Draft Energy Audit Report Secretariat Bloack Islamabad
A Block Secretariat
Draft Energy Audit Report
Dec/Feb-
ENERGY AUDIT REPORT
SUBMITTED BY: ARSALAN
“A” Block – Energy Audit | www.sharifinternational.net
Page 1 of 68
Sharif International
Table of Contents
Introduction ................................................................................................................................ 5
1
Executive Summary .............................................................................................................. 6
1.1
Perceived Energy Audit Objectives ...................................................................... 7
1.2
Energy Audit Activities ......................................................................................... 7
1.3
Challenges Encountered ...................................................................................... 8
1.4
Short Summary .................................................................................................... 8
2
“A” Block Secretariat - Building characteristics and General operational Features ................ 10
3
Energy Systems in “A” Block Secretariat .............................................................................. 12
4
5
3.1
Electricity............................................................................................................ 12
3.2
Natural Gas ........................................................................................................ 13
3.3
Energy Utilization By Types ................................................................................ 13
Energy audit findings .......................................................................................................... 14
4.1
Energy Efficiency and conservation opportunities ............................................ 14
4.2
Energy utilization ............................................................................................... 14
4.2.1
Historical Electrical Bill Analysis ......................................................................... 15
4.2.2
Luminaries .......................................................................................................... 20
4.2.3
Electrical Appliances .......................................................................................... 25
4.2.4
AC Units .............................................................................................................. 28
4.2.5
Mass Transportation (Lifts) ................................................................................ 31
4.2.6
Building Envelope/Ventilation ........................................................................... 32
4.2.7
Fire Protection ................................................................................................... 34
4.2.8
Electrical Safety .................................................................................................. 35
4.2.9
General Observations ........................................................................................ 44
Energy Conservation & Maintenance Opportunities ............................................................ 45
5.1
Recommendations with Conservation Estimates & ROI ................................... 46
“A” Block – Energy Audit | www.sharifinternational.net
Page 2 of 68
5.1.1
Luminaries .......................................................................................................... 46
5.1.2
IT & Office Equipment ........................................................................................ 48
5.1.3
AC Units .............................................................................................................. 50
5.1.4
Mass Transportation (Lifts) ................................................................................ 51
5.1.5
Building Envelope/ventilation............................................................................ 53
5.1.6
Fire Protection ................................................................................................... 55
5.1.7
Electrical Safety .................................................................................................. 55
5.1.8
General Recommendations ............................................................................... 56
5.2
Alternate Energy Resources Potential ............................................................... 57
5.2.1
Solar System Potential for Sub-Metering .......................................................... 57
5.2.2
Solar System Potential ROI Calculations ............................................................ 62
5.3
Floor wise Sub-Metering .................................................................................... 64
5.4
Water Conservation at “A” Block....................................................................... 66
“A” Block – Energy Audit | www.sharifinternational.net
Page 3 of 68
Report Layout and Legends utilized therein:
1. This is a sample Chapter Heading.
1.1
This is 2nd Level Heading
1.1.1 This is 3rd Level Heading
1.1.1.1
This is 4th Level Heading
Symbols Utilized to denote:
Areas/situations requiring immediate attention and opportunities for safety or
protection.
Occasions and situations requiring urgent attention that if not handled can
possibly pose hazard to health and/or loss of life and property.
Situations that could potentially pose adverse effects on human health and wellbeing. Their remedial measures should be prioritized.
“A” Block – Energy Audit | www.sharifinternational.net
Page 4 of 68
Introduction
The current shifts in global trends like increase in the greenhouse gases, depletion of
hydrocarbon reserves and instability in energy rich countries of the world has spiraled the
cost of energy manifold. For industries & businesses to survive and be profitable,
incorporation of energy savings technology is a must.
The building model is calibrated against actual utility data to provide a realistic baseline
against which to compute operating savings for proposed measures. Extensive attention is
given to understand not only the operating characteristics of all energy consuming systems,
but also situations that cause load profile variations on short and longer term bases (e.g.
daily, monthly, annual).
Pakistan has limited resources of fossil fuels and is mostly dependent on hydropower
generation for its staple electrical energy requirements. This is one of the major reasons for
witnessing long hours of power outages on top of inefficient devices and processes all
across the country.
There are huge opportunities in the shape of sustainable energy savings in industrial and
commercial sectors, we simply need to identify them and implement Energy Conservation
Measures (ECMs), especially in the industrial and building sectors. This specifically highlights
the importance of implementing energy auditing across the board, initially to identify and
subsequently to address the low hanging fruit.
“A” Block – Energy Audit | www.sharifinternational.net
Page 5 of 68
1 Executive Summary
The National Energy Efficiency & Conservation Authority (NEECA) is an attached Department
of Ministry of Water and Power and is the focal federal agency to capture the substantial
economic and environmental benefits available through energy conservation and efficiency
in all sectors of economy. NEECA has been encouraging industries and buildings to conduct
Energy Audits which will not only help in identification of various energy saving
opportunities and will also establish a base to develop an organized reporting system
pertaining to flow of energy in the industry/building.
The building namely “A” Block Secretariat along with other blocks was constructed in 1968,
and is currently under the use of four ministries namely Ministry of Industries and
Production, Ministry of Water and Power, Ministry of Petroleum and Natural Resources and
Ministry of Commerce.
NEECA with a specific aim to demonstrate energy efficiency and conservation in public
sector buildings selected A-Block building for conduct of energy audit and subsequently
engaged M/s Sharif International(SI) for conduct of Energy audit at “A” Block Secretariat
after its selection through competitive bidding process. The first orientation/opening
meeting was held on 13th December, 2016 in which necessary guidelines were given by
NEECA officials. The salient main points of the meeting and activities carried out are
summarized below
1)
2)
3)
4)
The Energy Audit should be result oriented.
The floor wise running/connected peak load demands to be identified
Possibility of Net Metering for Ministry of Water and Power to be explored
Capital Development Authority (CDA) officials were briefed on conduct of Energy
Audit and general methodology.
5) Team of Sharif International took a quick round of the building in order to familiarize
themselves with the building surroundings, its envelope so that they can plan their
approach for preliminary survey accordingly to determine current level of operations
and practices.
As per the direction of Additional Secretary (MoWP)/ Managing Director (NEECA) Mr.
Hassan Nasir Jamy and guidelines given by the Manager Technical ECF/NEECA Mr. Asad
Mahmood, the field activity was subsequently initiated in mid of December and visits for
data collection purpose were done on intermittent basis as per the availability of CDA
nominated team and focal persons nominated by the Ministries located in A-Block. The
names of the focal persons along with their respective departments are presented in the
“A” Block – Energy Audit | www.sharifinternational.net
Page 6 of 68
Table below. The activities pertaining to Energy Audit activities were carried out in between
January-February 2017.
Sr. No
1
2
3
4
5
Name of Ministries
Ministry of Industries & Production
Ministry of Water & Power
Ministry of Petroleum & Natural Resources
Ministry of Commerce
Capital Development Authority
Focal Persons
Mr. Sikander Masood
Mr. Akbar Azam Rajar
Mr. Shafaat
Mr. Rafeeq Khan
Mr. Jamshaid Baloch
Table 1: Name of Ministries and Concerned Focal Persons
1.1 Perceived Energy Audit Objectives
An energy audit is an inspection, survey and analysis of energy flows in a building, process or
system with the objective of understanding the energy dynamics of the system under study.
Typically an energy audit is conducted to seek opportunities to reduce the amount of energy
input into the system without negatively affecting the outputs. Detailed Energy Audit is a
major tool for identifying low cost, medium cost and cost intensive energy conservation
opportunities in a facility. The Audit can be performed by an organization's own staff, or by
outside consultants or government organizations specialized in conducting energy audits.
The Detailed Energy Audit is often performed in two sequential phases: the Preliminary
Energy Audit, and the Detailed Energy Audit. The Audit process is described below.
When the object of study is an occupied industry then reducing energy consumption while
maintaining or improving production rate and health and safety of workers are of primary
concern. While in building energy audits, the nature of activities carried out in the buildings
and associated building systems are studied in order to enhance the energy efficiency of
different building systems to improve overall energy efficiency of the building to reduce the
carbon foot print and the kWh/m2 indicator. Beyond simply identifying the sources of
energy use, an energy audit seeks to prioritize the energy uses according to the greatest to
least cost effective opportunities for energy savings.
1.2 Energy Audit Activities
The Energy Audit was divided into three phases i.e. orientation, preliminary energy audit
and detailed energy audit. Major activities conducted in these phases are listed below
i.
Orientation
✓ Meeting with concerned officials
✓ Briefing the management about Energy Audit
ii.
Preliminary Energy Audit
“A” Block – Energy Audit | www.sharifinternational.net
Page 7 of 68
✓ Familiarization with the work done in the building
✓ Collection of required documents
✓ Taking Brief notes on High Visibility Opportunities
✓ Making a List of low hanging fruit
✓ Highlighting areas requiring extensive study
iii.
Detailed Energy Audit
✓ Measurements and Collection of Electrical Data
✓ Thermography of electrical panels
✓ Study of the Building Envelope
✓ Analysis of collected data and generation of useful information.
✓ Recommendations and commentary on investment, low investment and
major investment measures with resultant payback calculations.
✓ Examination of Fire Detection and Fire Hydrant Systems
✓ Feasibility study for solar system installation
✓ Draft Report Compilation.
1.3 Challenges Encountered
The SI Team faced some challenges during this Energy Audit, which are as follows:
✓ Restricted movement due to security issues caused some delays.
✓ Delayed response from the CDA technical housekeeping team.
✓ Lack of awareness/understanding
regarding the equipment used within
building;
✓ Unavailability of relevant data such as built construction design, construction
material, usage logs of essential equipment like passenger lift and transformer
maintenance report.
✓ The electric utility bills were estimated and did not provide an accurate picture
of the energy consumption of the building; this led to change of audit
methodology.
1.4 Short Summary
The electrical utility bill of “A” Block Secretariat can drastically come down from 3-6 million
rupees being charged on monthly basis to less than 1 million rupees per month if
immediate action to replace electric meter installed at “A” Block Secretariat is taken by
CDA/IESCO administration. Due to moderate weather conditions the analysis was done on
the basis of total connected load however attempts were also done to measure the running
loads with the help of equipment wherever possible. However, to give the reader a brief
overview, the summarized detail of the energy audit findings and the proposed savings are
“A” Block – Energy Audit | www.sharifinternational.net
Page 8 of 68
given below which will help in development of an effective energy efficient appliance
replacement program.
Appliances Connected Peak Load in Operational Condition (Watt Hours)
Air Conditioning
IT and Other
Floors
Lighting
Load
Equipment
Ground
28,800
24,000
19,360
480,000
1st
86,944
324,000
Total Floor-wise
Appliances Load
(Watt Hours)
72,160
890,944
2nd
93,024
524,000
344,360
961,384
3rd
76,752
556,000
319,400
952,152
4th
85,824
536,000
471,880
1,093,704
5th
47,808
352,000
304,720
704,528
6th
44,928
320,000
192,520
557,448
Total
464,080
2,792,000
1,976,240
5,232,320
Table 2: Summary of Total Connected Load
6th
5th
4th
3rd
2nd
1st
Ground
0
200,000
400,000
600,000
800,000
1,000,000
1,200,000
Figure 1: Graphical Representation of Summary of Total Connected Peak Load in Watt Hours
As it can be seen in the table and the graph above, majority of the electrical load is due to
the air-conditioning and IT and other equipment.
Summary - Total Calculated Energy Saving Potential
Energy
Cost Saving
Energy Saving
Saving
Cost Saving
Per Day (Rs)
Source of Load
Potential per Potential Per
Per Month
@ Rs.
Day (kWh)
Month
(Rs)
15/kWh
(kWh)
Lighting
302
9,060
4,530
135,900
Air Conditioning Load
888
26,640
13,320
399,600
IT and Other Equipment
207
6,210
3,105
93,150
Total
1,397
41,910
20,955
628,650
Table 3: Summary of Total Saving Calculated
*Air
Conditioning Load computed on 4 Months per year
“A” Block – Energy Audit | www.sharifinternational.net
Page 9 of 68
Cost Saving
Per Year
(Rs)
1,132,500
1,598,400*
776,250
3,507,150
IT and Other Equipment
Air Conditioning Load
Lighting
-
5,000
10,000
15,000
20,000
25,000
30,000
Figure 2: Graphical Representation of Energy Saving Potential per Month
IT and Other Equipment
Air Conditioning Load
Lighting
-
50,000
100,000 150,000 200,000 250,000 300,000 350,000 400,000 450,000
Figure 3: Graphical Representation of Energy Saving Potential per Month PKR per Month
The detail analysis about savings is explained in Chapter 5.
2 “A” Block Secretariat - Building characteristics and
General operational Features
The building was constructed as per the master plan which was developed by the Athensbased firm Doxiades and Associates for Islamabad. Commissions for individual structures
were given to many international architects. The Government Secretariat Buildings were the
first official structures to be constructed. These buildings were to house the offices of all
government ministries and form the nucleus of the capital's Administrative Centre.
“A” Block Secretariat building located at Pak secretariat Islamabad is six-storeys building in
which following Ministries are housed.
“A” Block – Energy Audit | www.sharifinternational.net
Page 10 of 68
1) Ministry of Industries and Production
2) Ministry of Water and Power
3) Ministry of Petroleum and Natural Resources
4) Ministry of Commerce
With the passage of time as informed by the CDA officials that electrical load demand for
“A” Block Secretariat increased manifolds due to installation and usage of more electrical
appliances such as electric heaters, photocopier, desktops and laptops etc furthermore due
to over occupancy the cooling and heating load also contributed to an increase of electrical
load demand.
Foregoing in view, the electrical wiring of “A” block was again laid down and single phase
supply of “A” Block Secretariat was converted to three phase system. The operation and
maintenance of all the blocks located at Pak Secretariat Islamabad including “A” block is
being done by Capital Development Authority (CDA) officials. For all the blocks located at
Pak Secretariat only one electrical person was well aware of all the electrical wiring layouts.
CDA officials can carry out the activities which are limited to floor wise Low Tension(LT)
Distribution panels and for retrofitting of lighting fixtures only.Normal office timing as per
Government rules of Pakistan are form 8:00 am to 4:00 pm. Saturday and Sunday are
observed as holidays.
The Secretariat Buildings are bundled into two groups; each group consisting of four Lshaped blocks connected by circulation bridges. Blocks are expressed by vertical elements
that house staircases and elevators, and differentiated by the number of office floors per
block (four or six) and the façade treatment (determined by solar orientation). The
interrupted lines in the building's massing against the skyline of the mountains in the
background tie the architecture to the landscape. The office floor plans are flexible, allowing
for transformations in the Ministries themselves.
South-east and north-west walls are exposed to the sun in the mornings and afternoons
respectively. Orientation is with the longer axis of the building running east – west and also
North-South.
“A” Block – Energy Audit | www.sharifinternational.net
Page 11 of 68
Buildings designed between the existing mature trees and mountains on the North side with
frame structured building. It is a six storey building with longer facades: N-S & E-W and
Window openings towards: N-S & E-W Windows areas are protected to some extent from
direct solar radiation by being recessed by 30 inches from the external wall surface.
Figure 4:”A” Block Secretariat (Building Perspective from the Aerial View)
3 Energy Systems in “A” Block Secretariat
3.1 Electricity
It was noted that the building has A-1 Tariff Structure and a sanctioned electrical load of 90
kVA. Automatic changeover switch was used to run load from one of the two feeders for the
continuous supply of electricity which is out of order now and this problem has been
catered by manual switching of changeover. As per nameplate data, 750kVA SIEMENS
transformer energizes the block.
It was observed that the building do not have an assigned electric meter for every floor to
measure the units consumed and the monthly electricity bills are being generated on
estimated basis which could be seen in table 4 below. From the table it could also be seen
that there was not too much variation in the quantity of units consumed and even no
impact of seasonal variation and subsequent increase / decrease in demand of electricity
was noticed. Upon investigation From CDA designated official it was told that the meter is
not functional for many years and it was already in their notice and no such corrective
actions has been taken yet to replace faulty meter.
“A” Block – Energy Audit | www.sharifinternational.net
Page 12 of 68
Main applications of electrical energy include air-conditioning units, lighting fixtures and
passenger lifts as well as office equipment including desktops, heaters etc. A month-wise
table depicting units consumed and amount paid by CDA for each respective month of year
2016 is given below.
Electricity Bills
Bill Month
(2016)
Units Consumed
(kW/h)
MDI
Meter
Reading
Monthly Bill
incl. of GST etc
(Rs)
Power
Factor
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Total
Average
148,800
139,717
140,278
140,796
141,322
141,817
142,270
142,712
143,143
143,561
159,200
143,965
1,727,581
143,965
-
5,279,579
2,605,293
2,730,816
2,724
2,733,217
2,821,815
-,230,756
3,915,449
2,530,600
3,236,156
6,210,230
31,763,252
2,646,938
-
Payment
6,234,756
2,605,293
5,461,632
2,724
2,733,217
2,821,815
4,330,490
2,530,600
5,662,310
Average
Unit Cost
(Rs-
Table 4: Historical Electrical Bills
3.2 Natural Gas
The building’s natural gas is provided by Sui Northern Gas and Pipe line limited (SNGPL)
which is used to mainly operate geysers which are used to heat up water used in
washrooms. As a result, the use of natural gas in the building was minimal. When the liaison
officers were requested to handover the natural gas bills, the energy audit team were told
that they had no record of natural gas bills in their possession. In winters heating in rooms is
mainly done through electric heaters instead of gas heaters.
3.3 Energy Utilization By Types
At the moment grid electricity is the primary energizing source for “A” Block Secretariat.
Hence, grid electricity provides 100% of the power requirements when available. In order to
get uninterrupted supply of electricity, the feeders from Mangla Dam and the other from
Tarbela Dam are switched through manual changeover in case if anyone of them undergoes
load shedding.
“A” Block – Energy Audit | www.sharifinternational.net
Page 13 of 68
4 Energy audit findings
As a part of the Energy Audit, the following building systems/areas were surveyed and
findings were recorded:
1.0
Historical Energy Bill Analysis
2.0
Lighting System
3.0
Lighting Controls
4.0
Equipment and Appliances
5.0
Air-conditioning Units
6.0
Mass Transportation Systems (Elevator)
7.0
Building Envelope/Ventilation
8.0
Fire Protection
4.1 Energy Efficiency and conservation opportunities
it was found out upon interaction with relevant focal persons of every ministries nominated
by the respective ministries to assist in conduct of Energy Audit at their respective floor that
they were not aware of the electrical energy consume at their floors and the amount of the
bills being paid, even though at certain floor energy efficient light such as T-5 Rods, LED
Tube Rods etc. have been installed but the impact of energy savings have not being
documented. It was found out that in order to have proper sub-metering of each floor, first
step is to launch energy efficiency and conservation drive at “A” Block Secretariat which
could further being replicated in other such blocks located in Pak Secretariat Islamabad.
Negligible energy conservation practices were being implemented in A-Block secretariat
which left for a lot of room for energy conservation.
Other possible avenues for conservation and activities related to them are outlined in
‘Chapter 5 – Energy Conservation Opportunities’.
4.2 Energy utilization
As per Section ‘3.3 - Energy Utilization by Types’, electrical energy is the main form of
energy being used at A-Block Secretariat. Electrical energy constitutes approximately 99% of
all energy costs incurred to CDA for the respective block and up to 1% of the total energy
costs is associated with the use of natural gas.
The bulk of electrical energy is consumed by Air-conditioning, office equipment and lighting.
Whereas gas geysers are the main source of natural gas consumption. All the equipment
categories are individually discussed in detail.
“A” Block – Energy Audit | www.sharifinternational.net
Page 14 of 68
4.2.1 Historical Electrical Bill Analysis
As per the graphical representation specified in section 3.1, bar chart showing the electrical
energy consumption trend is shown below in figure 5.
Units Consumed (KW/h)
160,000
155,000
150,000
145,000
140,000
135,000
130,000
125,000
Jan
Feb
Mar
Apr
May
Jun
Jul
Aug
Sep
Oct
Nov
Dec
Figure 5: Graphical Representation of Month-wise Electrical Consumption
Main applications of electrical energy include air-conditioning units, lighting fixtures and
passenger lifts as well as office equipment including desktops, heaters etc. A month-wise
table of estimated electrical bills for the last 12 months and its graphical representation is
already shared in section 3.1
A word on MDI Penalty
PEAK Vs. OFF-PEAK
Power consumption is typically represented by kilowatts or kW. Utility and power
distribution companies typically charge by kW, however, different rates apply to the time of
use – peak demand usage versus off-peak usage.
Even though there wasn’t any MDI penalty being applied on A-Block Secretariat, the concept
of power factor has been explained below to give a better understanding of power factor
penalty, demand charge and MDI penalty.
“A” Block – Energy Audit | www.sharifinternational.net
Page 15 of 68
POWER FACTOR
A very important element in understanding energy use and distribution is the power factor
or, in simple terms, how much effort it takes to push electricity through a building or power
grid. The power factor indicates how efficiently a building accepts and uses electricity.
Power Factor = Active power/Apparent power = kW/kVA
= Active power/(Active Power + Reactive Power)
= kW/(kW + kVAr)
Higher kVAr indicates low power factor and vice versa. In electrical terms kW, kVA, and kVAr
are vectors and must be summed.
Figure 6: Vector Diagram explaining power factor
Power factor is the ratio of true power or Watts to apparent power or Volt Amps, so the
theoretical best value for a power factor is one (on a scale of zero to one). In an electric
power system, a load with a low power factor draws more current than a load with a high
power factor for the same amount of useful power transferred. The higher currents increase
the energy lost in the distribution system and require larger wires and other equipment.
Because of the costs of larger equipment and wasted energy, electrical utilities will usually
charge a higher cost to industrial or commercial customers where there is a low power
factor.
Based on the above explanation of electricity there are two kinds of loads i.e. Resistive
Loads (lights, water heaters, coil heaters, etc.) and Inductive Loads (anything which has a
motor viz. ceiling fan, water pump, air conditioners, refrigerators and so on). Resistive load
get what they ask for. But inductive loads need extra current used up to create a magnetic
field which is like “froth” and is not really useful as it is not used for doing actual work. The
“A” Block – Energy Audit | www.sharifinternational.net
Page 16 of 68
ratio between the “actual work” that you get and the total energy supplied by the utility is
called the power factor (PF).
If the power factor was 1 or close to 1 then a one HP motor would take one HP equivalent
power from the utility, but in reality it has to draw more energy from the utility so there is a
penalty for it, which is called Power Factor Penalty. And formula for power factor is defined
as:
PF = kW (kilo Watt)/kVA (kilo Volt Ampere)
How can Power Factor Penalty be avoided?
Power Factor can be improved by switching over to more efficient appliances that give more
output power (W) per unit (VA) of energy used. The other way to fix the problem is by
installing Capacitor Banks (sold as Power Savers or Power Factor Correction Panels).
Capacitive load is opposite to inductive load and negates the inductive load when added in
parallel. Power factor can be increased up to 1 or at least 0.95 to 0.99 by installing
appropriate capacitor banks.
Demand Charge and MDI penalty
When you sign up for commercial electricity connection from a utility grid company like
GEPCO, you have to specify the maximum ‘demand’ (in kVA) that you need. During any
given month if maximum demand is exceeded a penalty (or extra price) has to be paid for
the same. That is the MDI penalty that appears on the electricity bills. The MDI is the
maximum power value, usually the average of 15 minutes, reached during the billing period
(this average time may vary depending on the country). Once the value is higher than the
contracted power, the customer will pay a penalty on the electricity bill
Maximum Demand Calculation
The maximum demand value is the average from the instantaneous power (in kW or kVA)
during a defined time interval, usually every 15 minutes. There are different methods to
calculate this parameter:
Fixed window (Block window)
This is the maximum demand calculation during a defined interval (usually every 15
minutes). Once the data is obtained, the value is stored and it makes a reset to start a new
calculation for the next 15 minutes. This 4 registers will be measured every hour.
“A” Block – Energy Audit | www.sharifinternational.net
Page 17 of 68
Sliding Window
This is the maximum demand calculation during a defined interval (usually every 15
minutes). Once the data is obtained, it will wait one minute to start a new 15 minutes
calculation. This means that every minute (this time can depend on the meter) it will record
one maximum demand value from the last 15-minute period. This 60 registers will be
measured every hour.
How can MDI penalty be avoided?
✓ If your power factor is less than 1 you can improve your output kW per KVA supplied
by improving power factor as mentioned above. This ensures that you are not
wasting any kVA that is supplied to you by your utility.
✓ Another option of avoiding MDI penalty is by shifting your peak load to a time of day
when your other load is less.
✓ If more kW or kVA is being used than the grid utility sanctioned load then one either
needs to switch to more efficient appliances (i.e. the ones using less kWhs) so that
the total need matches demand, or if it is felt that already the most efficient
appliances are in use then one can request the utility company to increase the
maximum demand already allotted. If it is felt that increasing the sanctioned load
ceiling is not possible or difficult than Maximum Demand Control Equipment could
be utilised to automatically switch OFF non-essential loads on case based scenarios
for different times of the day. For example the Circuitor® MDC 4 is perfect for those
installations which need a basic maximum demand control. Following some easy
configuration steps the user will define up to 4 maximum power levels to start
disconnecting non-critical loads.
Furthermore, MDC 4 incorporates an internal power analyser for the maximum demand
calculation (it also records electrical parameters such as voltage, current and power). Every
time MDC 4 detects a power excess, this will disconnect several lines with non-critical loads,
reducing automatically the instantaneous power. This will ensure that the installation will
not exceed the maximum demand limit, hence avoiding penalties on the next electricity bill.
“A” Block – Energy Audit | www.sharifinternational.net
Page 18 of 68
Figure 7: Operation method of MDC 4
➢
Avoids maximum demand penalties
➢
Avoids power peaks due to simultaneity
while connecting loads
➢
Helps to adjust the contracted power to
the real situation
➢
Manages up to 4 relay outputs
➢
Built in power analyser
➢
Internal clock for power synchronization
Figure 8: MDC 4
“A” Block – Energy Audit | www.sharifinternational.net
Page 19 of 68
4.2.2 Luminaries
Luminary load contributes approximately 9% to the total electrical load of A-Block
Secretariat. The bulk of illumination is provided by Fluorescent Tube Lights (FTLs) and
Compact Fluorescent Lamps (CFLs).
FTLs: Fluorescent Tube Lights (FTL’s) were the most used luminary in the building and
contributed to 95% of the total luminary load. FTLs are a low pressure mercury vapor gasdischarge lamp that use fluorescence to produce visible light. As compared to other
luminaries installed in A-Block Secretariat, FTLs have the lowest lumens to watt ratio and
therefore they are the least energy efficient. FTLs contributing such a significant amount to
the luminary load is an area which requires attention as there is a lot of energy conservation
potential in it.
CFLs: Compact Fluorescent Lamps (CFLs) contributed to 4% of the total luminary load. CFL
use a tube which is curved or folded to fit into the space of an incandescent bulb and a
compact electronic ballast in the base of the lamp. Though these are considered quite
energy efficient, the new LED technology is gradually taking over as it is a higher lumen to
watt ratio and therefore it is more energy efficient.
LED Panels: An LED lamp is a light-emitting diode product which is assembled into a lamp for
use in lighting fixtures. It is the presently the most energy efficient luminary source as its
lifespan and electrical efficiency is significantly greater than incandescent and fluorescent
lamps. LED panels were the least used luminary source.
The newer LED Panels come in round, square and rectangular shapes and in different sizes
and power denominations to suit every situation. The best part is that their prices have also
dropped significantly so as to be affordable by almost everyone.
Tabular and graphical representation of summary of total installed lamps, luminary
quantities vs total load and floor-wise summary of total luminary load has been shared
below.
“A” Block – Energy Audit | www.sharifinternational.net
Page 20 of 68
Summary of Installed Lamps
Wattage
Total
Energy
Luminary Detail/Technology
Hours
per
Luminaries
Consumed
Type
Qty
Used/Day
Lamp
Load
Luminaries
(FTL/CFL/HPS/LPS/MH/MV/GLS)
(Hours)
(Watts)
(Watts)
(Wh)
FTL Tube Light (36W)
36
1,308
47,-,704
FTL Tube Light (18W)
18
454
8,172
8
65,376
CFL Energy Saver (25W)
25
101
2,525
8
20,200
LED Lights
12
LED Panel-,800
SMD Rods
18
Total
58,010
464,080
Table 5: Summary of Total Installed Lights
Types of Luminaries with respect to Load in Wh
1%
0% 0%
4%
14%
81%
FTL Tube Light (36W)
FTL Tube Light (18W)
CFL Energy Saver (25W)
LED Lights
LED Panel
SMD Rods
Figure 9: Daily Calculated Energy Consumed By Luminaries (Watt hours)
“A” Block – Energy Audit | www.sharifinternational.net
Page 21 of 68
Luminaries Quantities vs Total Lighting Load
Summary-
400,000
350,000
300,000
250,000
200,000
150,000
100,000
50,000
FTL Tube Light
(36W)
FTL Tube Light CFL Energy Saver
(18W)
(25W)
Wattage per Lamp (W)
Qty
LED Lights
LED Panel
SMD Rods
Power Consumed Luminaries (Wh)
Figure 10: Summary of Lighting Load
Floor-wise Summary of Total Luminaries Load
Floor
Total
Luminaries
(W)
Energy
Consumed
Luminaries
(Wh)
Ground
3,600
28,800
1st Floor
10,868
86,944
2nd Floor
11,628
93,024
3rd Floor
9,594
76,752
4th Floor
10,728
85,824
5th Floor
5,976
47,808
6th Floor
5,616
44,928
58,010
464,080
Total
Table 6: Floor-wise Summary of Total Luminaries Maximum Connected Load
“A” Block – Energy Audit | www.sharifinternational.net
Page 22 of 68
Floor-wise Power Consumed by Luminaries (Wh)
500,000
450,000
400,000
350,000
300,000
250,000
200,000
150,000
100,000
50,000
Ground
1st Floor 2nd Floor 3rd Floor 4th Floor 5th Floor 6th Floor
Total
Summary
of Installed
Lamps
Power Consumed Luminaries (Wh)
Figure 11: Floor-wise Power Consumed by Luminaries
A general summary of the luminaries has been summed up in the following table.
Q No.
1
Question
What
is
Answer
the
Recommendation
main
technology type of majority Mostly
Need to switch to brighter and more
of luminaries installed on FTLs
efficient solid state luminaires.
site?
2
How old are the luminaries
in general?
3
No info
Is focused lighting method
implemented
when
suitable, instead of lighting
No
Effort to use focused lighting method
should be made.
the whole room?
4
Due to the building layout, utilization of
Is natural light utilized?
Modera
sunlight in the corridors is not an option.
tely
However, natural light can be utilized in
rooms.
6
Can natural light utilisation
be maximized?
7
Is
signage
installed
Yes
Solar tubes utilising total internal reflection
concept could be experimented with.
to
remind the users to switch
off the lights when they are
No
There has to be an engaging reminder near
every switch.
no longer needed?
“A” Block – Energy Audit | www.sharifinternational.net
Page 23 of 68
Does the organisation have
8
programmable lighting
No
(timers)?
9
How often is the luminary
source cleaned?
Never
Timers could help control wastage
stemming from unattended lights.
Monthly cleaning of fixtures can work
wonders for addressing light depreciation.
Some forms of luminaires could be dimmed
10
Does the organisation have
light dimming devices?
No
if fitted with dimmable/DALI PSUs. They
can provide up to 60% saving through
timed dimming.
Are the lights connected to
11
photoelectric/daylight
sensors or motion sensors
No
Automatic switching OFF of lights could
provide up to 30% savings.
to increase efficiency?
Table 7: Summary of Luminary Details
“A” Block – Energy Audit | www.sharifinternational.net
Page 24 of 68
4.2.2.1 Lighting controls
Some general observations regarding the lighting controls are listed below.
•
A single switch is utilized to turn ON many lights simultaneously, which results in a
huge wastage of electrical energy even if a single person is occupying a room.
•
No occupancy sensors are installed in sparsely populated rooms and areas like
toilets, again resulting in energy wastage for long hours.
•
There is no awareness signage displayed in appropriate points reminding the staff to
turn on the lights only when required and to switch off the lights when not needed.
4.2.2.2 Lux Levels
Lux levels were calculated at various locations where different actions were being
performed and matched with the international standards. The lux levels varied between 200
and 300 lux which is acceptable. However, rooms facing the southern side had lux levels
around 700 lux with the lights switched on and around 400 lux with the lights switched off.
This was because the light from the sun directly enters these rooms. This provides an energy
saving opportunity if the lighting in these rooms is used intelligently.
4.2.3 Electrical Appliances
Majority of the load in the electrical appliances category came from electric heaters, fans,
desktops and photocopying machines. Though some of the appliances such as photocopying
machines and TVs were not used continuously for 8 hours, it has been assumed in this
energy audit that they are used for 8 hours daily in order to calculate the load in the worst
case scenario.
Heaters: Electric heaters, blowers and radiators made up 49% of the total electrical
appliances load. There was no maximum set time for the operation of these heaters and the
rooms were not properly insulated. This resulted in a lot of energy wastage.
Desktops: 24% of the total electrical appliances load was due to desktops. If we are to follow
the trend elsewhere in the world pretty much everyone is using a laptop or a notebook
computer due to its many benefits including but not limited to lower power footprint,
portability, compactness etc. In this sense the PC at A-Block in conjunction with LCD
consume approx. 175 – 200W each, which although is not a big figure but given the fact that
they stay switched ON eight hours continuously ends up in a higher electricity bill. As such
even if 65W is saved per computer through switching to a portable laptop we stand to gain
65W x 276 Desktops = 960W savings immediately. The same translates to approx. 144KW
per day.
“A” Block – Energy Audit | www.sharifinternational.net
Page 25 of 68
Energy Saving features implementation on the Desktop PCs was rarely noticed. Features
such putting the monitor in sleep mode and powering down HDD and NICs are readily
available on all Windows versions. Most of the users were not aware of these green
features, whereas the rest do not seem to bother about it. These features when
implemented can help reduce the energy footprint of the building. Take for example the
case of an LCD monitor which consumes a mere 3-4 Watts in sleep mode as compared to its
original 25-50 Watts.
Tabular and graphical representation of summary of total electrical appliances, different
appliances vs total load and floor-wise summary of total appliances load has been shared
below.
Summary of Equipment
Type of Device
Pedestal Fan
LCD TV
Electric Blower
Electric Heater
Electric Kettle
Microwave Oven
Fridge
Radiator
CPU
Monitor
LCD
Printer/Scanner
Projector
Photocopy Machine
Fax Machine
Water Dispenser
Total
Wattage Per
Device(Watts-
Qty
Total
Load(Watts)
Hours
Used/Day
-
11,660
2,795
50,000
61,500
36,000
16,000
6,250
9,600
41,400
4,000
5,900
8,-,000
3,-,035
-
Table 8: Summary of the Total Electrical Appliances Connected Load
Room-wise data referred by CDA official is placed at appendix 6.1
“A” Block – Energy Audit | www.sharifinternational.net
Page 26 of 68
Total Load
(Watt
Hours)
93,280
22,360
400,000
492,000
72,000
32,000
50,000
76,800
331,200
32,000
47,200
65,600
5,280
224,000
30,000
2,496
1,976,240
ELECTRICAL APPLIANCES LOAD DISTRIBUTION (WH)
Fax Machine
2% Water Dispenser
0%
Photocopy Machine
11%
Pedestal Fan
5%
LCD TV
1%
Projector
0%
Printer/Scanner
3%
LCD
2%
Electric Blower
20%
Monitor
2%
CPU
17%
Radiator
4%
Mircowave Oven
2%
Electric Heater
25%
Fridge
2%
Electric Kettle
4%
Figure 12: Graphical Representation of the Total Electrical Appliances Load
Equipment Quantities vs Total Load (Wh)
2500
600,000
2000
500,000
400,000
1500
300,-
200,000
212
43
25
123
276
30
8
20
8
40
236
164
4
28
0
25
8
100,000
-
Wattage Per Device/Watt
Qty
Total Load/Watt Hours
Figure 13: Electrical Appliances Power Rating vs Total Load
“A” Block – Energy Audit | www.sharifinternational.net
Page 27 of 68
Floor
Peak Load Summary
Total
Total Electricity
Connected
Consumption/Day
Load
(Watt Hours)
(Watts)
Ground Floor
19,360
2,420
40,500
324,000
43,045
344,360
39,925
319,400
58,985
471,880
38,090
304,720
6th Floor
24,065
192,520
Total
247,030
1,976,240
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
Table 9: Floor-wise Appliances Connected Peak Load Summary
500,000
450,000
400,000
350,000
300,000
250,000
200,000
150,000
100,000
50,000
Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
6th Floor
Figure 14: Graphical Representation of Floor-wise Summary of Appliances Connected Peak
Load (Watt Hours) Summary
4.2.4 AC Units
The air conditioning load was alarmingly high and contributed to 53% of the total electrical
load. This was because most of the installed ACs were window type which consume twice as
much energy as the split-type ACs which are based on a more energy efficient inverter
technology.
Energy Audit findings show that 74 window-type ACs and 69 split-type ACs were installed
and window-type ACs contributed to 64% of the total AC load compared to split-type ACs
“A” Block – Energy Audit | www.sharifinternational.net
Page 28 of 68
36%. A huge chunk of energy can be saved from the air-conditioning load. Details of how to
save the energy are given in the next chapter.
Tabular and graphical representation of summary of total air-conditioning load, airconditioning units vs total load and floor-wise summary of total air-conditioning load has
been shared below.
Summary of AC Units
Cooling
Total
AC Unit
Total
Capacity
Hours
Load
Description with
Power Rating/Watt Quantity
Load
(Tonnage
Used/Day
(Watt
Brand Name
(Watts)
per AC)
Hours)
Window-type AC's
National-,-,000
General-,-,000
LG-,-,000
ACMA-,-,000
Total window-type AC load
74
222,000
1,776,000
Split-type AC's
Mitsubishi (1.5 ton-,-,000
Mitsubishi (2 ton-,-,000
Ascon (1.5 ton-,500
8
60,000
Ascon (4 ton-,-,000
PEL (1.5 ton-,000
8
48,000
Sabro (1.5 ton-,000
8
96,000
Waves -,000
8
80,000
Kenwood (1 ton-,000
8
72,000
Fujia (1.5 ton-,000
8
72,000
Samsung (1.5 ton-,500
8
12,000
Orient -,000
8
72,000
Total split-type AC load
69
125,500
1,016,000
Total AC Load
143
347,500
2,792,000
Table 10: Summary of AC unit Load
“A” Block – Energy Audit | www.sharifinternational.net
Page 29 of 68
Graphical Representation of AC Usage
36%
64%
Window Type AC
Split-Type AC
Figure 15: Graphical Representation of AC Units Load
Since the energy audit was conducted in winters, the air-conditioning units were not
operational. Therefore, there conditioning and method of usage could not be studied and
the data collected was a result of questioning from users.
A tabular summary of the data collected is given below.
Q
No-
Question
Is the air conditioning unit older than ten years?
Does the AC have an economic cycle?
How often is it used?
How is it controlled?
At what temperature is the thermostat normally set at?
How is the insulation?
Can the heat producing equipment in the room be
minimized?
In what timeframe does the maintenance of the AC units
take place?
How often service of air conditioning unit is done?
Answer
Mostly
No
All day in summers
Remote
18 degree Celsius
Not properly insulated.
Yes. Kettles and FTLs produce
heat.
No set timeline.
No set timeline.
Table 11: Summary of air-conditioning units
“A” Block – Energy Audit | www.sharifinternational.net
Page 30 of 68
Total Load (Watts)
Floor
Window-Type AC
Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
6th Floor
36,000
39,000
39,000
36,000
39,000
33,000
Split-Type AC
3,000
24,000
26,500
30,500
31,000
6,500
7,000
Total
222,000
125,500
Total Load(Watt Hours)
Window-Type AC
288,000
312,000
312,000
288,000
312,000
264,000
1,776,000
Split-Type AC
24,000
192,000
212,000
244,000
248,000
40,000
56,000
1,016,000
Table 12: Floor-wise Peak Connected load summary of AC Units
600,000
500,000
400,000
300,000
200,000
100,000
0
Ground Floor
1st Floor
2nd Floor
3rd Floor
4th Floor
5th Floor
6th Floor
Figure 16: Graphical Representation of floor-wise Connected load summary of AC units
4.2.5 Mass Transportation (Lifts)
“A” Block has operational passenger lifts which was used to move to different floors. The
lifts drew their motion from 3 phase 10 HP (7.7 kW) motors and had a mass of 650kg which
supported a capacity of 925kg.
Apart from the technical specs mentioned above, the following observations were made
regarding the elevators.
•
This lift operated continuously between 8am and 4pm.
•
The equipment of the elevators (belts, motors etc) was in very good condition.
According to the personnel responsible for its maintenance, the elevators were
installed 5 years ago and were checked weekly.
“A” Block – Energy Audit | www.sharifinternational.net
Page 31 of 68
•
No Regenerative Drive was installed in the elevators. A regenerative drive uses the
motion of the elevator to generate electricity. It is explained in detail in the next
chapter.
4.2.6 Building Envelope/Ventilation
Whenever there are temperature differences between the inner and outer surfaces of any
structure, heat transfer will occur from higher temperature zone to lower temperature
zone. The Building Envelope studies the different aspects of a given buildings’ thermal
characteristics and its insulation is used to indicate the adoption of ways and means,
whereby transmission of heat is minimized. The aim of thermal Insulation is to minimize the
transfer of heat from either side of a building. The building envelope directly affects the
energy performance of a given building in many ways including but not necessarily limited
to:
a. The fenestrations providing necessary protection from undesirable heat gains in
summer month.
b. Capability/means of some desirable heat gain in winter months from the South.
c. Making maximum use of ambient daylight through its at penetration in different
areas.
d. Provision of cross ventilation opportunities.
The energy performance of the building is greatly affected by building envelope in the
following ways:
•
Undesirable heat transfer in summer season due to windows resisting.
•
Desirable heat transfer in winter on the South.
•
Penetration of daylight.
•
Desirable ventilation being blocked in different sections by constructing visitor
rooms.
Bricks, concrete, cavity and cement layers are considered in opaque materials which does
not allow any light to pass through.
Single glass used in windows and curtain walling, which is the source of heat gain is
categorized in translucent materials which passes partial amount of heat and light.
“A” Block – Energy Audit | www.sharifinternational.net
Page 32 of 68
Most of the air conditioned and non-air conditioned areas that were observed has wall
construction layers of cement on the inside and outside Concrete blocks, cavity, brick and
cement.
Figure 17: Cavity Wall
The roof layers provided by CDA; cement layer RCC Foam concrete with polythene large
sheet / fibre glass. Window data along with its frames were directly estimated and observed
by the audit team. Almost all of the windows in the facility consisted of single glazed
windows on a metallic panel frame (mostly 3’x6’ and 4’x6’), in both air conditioned and nonair conditioned areas.
Orientation
The main factor under which the building orientation is studied is the daily path of the sun
through the sky and the pattern by which this changes through the year besides this
windows orientation also plays an important role in heat transfer moreover in most cases,
sitting arrangement/orientation is not to utilize the sunlight. During day time it has been
observed that artificial light is being used instead of making use of day light. As per
measurements for a room which is availing maximum sunlight, lighting level is 680 lux
whereas for shaded room, lighting level is 300 lux.
South-east and north-west walls are exposed to the sun in the mornings and afternoons
respectively. Orientation is with the longer axis of the building running east – west and also
North-South.
“A” Block – Energy Audit | www.sharifinternational.net
Page 33 of 68
The south, east and west walls are exposed to the sun in the mornings and afternoons
respectively. Building wing facing east and west receive less solar radiation during the
summer months. The windows are protected from direct sun rays with pillar and by
arranging shading element (overhang). Heating by direct sunlight is thus reduced.
The South face of the buildings gains solar heat in the winter. It exposes the windows to the
low winter sun and is shaded to protect it from summer sunshine. Walls that face the south
and west, gain summer heat till 02:30 p.m., whereas west and north are exposed to sun in
the afternoon. South and East−west façades receive higher intensity of solar radiation
throughout the year.
It is observed that shaded walls have temperature of 32ºC and the walls directly exposed to
sunlight have up to 40ºC, resulting in higher heat gain and increasing the AC load. Thermal
insulation is the dominant factor to determine the external heat gain but due to the absence
of materials and specific knowledge and building codes, buildings are made without any
thermal insulation, which increases the AC/cooling and heating load in summer season.
It is observed that during summers heat gain on the first and second floors increases due to
heat transfer through radiation from the hard ground surface. It is observed that due to the
compact geometry of the building, conduction gains from the building envelope as well as
solar gains from windows are the least in comparison to other building geometries.
4.2.7 Fire Protection
Fire hydrant pump systems (also known as fire pumps, hydrant boosters, fire water pumps)
are high pressure water pumps designed to increase the firefighting capacity of a building by
boosting the pressure in the hydrant service when mains is not enough, or when tank fed.
Fire Protection systems are available in diesel and electric drive configurations, assembled
on a common fabricated base with pipework manifolds, valves, controls and accessories to
provide a fully automated system
For a fire hydrant system to function properly many detectors are required to provide
information to the fire control panel. These include but are not necessarily limited to:
1. Ionisation smoke detectors;
2. Optical smoke detectors;
3. Rate of Rise Heat Detectors;
4. Fixed temperature break glass type detectors and so on.
“A” Block – Energy Audit | www.sharifinternational.net
Page 34 of 68
A-Block Secretariat looked well equipped to combat fire if God-forbid any such situation
arose. Each floors had two fire hydrant pumps and 4 fire extinguishers. This firefighting
equipment was well maintained and according to the firefighting department it was checked
yearly and maintained monthly.
However, when it came to fire detection, the system installed in A-Block secretariat was
quite obsolete. No smoke detectors were installed to detect fire, but instead an emergency
button was installed in the corridor of each floor which was connected to a screen at the
entrance of the building. This screen would inform the firefighter on which floor had the
emergency button been pressed. This method is very unreliable as it requires manually
alerting the firefighting team that a fire has spread out in the building. In an emergency,
relying on untrained people is highly unadvisable.
In case of any fire incident the building does not seem to have any fire
detection facility and will be totally dependent on timely outside
assistance or to manually start Fire Hydrant System.
4.2.8 Electrical Safety
Most of the electrical hazards that take place are overloading and improper wiring, earthing
and insulation. Therefore, to study the electrical safety of the factory, the following
activities were carried out.
•
Thermal Imaging
Thermal Imaging was done on transformer and low tension distribution boards.
Thermal Imagining helps in identifying overloading. The pictures taken did not show
any overloading. Few pictures of the thermal imager are shared below.
“A” Block – Energy Audit | www.sharifinternational.net
Page 35 of 68
Visible Light Image
Figure18: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 19: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 36 of 68
Visible Light Image
Figure 20: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 21: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 37 of 68
Visible Light Image
Figure 22: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 23: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 38 of 68
Visible Light Image
Figure 24: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 25: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 39 of 68
Visible Light Image
Figure 26: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 27: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 40 of 68
Visible Light Image
Figure 28: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 29: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 41 of 68
Visible Light Image
Figure 30: Thermal and Original Image of a distribution
board
Visible Light Image
Figure 31: Thermal and Original Image of a distribution
board
“A” Block – Energy Audit | www.sharifinternational.net
Page 42 of 68
Visible Light Image
Figure 32: Thermal and Original Image of a distribution
board
Since the energy audit was conducted in winters. “A” Block Secretariat wasn’t operating on
its maximum load and the thermal imaging results can’t be taken as conclusive.
•
Earthing Tests
In electricity supply systems, an earthing system or grounding system is circuitry which
connects parts of the electric circuit with the ground, thus defining the electric potential of
the conductors relative to the Earth's conductive surface. The choice of earthing system can
affect the safety and electromagnetic compatibility of the power supply. In particular, it
affects the magnitude and distribution of short circuit currents through the system, and the
effects it creates on equipment and people in the proximity of the circuit. If a fault within an
electrical device connects a live supply conductor to an exposed conductive surface, anyone
touching it while electrically connected to the earth will complete a circuit back to the
earthed supply conductor and receive an electric shock.
As explained earlier, earthing is a very important factor in electrical safety. To check
whether the equipment has been properly grounded, earthing tests were carried out at
different places. The earthing tests showed that the impedances were below 5 ohms which
is according to international standards is considered safe.
•
Studying of the Wiring and LT Distribution Box
The wiring was also studied during the inspection of the electrical safety. This study included
the inspection of wires with respect to the load that it carried and whether it was properly
“A” Block – Energy Audit | www.sharifinternational.net
Page 43 of 68
insulated or not. Though the wires were installed in accordance with the load but the
insulation was a concern at a few places.
Figure33: A huge opening untidy and risky in the bathroom of second floor
The LT Distribution Box as depicted in the picture above is located directly besides
the opening of bathroom. In case of water leakage can drip into the LT box, this
can lead to short circuiting which can not only destroy the LT Distribution
Equipments, it can also cause electric shock and sparking which can cause an explosion.
4.2.9 General Observations
Some of the general observations made during the energy audit were as follows:
•
The distribution boards and switchgears were not tagged.
•
Most of the distribution boards and switchgear was maintained and the wiring was
tidy.
•
Thermal imaging did not show any overloading but since the energy audit was
conducted in winters, they were not working on their maximum load so therefore
this evidence cannot be taken as conclusive.
•
The building was not properly insulated and had several leakages.
•
The windows were not tainted which reduces protection from heat in summers.
•
There was no vegetation nearby which provided cover from the sun.
•
There was very little indoor vegetation.
“A” Block – Energy Audit | www.sharifinternational.net
Page 44 of 68
•
Most rooms in offices were occupied by multiple incumbents.
•
There were no set dates for the use of AC’s and heaters.
•
There was no formal energy conservation plan for the employees.
•
There were no signage installed to remind the staff to use energy more intelligently.
•
There was no energy management staff assigned the task of energy saving.
Few pictures supporting the observations have been attached on the following page.
Figure 34: Untidy Wiring in Distribution boards
Figure 36: Old and inefficient System
Figure 35: Untidy and not tagged wires
Figure 37: No Indication on MCBs
5 Energy Conservation & Maintenance Opportunities
“A” Block – Energy Audit | www.sharifinternational.net
Page 45 of 68
5.1 Recommendations with Conservation Estimates & ROI
5.1.1 Luminaries
As mentioned in the previous chapter, most common luminary used were FTLs. Even though
FTLs are energy efficient, they are now being replaced by a more advanced LED technology
is significantly more efficient.
As a result such a wide scale usage of FTLs is not recommended during the current times.
However, to keep the budget under control, rather than replacing all the legacy lighting at
once a policy may be considered whereby all the luminaries that fail should be replaced by a
newer technology. By this way over a certain period of time all the luminaries will be
replaced. Considering the relatively smaller useful lives of FTLs the change could happen in
less than a year.
Working regarding the replacement of FTLs is shown in the tables below.
Type of Equipment
Wattage
(Watts)
Qty
FTL Tube Light (36W)
36
FTL Tube Light (18W)
CFL Energy Saver
(25W)
18
-
25
101
Hour
s
Used
(H)
Power
used
per Day
(kWh)
8
376,70
4
65,376
8
20,200
8
Electricit
y
Cost/kW
h (Rs)
15
Electricit
y Cost
per Day
(Rs)
5,650,56
0
980,640
Electricity
Cost per Year
(250 days) (Rs)
1,412,640,00
0
245,160,000
15
303,000
75,750,000
15
Table 13: Most common luminaries
Replacing FTL Tube Light (36W) with LED Panel
Hours
Wattage
Quantity Used
(Watts)
(H)
Type of Equipment
FTL Tube Light (36W)
36
1408
8
LED Panel
14
1408
8
Difference
Power
used
per
Day
(kWh)
406
158
Electricity Electricity
Cost/KWh Cost per
(Rs)
Day (Rs)
15
15
248
6,083
2,365
3,717
Table 14: Replacing FTL Tube Light (36W) with LED Panel
“A” Block – Energy Audit | www.sharifinternational.net
Page 46 of 68
Electricity
Cost per
Year (250
days) - (Rs)
1,520,640
591,360
929,280
Return of Investment
Total Cost for Installation of LED Panels (Rs)
ROI (Years)
2,534,400
2.73
Table 15: ROI Calculation
FTL Tube Light (36W) vs LEDPanel
Electricity Cost per Day (Rs)
Power used per Day (KWh)
Wattage (W)
0
1000
2000
LED Panel
3000
4000
5000
6000
7000
FTL Tube Light (36W)
Figure 38: Graphical Comparison of FTL (36W) vs LED Panel
Replacing FTL Tubelight (18W) with LED Light
Hours
Wattage
Quantity Used
(Watts)
(H)
Type of Equipment
FTL Tube Light (18W)
18
454
8
LED Light
6
454
8
Difference
Power
used Electricity Electricity
per
Cost/KWh Cost per
Day
(Rs)
Day (Rs)
(kWh)
65
22
15
15
43.58
653.76
Table 16: Replacing FTL (36W) with LED Light
Return of Investment
Total Cost for
Installation of LED
Lights (Rs)
ROI (Years)
385,900
2.36
Table 17: ROI Calculation
“A” Block – Energy Audit | www.sharifinternational.net
981
327
Page 47 of 68
Electricity
Cost per
Year (250
days) - (Rs)
245,160
81,720
163,440.00
FTL Tube Light (18W) vs LED Light
Electricity Cost per Day (Rs)
Power used per Day (KWh)
Wattage (W)
0
200
LED Light
400
600
FTL Tube Light (18W)
800
1000
1200
Figure 39: Graphical Comparison of FTL (18W) vs LED Light
Installing an infrared motion sensor can result in energy saving by only supplying electricity
when its senses that a person is present in the room. This can be very efficient in places like
small offices. A feasibility of PIR Detector Kits with an assumed load is given below.
PIR Detector Kits (Estimating for 1 room with 8 FTL's (40W) and 2 pedestal fan (80W))
Cost
Power
Saved
Power
Consumed by
Total
Power
per
ROI
Cost
Consumed
Description
Qty
Pedestal Fan
Power
Saved
Year
(Years
(Rs)
by FTL per
per Day
(kWh)
(kWh)
(250
)
Day (kWh)
(kWh)
days) (Rs)
Infrared Motion
4,-
Sensor
0
Table 18: Feasibility of PIR Detector Kits
5.1.2 IT & Office Equipment
Most of the appliances are of small energy foot print and there isn’t much that can be
recommended other than the fact that energy saving mode should be implemented on
them whereby the LCD Screen goes to standby mode after a given time of inactivity. This no
cost method.
Energy Saved by Using Energy Saving Mode on LCDs
LCD Setting
Wattage
(Watts)
Qty
Without Energy
25
236
Saving Mode
With Energy Saving
4
236
Mode
Anticipated Saving
Electricit
y Cost/
kWh (Rs)
Electricit
y Cost
per Day
(Rs)
Electricit
y Cost
per Year
(250
days) (Rs)
47
15
708
177,000
8
15
113
28,320
595
148,680
Hours
Used
(H)
Power
used
per
Day
(kWh)
8
8
40
Table 19: Energy Saved by Using Energy Saving Mode on LCDs
“A” Block – Energy Audit | www.sharifinternational.net
Page 48 of 68
Cost Intensive Alternative
Most of the computers are in desktop denominations and mostly of older generations
consuming around 175W including small LCD displays. They also take up much more space
and generate more heat as compared to their portable/laptop cousins. Generally an
equivalent capacity laptop only consumes around 110W and that too on intermittent basis
as it is also coupled with an inbuilt backup battery. The falling prices of laptop computers
can make this transition more manageable unlike previously when they were more than
twice as expensive. Also equivalent (even better) capacity & capability laptops that perform
better than existing older PC can be had as pre-owned guaranteed versions further reducing
the upfront cost of change.
Suggested Replacement of PCs 175W with Laptops 110W
Type of
Equipment
Wattage
(Watts)
Quantity
Desktop PC
175
276
Laptop PC
Hours
Used
(H)
Power
used
per
Day
(kWh)
8
8
110
276
Anticipated Saving
Electricity Electricity
Cost/KWh Cost per
(Rs)
Day (Rs)
-
15
15
5,796
3,643
2,153
Electricity
Cost per
Year (250
days) - (Rs)
1,449,000
910,800
538,200
Table 20: Comparison between Desktops and Laptops
Return of Investment
Total Cost for
Installation of Laptops
with previous desktops
exchanged (Rs)
ROI (Years)
4,140,000
7.69
Table 21: ROI Calculation
It was also noticed that Unit 2 did have a few cathode ray tube monitors. These monitors
consume 100W as compared to LCDs which consume 25W. There were forty monitors which
should be replaced. A calculation for the ROI is done in the table below.
Type of
Equipment
Monitor
LCD
Replacing Monitors with LCDs
Power
Hours
used
Electricity Electricity
Wattage
Quantity
Used
per
Cost/KWh Cost per
(Watts)
(H)
Day
(Rs)
Day (Rs)
(KWh-
Difference
24
360
“A” Block – Energy Audit | www.sharifinternational.net
Page 49 of 68
Electricity
Cost per
Year (250
days) - (Rs)
120,000
30,000
90,000
Table 22: Replacing Monitors with LCDs
Return of Investment
Total Cost for
Installation of LCDs (Rs)
ROI (Years)
200,000
2.22
Table 23: ROI Calculation
5.1.3 AC Units
As mentioned in the previous chapter window-type ACs contributed a huge chunk to the airconditioning electrical load. The following tables show a technical and financial comparison
between window-type ACs and split-type ACs and a working calculating the ROI if the
existing window-type ACs are replaced by split-type ACs.
Replacing Window-Type AC's with Split-Type AC's
Type of AC
Wattage
(Watts)
Quantity
Hours
Used
(H)
Window Type
3000
74
8
Split-Type
1500
74
8
Power
used
per Day
(kWh)
Difference
Electricity
Cost/kWh
(Rs)
Electricity
Cost per
Day (Rs)
15
26,640
13,320
1,776
888
15
888
13,320
Electricity
Cost per
Year (88
days) - (Rs)
2,344,320
1,172,160
1,172,320
Table 24: Suggested replacement of window-type AC’s with split-type AC’s
Return of Investment
Total Cost for
Installation of SplitType AC's with Old
Window-Type AC's
Adjusted in Price
(Rs)
ROI (Years)
2,738,000
2.2
Table 25: ROI Calculation
“A” Block – Energy Audit | www.sharifinternational.net
Page 50 of 68
WIndow-Type AC's vs Split-Type AC's
Electricity Cost per Day (Rs)
Power used per Day (KWh)
Wattage (W)
0
5000
10000
Split-Type
15000
20000
25000
30000
Window Type
Figure 40: Graphical comparison of window-type AC’s and split-type AC’s
Target
Area
Pay Back
Recommendations
(ROI)
Years
priority
Forced ventilation can keep the
Moderate - as Autumn is
areas at a comfortable
Ventilation temperature in non A/C areas as
0.5
Moderate
well as improving the indoor air
Set Thermostat at 24-25 deg C
approaching with its
expected lower
temperatures.
quality.
ACs
Action
level
0
High
Immediate
Consider replacement with
Hybrid Solar ACs whereby the
ACs
ACs run on solar for 90% of the
time during the day. Some
Can be considered from the
5-6
Intermedi
ate
versions don’t even require
point of view of cheaper
climate control costs
through lower OPEX.
battery banks
Table 26: AC Units Recommendation
Forced ventilation and keeping a thermostat at 25 degree Celsius along with regular
maintenance can reduce the air-condition electricity consumption by approximately 10%.
With the total air-conditioning load being 2,780,000Wh, saving 10% of the electricity could
result in a monthly saving of around 8340kWh and Rs 125,100.
5.1.4 Mass Transportation (Lifts)
Conservation Aspects Possible on Elevators
There are many advanced energy efficient and energy recovery devices (Regenerative
Converters) available in the market currently which could be considered for possible
induction for the current passenger lift unit. When an electric motor accelerates or
“A” Block – Energy Audit | www.sharifinternational.net
Page 51 of 68
maintains velocity, it consumes energy. But when this same electric motor brakes or
decelerates a body in motion, the motor becomes a generator of energy. This energy has
traditionally been considered a nuisance, but with the invention of integrated regenerative
drives, this “waste” energy is sent back into the electrical grid.
This waste heat is not only inefficient, but can raise the ambient temperatures in elevator
machine rooms and often require additional cooling.
When the DC bus voltage falls back below the threshold, the unit goes into standby mode.
Figure 41: Regenerative Drive Mechanism
Power is consumed in a traction
elevator first, by the gravitational pull
on ascending cabs that are heavier than
the descending counterweight and
second, by the gravitational pull on
ascending counterweights when they
are heavier than descending elevator
cabs.
“A” Block – Energy Audit | www.sharifinternational.net
Power is generated in a traction elevator
first, by the gravitational pull on
descending cabs that are heavier than the
ascending counterweight and second, by
the gravitational pull on descending
counterweights when they are heavier
than ascending elevator cabs.
In the case of power generation, the
mechanical energy of the descending car
or counterweight causes the elevator
motor to function as a generator (or regenerator) of electricity.
The elevator also produces electricity
when the motor works as a braking
system to decelerate. Conventional
elevator systems dissipate this untapped
electricity as waste heat, routing it
through electrical resistors in the elevator
shaft or machine
room, using essentially
Page 52 of 68
the same principle as an electric toaster.
Compared to the same type of elevator without a regenerative converter, this system
provides an energy-saving effect of up to 35%. (Reduction in CO2 emissions: 1400 kg/year) In
addition, the Regenerative Converter has the effect of decreasing harmonic currents.
Instead of using a braking resistor, it is possible to use a line regenerative drive. These
newer drives also have DC bus capacitors and are DC bus coupled to the other VFDs. A
typical such VFD uses advanced software to continuously measure and match the utility line
voltage and frequency. When the DC bus voltage on the system is above a certain threshold
the Regenerative VFD unit activates and it switches its IGBTs on/off to commutate current
back to the line.
Another way to think of the regenerative drive operation is that it enables two-way energy
flow in a VFD system. The regenerated energy can flow back onto the line where it is
typically consumed by other electrical loads in the building or factory. Some new
regenerative drives also have the ability to act as system rectifier. If dimensioned properly,
they can rectify all incoming power and can be DC bus connected to the inverters. This
topology simplifies the charging sequence upon start-up as all input current flows through
the said regenerative VFD.
Besides the net energy savings, another advantage to using a regenerative unit instead of a
braking resistor is that less heat is created. Braking resistors can create a lot of heat,
removing this heat could require an A/C unit, which in turn requires more energy.
Applications like a hoist or an elevator clearly favor regenerative technology and can show
ROI of less than 18 months considering 12 hours operation.
Typical regenerative applications include machines that lift and lower, torque controlled
applications, and cyclic applications. Lifts, hoists, automated storage and retrieval systems,
tension unwinders, and centrifuges are all types of machines that can benefit from
regeneration.
5.1.5 Building Envelope/ventilation
Thermal insulation in buildings is an important factor to achieving thermal comfort for its
occupants. Insulation reduces unwanted heat loss or gain and can decrease the energy
demands of heating and cooling systems. It does not necessarily deal with issues of
adequate ventilation and may or may not affect the level of sound insulation. In a narrow
sense insulation can just refer to the insulation materials employed to slow heat loss, such
as: cellulose, glass wool, rock wool, polystyrene, urethane foam, vermiculite, perlite, wood
fiber, plant fiber (cannabis, flax, cotton, cork, etc.), recycled cotton denim, plant straw,
“A” Block – Energy Audit | www.sharifinternational.net
Page 53 of 68
animal fiber (sheep's wool), cement, and earth or soil, Reflective Insulation (also known as
Radiant Barrier) but it can also involve a range of designs and techniques to address the
main modes of heat transfer - conduction, radiation and convection materials. Many of the
materials in this list deal with heat conduction and convection by the simple expedient of
trapping large amounts of air (or other gas) in a way that results in a material that employs
the low thermal conductivity of small pockets of gas, rather than the much higher
conductivity of typical solids. (A similar gas-trapping principle is used in animal hair, down
feathers, and in air-containing insulating fabrics).
The effectiveness of Reflective Insulation (Radiant Barrier) is commonly evaluated by the
Reflectivity (Emittance) of the surface with airspace facing to the heat source.
The effectiveness of bulk insulation is commonly evaluated by its R-value, of which there are
two - metric (SI) and US customary, the former being 0.176 times the latter. For attics, it is
recommended that it should be at least R-38 (US customary, R-6.7 metric). However, an Rvalue does not take into account the quality of construction or local environmental factors
for each building. Construction quality issues include inadequate vapor barriers, and
problems with draft-proofing. In addition, the properties and density of the insulation
material itself is critical.
Besides the building orientation, the amount of vegetation, especially trees, surrounding the
building is not satisfactory to provide a shading and a pleasing environment. The use of
plants and water are a traditional way of toning down the climate extremes in Pakistan. The
seasonal or high rise trees are not planted nearby to shade the building walls and windows,
an effective way to help remain comfortable during hot summers in Pakistan.
For heating and cooling purposes following things should be adopted in order to save
energy. The areas in the building that are air conditioned are mainly the offices and
conference hall, other areas in the vicinity is ventilated by natural ventilation.
•
ACs are being used without occupancy.
•
Central HVAC not functional.
•
Too many high energy consuming window ACs.
•
Room of top Management were found unoccupied while the utilities were running
or in stand-by form especially electric heaters which consume huge power.
•
The duct outlet for centralized heating and cooling system are open even though
central heating/cooling is out of order for about 20 years.
“A” Block – Energy Audit | www.sharifinternational.net
Page 54 of 68
•
Leakages in Windows, Panes, doors, Ceiling are observed in abundant.
•
Copiers and printers not networked.
•
There is no room entrance isolation chambers.
•
In open plan offices, the air-conditioning and lighting systems can be combined in
such a way that the return air is extracted through the lighting luminaires. This
measure ensures that lesser heat will be directed from the lights into the room.
5.1.6 Fire Protection
As mentioned in the previous chapter,
Fire Alarm System is number of devices working together to detect and warn people
through
visual
and
audio
appliances
when smoke, fire, carbon
monoxide or
other emergencies are present. These alarms may be activated automatically from smoke
detectors, and heat detectors or may also be activated via manual fire alarm
activation devices such as manual call points or pull stations. Alarms can be either motorized
bells or wall mountable sounders or horns. They can also be speaker strobes which sound an
alarm, followed by a voice evacuation message which warns people inside the building not
to use the elevators or defined exit path. Fire alarm sounders can be set to certain
frequencies and different tones including low, medium and high, depending on the country
and manufacturer of the device. Most fire alarm systems in Europe sound like a siren with
alternating frequencies. Fire alarm sounders in the United States and Canada can be either
continuous or set to different codes such as Code 3. Fire alarm warning devices can also be
set to different volume levels. Smaller buildings may have the alarm set to a lower volume
and larger buildings may have alarms set to a higher level
5.1.7 Electrical Safety
Precautions must be taken to protect workers from electric shock, electrocution, fires and
explosions.
•
Precautions when using power
•
Safeguards for electrical supply
Temporary supply switchboards
Electrical equipment inspection
Underground and overhead power lines
Fitting insulation under a suspended floor.
•
•
•
•
Precautions when using power on a building site include:
“A” Block – Energy Audit | www.sharifinternational.net
Page 55 of 68
•
•
•
•
•
Do not overload circuits
Do not used damaged flexible extension cords
Keep flexible extension cords away from sharp edges
Do not use electrical equipment in wet conditions
Use equipment suitable for the working environment, e.g. cordless tools for damp
conditions.
5.1.8 General Recommendations
The recommendations regarding the general observations mentioned in the previous
chapter are as follows:
•
The distribution boards and switchgears should be tagged. This would not only help
in identifying the location of the distribution board and switchgear but it would help
speed up the troubleshooting process.
•
A proper digital meter should be installed as soon as possible in order to pay the
accurate bill as per usage instead of estimated bill.
•
Solar Geysers should be installed in order to conserve natural gas and attain
maximum from solar energy.
•
The distribution boards and switchgear should be tidied up. This would help in
troubleshooting and it would also result in longer life of the wires.
•
Insulate the building properly by covering leakages so that the heat loss is reduced.
•
Taint the windows so that it provides protection from heat in summers.
•
Indoor and outdoor vegetation should be planted to combat the rising temperature
and also to provide much needed fresh air for the labour.
•
Regularly have the walls whitewashed as it increases light refraction and also helps
in fending off heat.
•
Set cut-off dates for the use of AC’s and heaters. This would ensure that AC’s and
heaters are not used absent need.
•
Educate the employees regarding energy conservation by setting up a formal energy
conservation plan.
•
Install signage in halls reminding the staff to use energy more intelligently.
•
Make a committee of energy management staff assigning them the task of energy
saving.
“A” Block – Energy Audit | www.sharifinternational.net
Page 56 of 68
5.2 Alternate Energy Resources Potential
5.2.1 Solar System Potential for Net-Metering
Renewable energy in the form of solar can be utilized for office work which will consists of
luminaries, electrical fans, computer desktops, laptops, scanner, printers and fax machines
etc.
But this will require huge area of rooftop which is not available and cost of project will rise
so high. Sub-Metering can be availed in utilization of solar energy with the help of Grid-Tied
Solar System which is capable of Net Metering option, this way system can feed back to grid
coming from solar PV modules even during the days of holidays or weekend.
The goal of this offer is to achieve more power from DC Solar PV, it is also comprehensive
and easy to understand as all relevant items and concepts are explained and accompanied
with data to backup. The financial offer is based on technical calculations listed overleaf.
“A” Block – Energy Audit | www.sharifinternational.net
Page 57 of 68
Financial Working – A Block Secretariat – Islamabad
15-kW Grid-Tied System
Sr. No.
1)
2)
3)
4)
5)
6)
7)
8)
9)
Item Description
InfiniSolar 10kw On-Grid Inverter with energy storage
Pure sine wave output
Self-consumption and Feed-in to the grid
Programmable supply priority for PV, Battery or Grid
User-adjustable battery charging current suits
different types of batteries
Programmable multiple operation modes: Grid-tie,
off-grid and grid-tie with backup
Built-in timer for various mode of on/off operation
Multiple communication for USB, RS-232, Modbus and
SNMP
Monitoring software for real-time status display and
control
Parallel operation up to 6 units for 5KW and 10KW
PV Modules 250W A-grade Poly Crystalline with 20
years warranty @ 80% efficiency.
PV Modules Frames in GI for each Panel, most
probably one Frame will consists of three 250W
panels in landscape mode.
Single Core DC Wire for 48V DC System, 16mm2 - 150
Meters Black + 150 Meters Red. Extra Cable to be
charged.
One Lot Small Items - Thimbles, Connectors,
breakers, ¾“ Flexible PVC Pipe Lengths, ON/OFF
Switches with back boxes, good quality elbows &
extenders, Spiral Pipe as required and ties etc.
Electrification,
Installation,
Testing
and
Commissioning of each site.
Transport to Site
IESCO Charges for Inspection & Net-Metering
Miscellaneous Balance of System Items
Qty
Rate (PKR)
1.00
315,500.00
Line Total
PKR
315,500.00
60.00
15,000.00
900,000.00
20.00
9,000.00
180,000.00
1.00
59,400.00
59,400.00
1.00
60,000.00
60,000.00
1.00
25,000.00
25,000.00
-
12,-,-,100.00
12,-,-,100.00
Grand Total in PKR Sharif International recommended
1,617,000
Table 27: Financial Working of Solar System Installation
The datasheets of the proposed equipment are given on the following pages
“A” Block – Energy Audit | www.sharifinternational.net
Page 58 of 68
Figure 42: Infini Inverter specifications
“A” Block – Energy Audit | www.sharifinternational.net
Page 59 of 68
Figure 43: Everexceed Solar PV Modules specifications
“A” Block – Energy Audit | www.sharifinternational.net
Page 60 of 68
Figure 44: Everexceed Solar PV Modules features
“A” Block – Energy Audit | www.sharifinternational.net
Page 61 of 68
Figure 45: Single Line Diagram of Solar system
5.2.2 Solar System Potential ROI Calculations
Tremendous amount of energy can be generated by availing the huge area of rooftop which
can be fed back to Grid and this system is explained above in details. However ROI
calculations are shared below with fruitful results with positive feasibility of Net-Metering
System.
“A” Block – Energy Audit | www.sharifinternational.net
Page 62 of 68
Upfront System
Cost
Rated Power (W)
10KW System
PV Power
PKR 1,617,000.0
250
Watts
PV Power Generate (Watt)
Total PV
Power
6
Hours/Day
Monthly
Annual
15,000 Watts
90,000
Wh
2,700,000
Wh
32,400,00
0
Wh
Revenue Generated (PKR)
ROI in years
Units Feed Back to Grid/Day
Units Earned @ Rs. 12.5
Annually
Return
90kWh units
Rs.1,125.00
405,000
4
Table 28: Financial Working of Solar System Installation
“A” Block – Energy Audit | www.sharifinternational.net
Page 63 of 68
5.3 Floor wise Sub-Metering
“A” Block Secretariat’s major concern was to monitor the whole electrical distribution
system in such a way that every floor show its own load in terms of Days and months in
comparison with other floors so that flow of power should be transparent to everyone
which will be a good practice to conserve your electrical energy.
However in this regard a separate survey was conducted and all distribution boards of
buildings were inspected once again in depth and finally come up with a Smart Energy
Analyzer system which will show floor wise power consumption through LCD on every floor
of a building.
Single line diagram of system is given below which mainly contains smart energy analyzer
with current transformers and LCD.
Figure 46: Single Line Diagram of Sub-Metering
“A” Block – Energy Audit | www.sharifinternational.net
Page 64 of 68
However financial feasibility of sub-metering system is also enlisted below with imported
goods which have already been installed by K Electric in few of their buildings.
Sub-Metering Financial Feasibility
S.No.
1
Description
CVM-C10 Power Analyzer, Model M55911, 3 Phase
Qty
12
Rate
40,000
Total
480,000
2
CVM-K2 Power Analyzer, Model M54400, 3 Phase
1
160,000
160,000
3
TCP1RS+, Model M62121
1
35,000
35,000
4
DB Box, communication wire
13
3,000
39,000
5
Power Studio Energy Management Software
1
300,000
300,000
6
CTs 100/5 Circutor Brand
39
4,000
156,000
Total amount of supply in PKR 1,170,000
GST 17% 198,900
Total Supply including Taxes in PKR
PKR
1,368,900
Table 29: Financial Working of Solar System Installation
Note:
Above Mention goods are imported and of Spain Origin. Please discuss before
withholding Sales tax and Income Tax.
“A” Block – Energy Audit | www.sharifinternational.net
Page 65 of 68
5.4 Water Conservation at “A” Block
A survey was carried out to review current operational water usage in sanitary ware at ABlock and develop basis for a demo project as part of Energy Audit activity with a focus on
Water Conservation using International Plumbing Code as green guideline. And from this
survey we analyzed that we can save tremendous amount of water in whole year. From the
below results it is very clear that how much water can be saved in different areas.
Figure 47: water saving per year by flush tanks
“A” Block – Energy Audit | www.sharifinternational.net
Page 66 of 68
Figure 48: water saving per year in ablution area
To obtain the desire results some of the recommendations in term of sanitary wares are
given below as per American standards.
Figure 49: Flush model with dimensions
“A” Block – Energy Audit | www.sharifinternational.net
Page 67 of 68
Figure 50: Flush model with dimensions
Figure 51: Taps model
“A” Block – Energy Audit | www.sharifinternational.net
Page 68 of 68