN
SECTION OF WALL
TO REMAIN
EXISTING WALL TO BE REMOVED
CL.
REF.
DN
INFORMALCRAFT LLC
SECTION OF WALL
DIGITAL CONCEPTS
ENTRYWAY
TO BE REMOVED
KITCHEN
ISLAND.
P.O BOX 932
LAUREL, MD, 20725
M:--
UP
EXISTING WINDOW TO BE REMOVED
Owner:
CL.
EXIST.
CONDENSER
UNIT TO BE
RELOCATED
EXIST. WINDOWS
TO BE REMOVED
AND OPENING
FILLED
EXIST. DOOR TO
BE REMOVED
D
W
EXIST. WINDOW
TO BE REMOVED
EXIST.
GAS WATER
HEATER
EXIST.WALLS TO BE
REMOVED
MEDIA ROOM
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
EXIST. DOOR TO
BE REMOVED
EXIST. DECK
UNFINISHED BASEMENT
EXIST. COLUMN
UP
EXIST. COLUMN
CL.
PROJECT No:
HALLWAY
UP
GARAGE
DRAWING TITLE:
EXISTING BASEMENT
& FIRST FLOOR
DEMOLITON PLAN
BEDROOM
BATH.
SCALE:
1/4" = 1'-0"
D-1
CONSTRUCTION DOCUMENTS
1
EXIST. BASEMENT DEMOLITON PLAN
1/4" = 1'- 0"
2
EXIST. FIRST FLOOR DEMOLITON PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. CHIMNEY
EXIST. GUTTER
& DS
SLOPE
1:4
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
BEDROOM
BATH.
CL.
HOUSE
1:5
SLOPE
1:4
CL.
SLOPE
BEDROOM
SEAL
SLOPE
1:4
CL.
DN
BEDROOM
UP
SKYLIGHT
SKYLIGHT
KEY PLAN
1:5
SLOPE
HALLWAY
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
BATH.
EXIST.
WINDOW TO BE
REMOVED AND
OPENING FILLED
Owner:
BEDROOM
EXIST. GUTTER
& DS
EXIST. ROOF TO BE
REMOVED
EXIST. DS TO BE
REMOVED
GARAGE
1:2
SLOPE
EXIST. GUTTER
& DS
EXIST. SKYLIGHTS
TO BE REMOVED
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
1:2
SLOPE
GARAGE
PROJECT No:
DRAWING TITLE:
EXISTING SECOND
FLOOR & ROOF
DEMOLITON PLAN
EXIST. GUTTER
& DS
SCALE:
1/4" = 1'-0"
D-2
CONSTRUCTION DOCUMENTS
1
EXIST. SECOND DEMOLITON PLAN
1/4" = 1'- 0"
2
EXIST. ROOF DEMOLITON PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
EXIST. SKYLIGHT
DATE
ISSUE
EXIST. ASPHALT
SHINGLE ROOF
ROOF 3
ROOF 3
EXIST. ASPHALT
SHINGLES
ROOF 2
ROOF 1
ROOF 2
ROOF 1
EXIST. ASPHALT
SHINGLES
EXIST. 5" GUTTER
& 4"x3" DS
EXIST. 5" GUTTER
& 4"x3" DS
0'
EXIST. 6" WOOD
SIDING
8'
16'
32'
SCALE: 1/4"= 1'-0"
EXIST. 6" WOOD
SIDING
LEVEL 3
LEVEL 3
LEVEL 2
GROUND
LEVEL 2
GROUND
SEAL
LEVEL 1
LEVEL 1
BASEMENT
BASEMENT
KEY PLAN
1
EXIST. NORTH ELEVATION
INFORMALCRAFT LLC
DIGITAL CONCEPTS
1/4" = 1'- 0"
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
ROOF 3
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
ROOF 3
ROOF 2
ROOF 2
ROOF 1
ROOF 1
EXIST. GUTTER
& DS
PROJECT ID# INC-010-DRG-001
EXIST. 6" WOOD
SIDING
DRAWING TITLE:
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
EXIST. 6" WOOD
SIDING
LEVEL 3
LEVEL 3
LEVEL 2
LEVEL 2
GROUND
PROJECT No:
DRAWING TITLE:
EXISTING NORTH AND
EAST ELEVATION
GROUND
LEVEL 1
LEVEL 1
BASEMENT
BASEMENT
ELECTRIC METER
TO BE RELOCATED
EXIST. WOOD DECK
SCALE:
1/4" = 1'-0"
D-3
CONSTRUCTION DOCUMENTS
2
EXIST. EAST ELEVATION
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
ARCHITECTURAL NOTES
1.
ALL WORK SHALL CONFORM TO THE I.B.C. 2012 CODES, APPLICABLE
ZONING REGULATIONS AND ALL OTHER APPLICABLE CODES,
REGULATIONS AND REQUIREMENTS.
2.
THIS DESIGN AND THE CONSTRUCTION SHALL BE SUBJECT TO HISTORIC
PRESERVATION REVIEW REQUIREMENTS AND CONSTRUCTION
INSPECTION WHERE APPLICABLE.
3.
4.
THE CONTRACTOR SHALL PROVIDE ALL MATERIALS, LABOR,
EQUIPMENT, TOOLS AND SUPERVISION AS REQUIRED TO COMPLETE ALL
PARTS OF THE WORK.
5.
THE WORK AREA SHALL BE KEPT CLEAN, NEAT AND IN A SAFE MANNER
AT ALL TIMES.
6.
THE CONTRACTOR SHALL OBTAIN SEPARATE PLUMBING AND
MECHANICAL AND ELECTRICAL PERMITS.
7.
THE CONTRACTOR SHALL OBTAIN ALL REQUIRED INSPECTIONS AND
APPROVALS.
8.
0'
8'
16'
SCALE: 1/4"= 1'-0"
D
W
SEAL
EXIST.
GAS WATER
HEATER
MEDIA ROOM
THE CONTRACTOR SHALL EXERCISE CAUTION TO PREVENT DAMAGE TO
AREAS NOT SCHEDULED FOR WORK. PROVIDE A SMOOTH INVISIBLE
TRANSISTION BETWEEN THE NEWWORK AND AREAS NOT SCHEDULED
FOR WORK.
UNFINISHED BASEMENT
9.
32'
THE CONTRACTOR SHALL CONSULT THE ARCHITECT IMMEDIATELY UPON
THE OCCURRANCE OF DISCREPANCY BETWEEN THE DRAWINGS AND
THE SITE CONDITIONS.
EXIST. COLUMN
KEY PLAN
UP
EXIST. COLUMN
INFORMALCRAFT LLC
HALLWAY
UP
10. THE ARCHITECTURAL DIVISION OF THE SCOPE OF WORK,INCLUDING BUT
NOT LIMITED TO FINISHES, FURNISHING AND INSTALLATIONS, SHALL BE
COORDINATED WITH ALL OTHER DIVISIONS OF THE WORK, INCLUDING
BUT NOT LIMITED PLUMBING, ELECTRIICAL, MECHANICAL AND
EQUIPMENT. CONTRACTOR SHALL REPAIR DAMAGED AREAS, PATCH
HOLESAND REFINISH AREAS DUE TO THE INSTALLATION OF
PLUMBING,MECHANICAL AND ELECTRICAL EQUIPMENT.REPAIRS AND
REFINISHES SHALL MATCH AND BLEND WITHADJACENT AREAS AND
SHALL BE AT AN ACCEPTABLE QUALITY.
CL.
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
BEDROOM
BATH.
11. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, SAMPLES, CATALOG
CUTS, AND MANUFACTURER'S SPECIFICATIONS FOR ALL INSTALLATIONS
TO THE ARCHITECT FOR APPROVAL, PRIOR TO STARTING THE WORK.
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
12. THE LAYOUT DELINEATED WITHIN THESE FLOOR PLANS MAY DEVIATE
FROM THE ACTUAL CONSTRUCTION. ANY DEVIATIONS SHALL FULLY
COMPLY WITH ALL APPLICABLE CODES.
PROJECT No:
DRAWING TITLE:
ARCHITECTURAL NOTES
& PROPOSED BASEMENT
PLAN
SCALE:
1/4" = 1'-0"
A-1
CONSTRUCTION DOCUMENTS
1
PROP. BASEMENT FLOOR PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. DECK
21'-3 1/2"
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
DN
SEAL
A
41'-4"
DECK
A
A
8'-6 1/2"
12'-0"
7'-5"
P3
CL.
KEY PLAN
AQUARIUM
CL.
DN
3'-0"
4'-9 1/2"
6'-0"
5'-2 1/2"
4'-2"
3'-0"
6'-1"
4
INFORMALCRAFT LLC
DIGITAL CONCEPTS
UP
DINING TABLE
6'-0"
P.O BOX 932
LAUREL, MD, 20725
M:--
P2
6'-7"
SKYLIGHT
4'-0"
P1
ELEC. METER
3
P3
5
P3
3
CL.
FOYER
8'-9"
E
3'-2"
3'-3 1/2"
STORAGE
12'-7 1/2"
10'-5"
4'-0"
DESK P2
3'-8"
A
5
SKYLIGHT
KITCHEN
3'-5 1/2"
2'-0"
2'-0 1/2"
4'-5 1/2"
A
6'-2"
11'-0"
5'-1 1/2"
PROP. DECK WITH
5/4" x 6" WOOD
DECKING
D/W
P2
A
11'-1 1/2"
SKYLIGHT
4'-0"
4'-7 1/2"
2'-0"
PANTRY
P1
1
E
11'-7 1/2"
PROJECT ID# INC-010-DRG-001
NEW PERGOLA
12'-6"
2
CONDENSER
UNIT
18'-4"
GARAGE
20'-7"
Owner:
2'-0 1/2"
REF.
10'-9"
DINING
DRAWING TITLE:
EXIST. DECK
PROJECT No:
DRAWING TITLE:
PROPOSED FIRST
FLOOR PLAN
SCALE:
1/4" = 1'-0"
A-2
CONSTRUCTION DOCUMENTS
1
PROP. FIRST FLOOR PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. DECK
21'-8"
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
DN
RECESSED LIGHT
CHANDALIER
SEAL
41'-4"
DECK
KEY PLAN
CL.
AQUARIUM
CL.
DN
INFORMALCRAFT LLC
DIGITAL CONCEPTS
UP
P.O BOX 932
LAUREL, MD, 20725
M:--
DINING TABLE
TRACK LIGHT
DINING
Owner:
REF.
SKYLIGHT
SKYLIGHT
D/W
SKYLIGHT
CL.
NEW DECK WITH
5/4" x 6" WOOD
DECKING
KITCHEN
FOYER
MOTION
SENSOR
LIGHT
STORAGE
13'-0"
4'-4"
DESK
PANTRY
PROJECT ID# INC-010-DRG-001
NEW PERGOLA
DRAWING TITLE:
EXIST. DECK
GARAGE
PROJECT No:
DRAWING TITLE:
PROPOSED FIRST
FLOOR LIGHTING
PLAN
SCALE:
1/4" = 1'-0"
A-3
CONSTRUCTION DOCUMENTS
1
PROP. FIRST FLOOR LIGHTING PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. CHIMNEY
EXIST. GUTTER
& DS
SLOPE
1:4
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
1:5
SEAL
1:5
SLOPE
SLOPE
1:4
RECESSED LIGHT
UNDER ROOF
OVERHANG
KEY PLAN
SLOPE
1:4
SLOPE
HOUSE
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
SKYLIGHT
NEW SKY LIGHT
Owner:
PROP. 5" GUTTER
& 4"x3" DS
VALLEY DRAIN
EXIST. GUTTER
& DS
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
1:2
GARAGE
SLOPE
PROP. ASPHALT
SHINGLE ROOF
1:2
SLOPE
PROP. 5" GUTTER
& 4"x3" DS
PROJECT No:
DRAWING TITLE:
PROPOSED ROOF
PLAN
EXIST. GUTTER
& DS
SCALE:
1/4" = 1'-0"
A-4
CONSTRUCTION DOCUMENTS
1
PROP. ROOF PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
PROP. SKYLIGHT
ISSUE
MOTION SENSOR
LIGHT
PROP. ASPHALT
SHINGLE ROOF
ROOF 3
ROOF 2
ROOF 2
2'-5"
ROOF 3
EXIST. ASPHALT
SHINGLES
ROOF 1
1'-5"
PROP. ASPHALT
SHINGLE ROOF
DATE
ROOF 1
EXIST. ASPHALT
SHINGLES
EXIST. 5" GUTTER
& 4"x3" DS
PROP. 6" WOOD
SIDING
PROP. 5" GUTTER
& 4"x3" DS
PROP. CANTELIEVER
PERGOLA
EXIST. 6" WOOD
SIDING
E
14'-1"
0'
EXIST. 6" WOOD
SIDING
8
16'
32'
SCALE: 1/4"= 1'-0"
E
LEVEL 3
LEVEL 3
LEVEL 2
GROUND
LEVEL 2
GROUND
SEAL
EXIST. DECK
KEY PLAN
1
PROP. NORTH ELEVATION
INFORMALCRAFT LLC
DIGITAL CONCEPTS
1/4" = 1'- 0"
P.O BOX 932
LAUREL, MD, 20725
M:--
EXIST. CHIMNEY
Owner:
EXIST. ASPHALT
SHINGLE ROOF
ROOF 3
ROOF 3
ROOF 2
ROOF 2
B
ROOF 1
ROOF 1
2'-2 1/2" 1'-7"
EXIST. ASPHALT
SHINGLE ROOF
EXIST. ASPHALT
SHINGLE ROOF
PROJECT ID# INC-010-DRG-001
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
19'-2 1/2"
EXIST. GUTTER
& DS
DRAWING TITLE:
PROP. DECK STAIR
EXIST. ASPHALT
SHINGLE ROOF
LEVEL 3
LEVEL 3
LEVEL 2
LEVEL 2
1'-4"
PROP. DECK
GROUND
3'-4 1/2"
PROJECT No:
DRAWING TITLE:
PROPOSED NORTH &
SOUTH ELEVATIONS
GROUND
SCALE:
1/4" = 1'-0"
A-5
CONSTRUCTION DOCUMENTS
2
PROP. SOUTH ELEVATION
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
0'
8
16'
32'
SCALE: 1/4"= 1'-0"
EXIST. CHIMNEY
PROP. 5" GUTTER
& 4"x3" DS
VALLEY DRAIN
ROOF 3
ROOF 3
ROOF 2
ROOF 2
ROOF 1
ROOF 1
EXIST. GUTTER
& DS
2'-2 1/2"
MOTION SENSOR
LIGHT
SEAL
C
D
A
A
A
A
2
EXIST. GUTTER
& DS
PROP. 6" WOOD
SIDING
A
EXIST. GUTTER
& DS
A
12'-11 1/2"
EXIST. GUTTER
& DS
EXIST. 6" WOOD
SIDING
PROP. 6" WOOD
SIDING
LEVEL 3
LEVEL 3
LEVEL 2
LEVEL 2
GROUND
16'-9"
EXIST. 6" WOOD
SIDING
KEY PLAN
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
GROUND
Owner:
NEW DECK STAIR
NEW DECK
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
PROJECT No:
DRAWING TITLE:
PROPOSED EAST
ELEVATION
SCALE:
1/4" = 1'-0"
A-6
CONSTRUCTION DOCUMENTS
1
PROP. EAST ELEVATION
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
ROOF
ANCHOR
TRIPLE JOISTS
ROOF
ANCHOR
ANCHOR
10" MINERAL FIBER INSUL.
8'
16'
32'
SCALE: 1/4"= 1'-0"
DOUBLE 2x6
HEAD PLATE
5/8" TYPE "X" GYP. BD.
LINE OF FIN. CLG.
10" MINERAL FIBER INSUL.
LINE OF FIN. CLG.
5/8" TYPE "X" GYP. BD.
SINGLE 2x4
HEAD PLATE
0'
DOUBLE 2x4
HEAD PLATE
1-HOUR FIRE RATED
L-507
UL DES. NO.
5/8" TYPE "X" GYP. BD.
LINE OF FIN. CLG.
2x4 WOOD STUDS,
SPACED @ 16" O.C. (TYP.),
w/ ONE-LAYER, TYPE "R" GYP. BD.
@ EACH SIDE
41/2"
2x6 WOOD STUDS,
SPACED @ 16" O.C. (TYP.),
w/ ONE-LAYER, TYPE "R" GYP. BD.
@ EACH SIDE
6"
1-HOUR FIRE RATED
L-507
UL DES. NO.
2x4 WOOD STUDS,
SPACED @ 16" O.C. (TYP.),
w/ ONE-LAYER, TYPE "R" GYP. BD.
@ EACH SIDE
2 LAYERS 5/8" TYPE "X" GYP. BD.
4 1/2"
@ EACH SIDE FOR P3a ASSEMBLY
4"MINERAL FIBER INSUL.
SEAL
2x6 WOOD
FIRE STOP
2x4 WOOD
FIRE STOP
2x4 WOOD
FIRE STOP
2-HOUR FIRE RATED
U411
UL DES. NO.
KEY PLAN
BASE
(SEE ROOM FINISH SCHEDULE)
SINGLE 2x4
SILL PLATE
BASE
(SEE ROOM FINISH SCHEDULE)
SINGLE 2x4
SILL PLATE
BASE
(SEE ROOM FINISH SCHEDULE)
ANCHOR
SINGLE 2x6
SILL PLATE
LINE OF FIN. FLR.
INFORMALCRAFT LLC
LINE OF FIN. FLR.
DIGITAL CONCEPTS
LINE OF FIN. FLR.
ANCHOR
ANCHOR
ANCHOR
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
P1
TYPICAL RATED
PARTITION AND CEILING ASSEMBLY
NOT DRAWN TO SCALE
P2
TYPICAL NON-RATED
PARTITION AND CEILING ASSEMBLY
NOT DRAWN TO SCALE
P3
TYPICAL NON-RATED
PARTITION AND CEILING ASSEMBLY
NOT DRAWN TO SCALE
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
PROJECT No:
DRAWING TITLE:
PARTITION WALL
SECTIONS
SCALE:
1/4" = 1'-0"
A-7
CONSTRUCTION DOCUMENTS
MAY 17, 2015
NO.
DOOR NOTES:
DATE
ISSUE
1. ALL EXTERIOR DOORS SHALL BE FIBERGLASS.
2. EXTERIOR DOORS SHALL BE AS MANUFACTURED BY ANDERSON OR APPROVED EQUAL.
DOOR SCHEDULE
FRAME
DOOR
TYPE
1
SWINGING
SIZE
3'-0" x 6'-8" x 1 3/4"
ROOM FINISH SCHEDULE
MAT./FIN.
FIBERGLASS
FACE
TYPE
4 PANEL
A
MAT./FIN.
THRESHOLD
WOOD
LOCKSET
WOOD
SWINGING
3'-0" x 6'-8" x 1 3/4"
FIBERGLASS
4 PANEL
B
WOOD
WOOD
PRIVATE
3
SWINGING
2'-6" x 6'-8" x 1 3/8"
HARDBOARD
4 PANEL
B
WOOD
WOOD
PASSAGE
4
SWINGING
6'-0" x 6'-8" x 1 3/4"
FIBERGLASS
1 PANEL
A
GLASS/WOOD
CLAD
WOOD
PRIVATE
5
FOLDING
4 -1'-2" x 6'-8" x 1 3/8"
HARDBOARD
4 PANEL
B
WOOD
WOOD
PASSAGE
3'-0"
3'-0"
1 1/2 PAIR,
HEAVY-DUTY
1 1/2 PAIR,
HEAVY-DUTY
1 1/2 PAIR,
HEAVY-DUTY
1 1/2 PAIR,
HEAVY-DUTY
1 1/2 PAIR,
HEAVY-DUTY
PRIVATE
2
2'-6"
HINGES
DOOR,
FRAME,
HARDWARE
RATING
UL LABEL "B"
ROOM
REMARKS
1. FULLY
WEATHERSTRIPPED
UL LABEL "B"
UL LABEL "B"
FLOOR
1. FULLY
WEATHERSTRIPPED
WALL
FOYER
HARDWOOD
KITCHEN/DINING
HARDWOOD
PANTRY
HARDWOOD
BEDROOM
CARPET
BASE WAINSCOT CEILING
GYP. BD.
WOOD
NONE
GYP. BD.
WOOD
NONE
GYP. BD.
WOOD
NONE
GYP. BD.
WOOD
NONE
TRIM
REMARKS
GYP. BD.
WOOD
CROWN MOLD.
GYP. BD.
WOOD
CROWN MOLD.
GYP. BD.
WOOD
CROWN MOLD.
GYP. BD.
WOOD
CROWN MOLD.
0'
8
16'
32'
SCALE: 1/4"= 1'-0"
WINDOW NOTES:
3'-0"
1. ALL WINDOWS SHALL BE VINYL FRAME/SASH WITH 1/2" DOUBLE PANE, INSULATED GLAZING
2.WINDOWS SHALL BE AS MANUFACTURED BY ANDERSEN OR APPROVED EQUAL.
SEAL
WINDOW SCHEDULE
WOOD DOOR
WOOD DOOR
GLASS
MARK
3
4
6'-8"
2
6'-8"
1
6'-8"
6'-8"
GLASS
WOOD DOOR
WOOD DOOR
WINDOW
FRAME
THRESH.
HDW.
REMARKS
TYPE
SIZE
A
CSMT
2'-0"X5"-0"X2"
GLASS/VINYL CLAD
FIELD VERIFY DIMENSIONS
WOOD
VINYL CLAD WOOD
LOW E GLASS
B
FIXED
1'-8"X27'-3 1/2"X2"
GLASS/VINYL CLAD FIELD VERIFY DIMENSIONS
WOOD
VINYL CLAD WOOD
LOW E GLASS
C
D
E
FIXED
4'-6 1/2"X16'-10"X2"
GLASS/VINYL CLAD
FIELD VERIFY DIMENSIONS
WOOD
VINYL CLAD WOOD
LOW E GLASS
FIXED
2'-4"X7'-111/2"X2"
GLASS/VINYL CLAD
FIELD VERIFY DIMENSIONS
WOOD
VINYL CLAD WOOD
LOW E GLASS
FIXED
1'-2"X6'-10"X2"
GLASS/VINYL CLAD
FIELD VERIFY DIMENSIONS
WOOD
VINYL CLAD WOOD
LOW E GLASS
MAT./FIN.
REMARKS
TYPE MAT./FIN.
REMARKS
KEY PLAN
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
1'-2"
1'-2"
1'-2"
27'-3 1/2"
1'-2"
1'-8"
2'-0"
B
1'-2"
B
17'-2
1/2
PROJECT ID# INC-010-DRG-001
"
DRAWING TITLE:
C
10 1/2"
A
4'-61/2"
5
5'-0"
6'-10"
16'-10"
8'-2"
NOT TO SCALE
D
2'-4"
DOOR ELEVATIONS
E
PROJECT No:
7"
6'-8"
A
7'-11 1/2"
WINDOW ELEVATIONS
DRAWING TITLE:
DOOR, WINDOW &
ROOM FINISH
SCHEDULES
SCALE:
1/4" = 1'-0"
NOT TO SCALE
A-8
CONSTRUCTION DOCUMENTS
MAY 17, 2015
NO.
STRUCTURAL NOTES
All work and materials to comply with the requirements of the 2012 IBC code
1.
Code: the following design standards are applicable by reference:
ACI 530-99/ASCE 5-99 Building Code Requirements for Masonry Structures.
AITC- Timber Construction Manual - Fifth Ed.
ACI 318-95 Building code requirements for reinforced concrete
AISC - Manual of steel construction Ninth Ed.
2.
Foundations: footings, underpinning and slab on grades are designed to bear on native soil type SM or SC with an
allowable bearing pressure of 1500 psf. A qualified
Soiling-bearing inspector prior to placement of concrete shall verify all bearing values.
3.
Structural Steel:
A. All structural steel, including detail material shall conform to ASTM a572 Fy = 50ksi, U.N.O.
B. All structural tubing shall conform to ASTM A500, grd.B
C. All steel pipe shall be ASTM A53, type E or S, grade B
D. All welders shop and field, shall be certified. Use E70xx electrodes only
E.
All steel exposed to weather and exterior masonry support shall receive one shop coat of corrosion-inhibiting
primer.
F.
Detailing, fabrication and erection shall be in accordance with AISC. Adequately brace all steel against lateral
loads during erection.
G. All exterior structural steel shall receive rust preventative paint.
H. Connections:
I.
All beams connections shall be simple shear connections, U.N.O Where no reaction is provided, the beam shall
be assumed to carry 120 % of the allowable uniform load in Kips for beams laterally supported, as given in the
AISC steel construction manual.
II. Except as noted, all fasteners shall be ¾” diameter ASTM A325 bolts, designed to act in bearing type
connections with threads included.
5.
Lumber:
A. Lumber shall be SPF #2 with a min. FB = 875psi Min. Fv = 135psi and min. E = 1,400,000psi.
B. LVL and PSL shall have a min. FB = 2850psi; Fv = 285psi; E= 2,000,000psi.
C. Floor decking shall be ¾' APA rated decking. Roof decking shall be 5/8” APA rated decking. Wall shall be
7/16”OSB. Glue and nail roof and floor decking to joist and rafters.
D. Exterior wood walls shall be 2x4 studs at 16” o.c. above the basement and 12” o.c. below and interior wood
walls shall be 2x4 studs at 16” O.C. with a single top place and a single bottom plate. Provide solid blocking at
the mid-height of each wall and at the minimum of 48” O.C vertically.
E.
Provide double joist under all walls that run parallel to floor framing.
F.
Nail all multiple members together per the manufacture's recommendations and at a minimum use 2-10d nails at
6” O.C staggered.
G. Provided bridging at center of all joist spans exceeding 8'-0” and at 1/3 points of all joist spans exceeding 16'-0”.
Provide solid blocking at all bearing points on top of walls or beams.
H. Provide solid blocking below all wood posts.
I.
All posts shall have Simpson Cap and Base Plates typ.
J.
All joists shall have Simpson Hangers where applicable.
K. Glue all multiple studs together. Nail together with 2-10d nails at 3” O.C Stagger the slides of the suds that the
nails are driven from.
L.
All lumber in contact with masonry or concrete or within in 8” of soil shall be pressure treated. All lumber to
conform to IRC R319 for protection against corrosion and termite damage.
M. All lumber shall be kiln dried. Store lumber on site in such a manner as to prevent the seepage of water into the
wood.
N. Wood Lintels shall be as follows:
Opening < 3'-0” - 2-2x6
3'-0” < Opening < 5'-0” - 2-2x8
5'0”< Opening < 8'-0” - 2-2x10
Greater Than 8'-0” - See Plans
6.
Fasteners:
A. All prefabricated angels, bearing plates, and joist hangers shall be installed per the manufacturer
recommendations.
B. Follow the manufacturer recommendations for setting epoxy bolts.
C. Expansion bolts shall be crawl power studs.
Masonry:
Masonry construction shall be in conformance with the applicable sections of ACI
530-99/ASCE5-99, “Specifications for masonry Structures.”
B.
Concrete masonry units shall be hollow load bearing units (ASTM C90)
SPF #2 -
25 PCF
½ Decking -
1.7 PSF
¾” Decking -
2.5 PSF
Asphalt Shingles -
2.5 PSF
Slate Shingles -
15 PSF
½” Drywall -
2.2 PSF
Insulation -
1.5 PSF
Sliding -
2.0 PSF
CMU -
87 PCF
Brick -
130 PCF
LIVE LOADS:
DECK:
40PSF
STAIRS:
100 PSF
PUBLIC HALLWAY:
100 PSF
ATTIC:
20PSF
FLOOR:
40PSF
BALCONY:
60PSF
BEDROOM:
40PSF
ROOF:
30PSF
BASIC WIND SPEED:
WIND EXPOSEURE FACTOR:
WIND DESIGN PRESSURE:
GROUND SNOW LOAD (PG):
30PSF
FLAT ROOF SNOW LOAD (PF):
30PSF
SNOW EXPOSURE FACTOR (CE):
0.9
SNOW IMPORTANCE FACTOR (I):
1.0
Rafters:
L/240
Walls and Partitions:
Floors and Plastered Ceilings:
H/180
L/360
All other structural members:
L/240
Ext. Walls - with plaster or stucco finishes:
L/360
Ext. Walls - Wind Loads with brittle finishes:
L/240
Ext. Walls - Wind Loads with flexible finishes:
L/120
PROP. 6"x6"
POST
SEAL
EXIST. FRIST
FLOOR WALL
SEISMIC IMPORTANCE FACTOR (LE):
1.0
SPECTRAL RESPONSE ACCELERATIONS:
(Ss):
20%
(S1):
8.0%
HOUSE
(Sds):
33%
(Sd1):
18.7%
SEISMIC DESIGN CATEGORY:
B
SEISMIC SITE CLASSIFCATION:
D
SEISMIC COEFFICIENT (Cs):
INFORMALCRAFT LLC
DIGITAL CONCEPTS
EXIST. BASEMENT
WALL
0.22
9.1K
Owner:
EQUIV. LATERAL FORCE
BASIC SFRS: ORDINARY PLAIN MASONRY SHEAR WALLS
AND LIGHT FRAMED WALLS.
< 3'-0” - L4x3 ½ x1/4 LLV/ 4” of wall
< 7'-0” - L6x31/2x5/16 LLV/ 4” of wall.
PROP. 1'-8"
CONTINUOUS
CONCRETE
FOOTING 8" DEEP
Cast in place concrete:
Concrete construction shall be in conformance with the applicable sections of
PROP.FOUNDATION
WALL
27'-4"
ACI 318-95, “Part 3 - Construction Requirements.”
B.
P.O BOX 932
LAUREL, MD, 20725
M:--
1.5
Opening > 7'-0” - See Plan
A.
KEY PLAN
SPECTRAL RESPONSE COEFFICIENTS:
ANALYSIS PROCEDURE:
3'-0” < Opening
8.
PROP. 16"x16"
FOUNDATION
BELOW
PROP. 16"x16"
FOUNDATION
BELOW
SEISMIC DESIGN DATA:
SHEAR:
Opening
SCALE: 1/4"= 1'-0"
DEFLECTION LIMITATIONS:
Mortar to comply with ASTM C270 (type M or S).
Lintels shall be as follows:
EXIST. BASEMENT
WALL
32'
SNOW LOADS:
Provide corrugate masonry ties between brick fascia and wood walls or cmu walls
G.
EXIST. BASEMENT
FOUNDATION
16'
20PSF
E.
Provide 9ga truss styles joint reinforcement @ 16” O.C vertically.
1.0
B
D.
F.
PROP. 12"x12"
FOOTING
8'
90MPH
WIND LOAD IMPORTANCE FACTOR:
SEISMIC MODIFICATION FACTOR ®:
at 16” O.C in each direction.
0'
WIND LOADS
Grade n-1 with a net strength of 2000psi and F'm -150psi.
C.
EXIST. SUNROOM
FOUNDATION
6'-10 1/2"
A.
ISSUE
DEAD LOADS:
7'-4 1/2"
7.
DATE
Concrete construction shall have a minimum compressive strength at 28
4 1/2"
C.
All concrete shall be placed with a slump of 4” (+1/2”)
D.
All concrete shall be normal weight, UNO.
E.
All concrete exposed to weather shall have 6% +1% entrained air.
F.
Contractor shall pour extra concrete to account for deflection of the
1'-8"
days of 3000psi, UNO (Unless noted otherwise).
17'-10"
PROP. 1'-8"
CONTINUOUS
CONCRETE
FOOTING 8" DEEP
formwork to provide a flat finished surface.
9.
G.
Concrete cover for reinforcement shall be:
H.
Columns and beams
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
1-½
Slabs
¾”
Footings
3”
Reinforcements:
A.
Reinforcing bars shall be deformed bars conforming to ASTM A615, grade
B.
Welded wire fabric (wwf) shall conform to ASTM a185. Lap edges of wire
60 (Fy=60ksi)
EXISTING
GARAGE WALL
fabric at least 6” in each direction.
10.
Dimensions: The Contractor shall field verify all dimensions prior to
GARAGE
fabrication of structural components.
11.
Coordination: The contractor shall coordinate all sleeves, duct openings and
holes between trades. Any conduits or pipes embedded in concrete must be in
EXISTING SLAB
ON GRADE
PROJECT No:
DRAWING TITLE:
PROPOSED
FOUNDATION PLAN
accordance with ACI 318-95, chapter 6. Where sleeves are closely spaced in a
group, the group shall be treated as an opening and reinforced accordingly.
Submit drawings showing all opening sizes and locations for the approval by
the structural engineer.
SCALE:
1/4" = 1'-0"
S-1
CONSTRUCTION DOCUMENTS
1
PROP. FOUNDATION PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. DECK
PROP. 2"x12"
LEDGER
8'-5 1/2"
8'-1 1/2"
4'-10"
4'-11"
0'
8'
16'
32'
PROP. (2) 2"x12"
LEDGER
2"x12" FLOOR
JOISTS @ 12" O.C
12'-0"
SCALE: 1/4"= 1'-0"
PROP. (2) 2"x12"
JOIST
PROP. 2"x12"
LEDGER
SEAL
PROP. 6"x6"
POST
PROP. 3 1/2"
METAL POST
PROP. 16"x16"
FOUNDATION
BELOW
PROP. 16"x16"
FOUNDATION
BELOW
EXIST. COLUMN
EXIST. STEEL
BEAM
DECK
12'-0"
PROP. 3 1/2"
METAL POST
EXIST. COLUMN
PROP. (3) 2"x6"
COLUMN
PROP. (3) 2x6
COLUMN
PROP. 16"x16"
FOUNDATION
BELOW
PROP. 16"x16"
FOUNDATION
BELOW
KEY PLAN
PROP. (3) 2"x4"
POST
PROP. 12"x12"
FOOTING
PROP. (3) 2"x4"
POST
INFORMALCRAFT LLC
DIGITAL CONCEPTS
2"x12" FLOOR
JOISTS @ 12" O.C
LVL LEDGER
PROP. 4"x4" POST
14'-0"
P.O BOX 932
LAUREL, MD, 20725
M:--
LVL LEDGER
14'-0"
12'-6"
Owner:
7'-10 1/2"
2"x12" FLOOR
JOISTS @ 12" O.C
PROP. 4"x4" POST
JOIST HANGER
LVL LEDGER
9'-0"
9'-0"
PROJECT ID# INC-010-DRG-001
PROP. (3) 2"x4"
POST
DRAWING TITLE:
EXIST. DECK
GARAGE
PROJECT No:
DRAWING TITLE:
PROPOSED
BASEMENT & FIRST
FLOOR FRAMING PLAN
SCALE:
1/4" = 1'-0"
S-2
CONSTRUCTION DOCUMENTS
1
PROP. BASEMENT FRAMING PLAN
1/4" = 1'- 0"
2
PROP. FIRST FLOOR FRAMING PLAN
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. DECK
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
SEAL
3'-9 1/2"
DECK
PROP. (3) 2"x12"
LEDGER
2'-0 1/2"
PROP. (3) 2"x4"
POST BELOW
BEARING WALL
PROP. (3) 2"x12"
LEDGER
2"x8" ROOF
JOISTS @ 16" O.C
OVERHANG
KEY PLAN
9'-0"
7'-9"
PROP. (3) 2"x4"
POST
2"x12" ROOF
JOISTS @ 12" O.C
BEARING WALL
9'-8 1/2"
PROP. (3) 2"x4"
POST BELOW
INFORMALCRAFT LLC
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
2"x12" ROOF
JOISTS @ 12" O.C
8'-8"
Owner:
PROP. (3) 2"x4"
POST
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
EXIST. DECK
BEARING WALL
GARAGE
PROJECT No:
DRAWING TITLE:
PROPOSED
ROOF FRAMING PLAN
SCALE:
1/4" = 1'-0"
S-3
CONSTRUCTION DOCUMENTS
1
PROP. ROOF FRAMING PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
EXIST. DECK
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
CS-WSP BRACING
3'-0"
DN
SEAL
DECK
KEY PLAN
DN
CS-WSP BRACING
INFORMALCRAFT LLC
UP
DIGITAL CONCEPTS
3'-0"
P.O BOX 932
LAUREL, MD, 20725
M:--
Owner:
3'-0"
CS-WSP BRACING
NEW PERGOLA
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
3'-0"
3'-0"
EXIST. DECK
CS-WSP BRACING
CS-WSP BRACING
GARAGE
PROJECT No:
DRAWING TITLE:
WIND BRACING PLAN
BRACING METHOD:
1) CS-WSP: CONTINUOUSLY SHEATHED WOOD STRUCTURAL PANEL IN ACCORDANCE TO IRC 2012, TABLE 602.10.4
SCALE:
1/4" = 1'-0"
S-4
CONSTRUCTION DOCUMENTS
1
PROP. WIND BRACING PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
DATE
ISSUE
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
PROP. (3) 2"x12"
LEDGER
EXIST. CHIMNEY
PROP. 2"x12"
JOIST
PROP. (3) 2"x12"
LEDGER
VALLEY DRAIN
SEAL
ROOF 3
ROOF 3
PROP. DOUBLE
2"X4" HEAD PLATE
ROOF 2
ROOF 1
ANCHOR
8'-7"
EXIST. GUTTER
& DS
EXIST. GUTTER
& DS
LEVEL 3
DIGITAL CONCEPTS
P.O BOX 932
LAUREL, MD, 20725
M:--
LEVEL 2
GROUND
GROUND
KEY PLAN
INFORMALCRAFT LLC
LEVEL 3
3'-0"
LEVEL 2
16'-9"
PROP. (2) 2"X12"
LEDGER
EXIST. GUTTER
& DS
8'-7"
EXIST. 6" WOOD
SIDING
PROP. (3) 2"X12"
BEAM
6'-6"
EXIST. RIDGE
BEAM
10'-0 1/2"
EXIST. GUTTER
& DS
13'-9 1/2"
ROOF 1
2'-2 1/2"
ROOF 2
12'-11 1/2"
JOIST TIE
Owner:
6'-3"
PROP. 3 1/2"
METAL POST
LEVEL 1
BASEMENT
BASEMENT
NEW DECK STAIR
NEW DECK
16"x16"
FOUNDATION
1'-9"
LEVEL 1
NEW FOUNDATION
AND FOOTING
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
PROJECT No:
DRAWING TITLE:
BUIDLING SECTION AT
A-A
SCALE:
1/4" = 1'-0"
S-5
CONSTRUCTION DOCUMENTS
1
PROP. WIND BRACING PLAN
1/4" = 1'- 0"
MAY 17, 2015
NO.
ARCH 80 ROOFING
15# FELT
5/8 CDX PLYW'D SHEATH'G
RAFTERS/TRUSSES @ 12" O.C.
CEILING JOISTS @ 12" O.C.
R-38 INSUL (R-30 VAULTED)
5/8" GYPSUM BD
DATE
ISSUE
2"x4" Top Rail
4"x4" Rail Post
INSUL BAFFLE @ EAVE VENTS
2"x2" Pickets
@ 5" O.C. Min.
SIMPSON H2.5 SEISMIC TIES
3'6" Min.
(2) 2X6 PLATE
Lower Rail Must Not
Allow 4" Dia Sphere
to Pass through.
GUTTER ON 2X8 FASCIA
0'
8'
16'
32'
SCALE: 1/4"= 1'-0"
2'10" Min.
5/4"x6" Decking
3/8" VENTED SOFFIT & 2x4 BLOCKING
4"
SEAL
7 3/4"
2"x Pressure Treated
Joist @ 16" O.C.
HOUSE
FLOOR FINISH
7/16" PART BD UNDERLAY
3/4" T&G STURDI-FLOOR DECKING
JOISTS (SEE PLAN)
R-30 UNFACED INSULATION
2"x12" Stringers W/1 1/2" x 1/1/2"
Blocking to Support Treads
10"
Min.
KEY PLAN
3
2X6 PLATE
STAIR SECTION AT DECK
INFORMALCRAFT LLC
DIGITAL CONCEPTS
N.T.S
P.O BOX 932
LAUREL, MD, 20725
M:--
2"
2X12 JOIST
Sheathing
2x6 P.T. MUDSILL W/ SILL SEAL &
3/4" X 12" AB @ 24" OC
(MIN OF 2 PER BOARD &
WITHIN 12" OF ANY CORNER)
6"
(2) - #5 TOP
Owner:
HOUSE
CONC FDN WALL
#5 @ 12" EW
Cont Flashing
BASEMENT
Rim Joist
5/4 x6"
Decking
PROJECT ID# INC-010-DRG-001
DRAWING TITLE:
2x12 P.T. Joist
CONC FOUNDATION WALL
3/8" X5" Lag
Screws @ 16" O.C.
#5 @ 12" EW
#5 @ 12" OC
ALT. BENDS
(3) - #5
6 MIL POLY BLACK
MOISTURE BARRIER
Beam
6x6 Support
Post
Joist Hanger
12x12x36 FOOTING
P.T. Ledger Board
BASEMENT
PROJECT No:
DRAWING TITLE:
DETAILS
EARTH
DRAINAGE SYSTEM
4" DIA PERF PIPE IN
FILTER FABRIC "SOCK"
3" CLR
24"
SCALE:
1/4" = 1'-0"
S-6
1
TYP. WALL SECTION
N.T.S
4
DECK DETAIL
N.T.S
CONSTRUCTION DOCUMENTS
MAY 17, 2015